SECTION II: DUCTWORK

DUCTWORK GENERAL INFORMATION

The duct system’s design and installation must:

1.Handle an air volume appropriate for the served space and within the operating parameters of the furnace specifications.

2.Be installed in accordance with standards of NFPA (National Fire Protection Association) as outlined in NFPA pamphlets 90A and 90B (latest editions), in Canada CAN/CSA-B139, Installation Code for Oil-Burning Equipment, or applicable national, provincial, or state, and local fire and safety codes.

3.For Manufactured (Mobile) Home and Modular Home Return Duct System Installations:

A return air duct and the return air plenum cannot be installed on this furnace. The return air is drawn through the louvers on the blower door. The vent system is a Sealed Combustion Direct Roof Jack Vent System. This is the ONLY vent system approved for use on this furnace.

4.Complete a path for heated or cooled air to circulate through the air conditioning and heating equipment and from the conditioned space.

5.Consideration should be given to the heating capacity required and also to the air quantity (CFM) required. These factors can be determined by calculating the heat loss and heat gain of the home or structure. If these calculations are not performed and the fur- nace is over-sized, the following may result:

a.Short cycling of the furnace.

b.Wide temperature fluctuations from the thermostat setting.

c.Reduced overall operating efficiency of the furnace.

On DFAA furnaces, the cooling coil must be installed in the bottom of the casing. DFAH furnaces must have the cooling coil installed downstream of the furnace. Cooled air may not be passed over the heat exchanger.

When the furnace is used in conjunction with a cooling coil, the coil must be installed parallel with, or in the supply air side of the furnace to avoid condensation in the primary heat exchanger. When a parallel flow arrangement is used, dampers or other means used to control airflow must be adequate to prevent chilled air from entering the furnace. If manually operated, the damper must be equipped with means to pre- vent the furnace or the air conditioner from operating unless the damper is in full heat or cool position.

The duct system must be properly sized to obtain the correct airflow for the furnace size that is being installed.

Refer to Table 8 and the furnace rating plate for the correct rise range and Table 4 for static pressures.

If the ducts are undersized, the result will be high duct static pres- sures and/or high temperature rises which can result in a heat exchanger OVERHEATING CONDITION. This condition can result in premature heat exchanger failure, which can result in personal injury, property damage, or death.

HAZARD OF ASPHYXIATION, DO NOT COVER OR RESTRICT FLOOR OPENING.

The duct system is a very important part of the installation. If the duct system is improperly sized, the furnace will not operate properly. The ducts attached to the furnace duct connector should be of sufficient size so that the furnace operates at the specified external static pres- sure and within the air temperature rise specified on the nameplate.

IMPORTANT: Fabricate and install an inspection door in the plenum base below the unit to allow an annual inspection of the heat exchang- ers. The inspection door can be fabricated by following method.

1.Cut a rectangular opening in the plenum base.

2.A Sheet metal plate can be made that completely covers the open- ing in the base.

3.The plate must be secured with screws.

4.This plate must be sealed to prevent leaks.

Table 2 is a guide for determining whether the rectangular duct system that the furnace is being connected to, is of sufficient size for proper fur- nace operation.

Unitary Products Group

5

Page 5
Image 5
York DFAA, DFAH Section II Ductwork, Ductwork General Information, Duct system’s design and installation must