Advanced Settings
AC Disqualification Priority
The Freedom Sequence power manager is capable of detecting a compatible inverter/charger, such as the Freedom SW 2012 or the Freedom SW 3012, that is connected on the Xanbus network. Upon detection, it initiates inverter/charger interactive functions. The purpose of the AC Disq Priority is to tell the inverter/charger when a critical load circuit is disconnected due to an overload condition. Another purpose is to request the inverter/charger to stop drawing any current for charging or to stop powering the connected loads through the inverter/charger’s bypass circuit if its battery is at high battery level.
The AC Disq Priority is any number between 1 to 10. This priority number implies that, if an AC load with a circuit Priority number that is the same or less than the AC Disq Priority number is ever disconnected by Freedom Sequence due to an overload condition, then an “AC disqualify request” is sent to the inverter/charger and that request is sustained until the same AC load circuit gets reconnected somehow. The inverter/charger can either accept this request and disqualify its incoming AC or reject the request and keep drawing AC current.
For more information, see “Freedom Sequence Interaction with Other Xanbus Devices” on page 39.
By default, the factory setting is set to 2.
NOTE: This setting can only be modified when Mode is set to Standby.
To change the AC disqualification priority from the Advanced Settings screen:
FSPM 00: StatusFSPM 00: Status
L2 Amps | 0.0A | Batt Voltage |
| 12.8V |
Batt Voltage | 12.8V | Circuit Status |
| |
Circuit Status |
| Config |
|
|
Config |
| Advanced Settings |
| |
1 Press all three buttons to | 3 Press button. | 2 Scroll down to select | ||
enable Advanced Settings. |
|
| Advanced Settings. | |
FSPM 00: Advanced Settings | FSPM 00: Advanced Settings | |||
GEN BKR Rating | [30.0A] | GEN BKR Rating | [30.0A] | |
GEN Warmup Delay | [2sec] | GEN Warmup Delay | [2sec] | |
Connect Seq Delay | [5sec] | Connect Seq Delay | [5sec] | |
AC Disc Priority | [2] | AC Disc Priority | [*2] | |
5 Press to change | 4 Scroll down | 7 Press to | 6 Scroll up or down | |
the setting. |
| confirm the | to choose a value. | |
FSPM 00: Advanced Settings | selected |
|
| |
value. |
|
| ||
GEN BKR Rating | [30.0A] |
|
|
|
GEN Warmup Delay | [2sec] |
|
|
|
Connect Seq Delay | [5sec] |
|
|
|
AC Disc Priority | [1] |
|
|
|
|
| 25 |
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|