Troubleshooting
Table 4-2 Error Messages
| Onboard Status Panel |
|
| |
Display | Indicator lights | Fault | Solution | |
|
|
|
| |
Hot | Green 100% indicator light | Battery too | Allow battery to cool. Improve ventilation | |
flashes | Hot Warning | or install in cooler location. It may | ||
| ||||
| Display green bank indicator |
| indicate a shorted cell in the battery or | |
| light for the affected battery |
| excessive water loss. If the temperature | |
| bank illuminated |
| increases, the XC Series will enter the | |
|
|
| fault level and stop charging the affected | |
|
|
| bank. | |
|
|
|
| |
Err | Red fault indicator light | Battery too | Allow battery to cool. Improve ventilation | |
illuminated | Hot Shutdown | or install in cooler location. It may | ||
Ht | ||||
Green 100% indicator light |
| indicate a shorted cell in the battery or | ||
|
| |||
| flashes |
| excessive water loss. | |
| Display green bank indicator |
|
| |
| light for affected battery bank |
|
| |
| illuminated |
|
| |
|
|
|
| |
|
| Cannot apply | The operation you have tried to execute | |
no |
| change | cannot be completed. | |
|
|
|
| |
Err | Red fault indicator light | No batteries | The charger did not detect any batteries. | |
illuminated | detected |
| ||
|
| |||
Bat |
|
|
| |
|
|
| ||
|
|