Quadra-Fire 839-1460 Vent Information, Venting Components, Use of Elbows, Measuring Standards

Page 10

5 Vent Information

A. Venting Components

In order to comply with applicable codes and product warranties, use only following venting components:

Hearth & Home Technologies (HHT)

Security Chimney's Secure Vent Chimney System

Selkirk Metalbestos

AmeriVent

Simpson Dura-Vent (SDV)

DO NOT USE FIELD-FABRICATED VENTING COMPONENTS. Refer to the venting manufacturer’s

instructions.

This product is approved to be vented either horizontally, through the side wall or vertically through the roof. You may vent through a Class A or masonry chimney if an approved adapter is used.

This appliance is a direct vent heater. All combustion air must come directly from the outside of the building. The vent pipe for this unit consists of an inner and an outer pipe. The inner pipe carries the appliance exhaust out of the system, and the outer pipe brings fresh combustion air into the appliance.

A round support box/wall thimble or heat shield is required when the venting passes through a combus- tible wall.

A support box or ceiling firestop is required when the venting passes through a ceiling.

Roof flashing and a storm collar are required when vent- ing passes through the roof.

Follow instructions provided with the venting for instal- lation of these items.

B. Use of Elbows

CAUTION

ALL vent configuration specifications MUST be followed.

This product is tested and listed to these specifications.

Appliance performance will suffer if specifications are not followed.

Diagonal runs have both vertical and horizontal vent aspects when calculating the effects. Use the rise for the vertical aspect and the run for the horizontal aspect. (See Figure

5.1.)

Two 45° elbows may be used in place of one 90° elbow. On 45° runs, one foot of diagonal is equal to 8-1/2 in. (216mm) horizontal run and 8-1/2 in. (216mm) vertical run. A length of straight pipe is allowed between two elbows. (See Figure

5.1.)

Vertical

 

 

.

 

.

in

 

1/2

12

in

 

8

 

 

-

8-1/2 in.

Horizontal

Figure 5.1

WARNING

Fire Hazard. Explosion Risk. Asphyxiation Risk.

Do NOT connect this gas appliance to a chimney flue serving a separate solid-fuel or gas burning appliance.

Vent this appliance directly outside.

Use separate vent system for this appliance.

May impair safe operation of this appliance or other appliances connected to the flue.

C. Measuring Standards

Vertical and horizontal measurements were made using the following standards.

Pipe measurements are from center line to center line.

Horizontal terminations are measured to the outside of the mounting surface (flange of termination cap). See Figure 4.1 on page 8.

Vertical terminations are measured to the top of the last pipe before termination cap.

Horizontal pipe installed level with 1/4 in. rise.

Page 10

Quadra-Fire · Sapphire · 250-7233F

January 28, 2008

Image 10
Contents Quartet Front What to do if you smell gasSolitaire Front Do not Discard this ManualQuadra-Fire · Sapphire · 250-7233F January 28 Table of Contents 1Listing and Code Approvals BELOW. Keep Clear of ALL Obstructions Requirements for the Commonwealth of MassachusettsManufacturer Requirements Getting Started Tools and Supplies NeededSelecting Appliance Location Appliance Location and ClearancesClearances 4Termination Locations Vent Termination Minimum ClearancesAlcove Applications Use of Elbows Vent InformationVenting Components Measuring StandardsHow to Use the Vent Graph Venting Guidelines TOP Vent Graph Rear Venting with Vertical RiseHorizontal Termination Type B Rear Installations for Use with Rear Vent KitType a Up & Out Installations for Top Vent Configurations StepElbow in Corner Installation 203mm 178mm 152mm Vertical Termination Direct Vent PipeStep Twist-lock the vent cap and seal Cathedral Ceiling Class a Metal Chimney Existing Masonry Chimney Ft mCap Flex Liner Flex Coupler Sheet Metal Screws Fuel Conversions Gas InformationConverting to LP Gas Propane Natural GAS Gas Pressures PressureGas Connection Check for GAS LeaksStanding Pilot Ignition System Wiring Recommendation for WireConnecting to the Appliance Wire Size Max. LengthThermopile GAS Pilot Ignitor Thermocouple Top and Rear Vent Conversion Appliance SetupRemove Shipping Materials At the TOP of the appliance, with exceptions notedReplace Burner Orifice for Horizontal Vent Configurations Accessories Grille Cover Plate Installation059 53 DMS 096 41DMS For Both Quartet and Solitaire Fronts Front InstallationFronts are shipped attached to the face Quartet Door AlignmentPositioning the Logs Hearth Legs InstallationQty Description Mineral Wool Glass Door Assembly InstallationBlower Installation Blower from frontPage 26 Blower Wiring Diagram BlowerFor TOP or Rear Vent Installations Damper AdjustmentShutter Adjustment Make adjustmentBefore Lighting Appliance Operating InstructionsControls For Your Safety Read Before Lighting Lighting ApplianceInitial Break-in Procedure Frequently Asked QuestionsAfter Appliance is Lit Troubleshooting Symptom Possible Cause Corrective ActionBe Placed in this Opening Maintaining and Servicing Appliance After servicingMaintenance Tasks Inspect Necessary. USE Caution When CLEANING/HANDLING Ceramic BurnerService and Maintenance Log Date of Service Performed By Description of ServiceAppliance Dimension Diagram Reference MaterialsVent Components Diagram Vent Components List MiscellaneousRD. Service Parts List Item # DescriptionRD. Service Parts cont’d Service Parts cont’d Accessories Cast Parts Individual PiecesWarranty Policy This page Intentionally Left Blank January 28 Quadra-Fire · Sapphire · 250-7233E Contact Information SapphireDealer Telephone