Advanced Settings

Connect Sequence Delay

Reconnect-delay Timer The Freedom Sequence power manager applies a reconnect-delay timer (Connect Seq Delay) before reconnecting an AC circuit that was previously disconnected due to a load shedding event. In other words, the reconnect-delay timer is applied before fully connecting to the power source again.

The reconnect-delay timer, which can be modified by changing the Connect Seq Delay, is set by default to ten seconds. The connect sequence delay value applies to all AC relays and can be set between 4 to 60 seconds.

By default, the factory setting is set to 10 seconds.

To change the Connect Seq Delay from the Advanced Settings screen:

FSPM 00: Status

 

 

FSPM 00: Status

 

L2 Amps

0.0A

 

Batt Voltage

12.8V

Batt Voltage

12.8V

 

Circuit Status

 

Circuit Status

 

 

Config

 

Config

 

 

 

Advanced Settings

 

 

 

 

 

 

 

1 Press all three buttons to

3 Press button.

2 Scroll down to select

enable Advanced Settings.

 

Advanced Settings.

Disconnect-delay Timer The disconnect-delay timer is programmed to two seconds and cannot be modified. This means that after an overload condition is detected, Freedom Sequence will wait for two seconds before disconnecting the load circuit controlled through that relay.

FSPM 00: Advanced Settings

GEN BKR Rating

[30.0A]

GEN Warmup Delay

[2sec]

Connect Seq Delay

[10sec]

AC Disc Priority

[2]

5 Press to change

4 Scroll down

the setting.

 

FSPM 00: Advanced Settings

GEN BKR Rating

[30.0A]

GEN Warmup Delay

[2sec]

Connect Seq Delay

[5sec]

AC Disc Priority

[2]

FSPM 00: Advanced Settings

GEN BKR

Rating

[30.0A]

GEN Warmup Delay

[2sec]

Connect

Seq Delay

[*10sec]

AC Disc

Priority

[2]

7 Press to 6 Scroll up or down confirm the to choose a value. selected

value.

 

 