Indicator Light Flashing Sequences

Indicator Light Flashing Sequences

Table 4-1Indicator Light Sequences on the XC Series

 

Activity

Charger status

 

 

 

 

 

 

 

 

Charging indicator light illuminates

The unit is charging in bulk or absorption mode

 

 

 

 

 

Charging indicator light flashes

The unit is performing the equalization charge.

 

 

(Charging indicator light flashes once every four

 

 

seconds if bank 1 is being equalized, twice every

 

 

four seconds if bank 2 is being equalized, and

 

 

three times every four seconds if bank 3 is being

 

 

equalized)

 

 

 

 

 

 

 

 

Ready indicator light illuminates

The unit is either in float mode of three stage

 

 

charging or rest mode of two stage charging. All

 

 

batteries have been fully charged.

 

 

 

 

 

Fault indicator light illuminates

Any fault condition that prevents the charger from

 

 

charging one or more banks, but is not a charger

 

 

fault condition - remote display shows details of

 

 

fault. Example:

 

(battery reverse

 

 

err

ErrCHfBATPoL

 

 

polarity detected)

 

 

 

Fault indicator light flashes

Charger fault condition - remote display shows

 

 

followed by

. The charger is damaged,

 

 

contact service.

 

 

 

 

Charging current indicator lights

These lights indicate the charging current. At

 

illuminate

transition points when the current is changing, two

 

 

indicator lights may flash alternately, then settle

 

 

into the new charging current reading.

 

Charging current indicator lights

100% indicator light flashes to indicate battery

 

flash

temperature too high warning (> 50 °C, 122 °F)

 

 

10% indicator light flashes to indicate battery

 

 

temperature too low warning (< 0 °C, 32 °F)

 

 

25% indicator light flashes to indicate that a

 

 

battery has been disqualified (see page 3–4)

 

 

 

 

 

Charging current indicator lights

100% indicator light flashes to indicate battery

 

flash,

temperature too high fault (> 55 °C, 131 °F)

 

Fault indicator light illuminated

10% indicator light flashes to indicate battery

 

 

temperature too low fault (< -20 °C, -4 °F)

 

 

 

 

 

 

 

 

 

 

 

 

975-0187-01-01

 

 

4–3

Page 61
Image 61