Quadra-Fire 839-1460, SAPPH-D-CWL, 839-1390, SAPPH-D-CSB, 839-1440 owner manual Gas Pressures

Page 25

E

D

F

Figure 6.7 Ensure that the rubber gasket (D) is properly posi- tioned and install the new HI/LO pressure regulator assem- bly to the valve using the new screws (E) supplied with the kit. Tighten screws securely. (Reference torque = 25 in./lb.) Install the enclosed identification label (F) to the valve body where it can be seen.

Fill out the conversion label and attach it to the valve cover.

WARNING

Fire Risk.

Explosion Risk.

Gas Leak Risk.

Rubber gasket must be seated properly on valve face.

Do no install a valve or regulator that has been dropped.

WARNING

Fire Risk.

Explosion Risk.

If the information in these instructions is not followed exactly, a fire, explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life.

The qualified service agency is responsible for the proper installation of this conversion kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer’s instructions supplied with the kit.

B. Gas Pressures

Proper input pressures required for optimum appliance per- formance, gas line sizing requirements need to be followed from NFPA51.

WARNING

Fire Risk.

Explosion Hazard.

High pressure will damage valve.

Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1/2 psig.

Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1/2 psig.

WARNING

Verify inlet pressures.

High pressure may cause overfire condition.

Low pressure may cause explosion.

Verify minimum pressures when other household gas appliances are operating.

Install regulator upstream of valve if line pressure is greater than 1/2 psig.

Pressure requirements for appliance are shown in the table below.

PRESSURE

NG

LP

Minimum Inlet Pressure

4.5 inches w.c.

11.0 inches w.c.

Maximum Inlet Pressure

7.0 inches w.c.

14.0 inches w.c.

Manifold Pressure on “HI”

3.5 inches w.c.

10.0 inches w.c.

If the pressure is not sufficient, ensure:

1)the piping used is large enough.

2)the supply regulator is adequately adjusted.

3)that the total gas load for the residence does not exceed the amount supplied.

The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank) should supply gas at the suggested input pressure listed above. Contact the local gas supplier if the regulator is at an improper pressure.

January 28, 2008

Quadra-Fire · Sapphire · 250-7233E

Page 25

Image 25
Contents Solitaire Front What to do if you smell gasQuartet Front Do not Discard this ManualQuadra-Fire · Sapphire · 250-7233F January 28 Table of Contents 1Listing and Code Approvals BELOW. Keep Clear of ALL Obstructions Requirements for the Commonwealth of MassachusettsManufacturer Requirements Tools and Supplies Needed Getting StartedSelecting Appliance Location Appliance Location and ClearancesClearances Vent Termination Minimum Clearances 4Termination LocationsAlcove Applications Venting Components Vent InformationUse of Elbows Measuring StandardsTOP Vent Graph Rear Venting with Vertical Rise How to Use the Vent Graph Venting GuidelinesType a Up & Out Installations for Top Vent Configurations Type B Rear Installations for Use with Rear Vent KitHorizontal Termination StepElbow in Corner Installation 203mm 178mm 152mm Direct Vent Pipe Vertical TerminationStep Twist-lock the vent cap and seal Cathedral Ceiling Class a Metal Chimney Ft m Existing Masonry ChimneyCap Flex Liner Flex Coupler Sheet Metal Screws Fuel Conversions Gas InformationConverting to LP Gas Propane Natural GAS Pressure Gas PressuresCheck for GAS Leaks Gas ConnectionConnecting to the Appliance Recommendation for WireStanding Pilot Ignition System Wiring Wire Size Max. LengthThermopile GAS Pilot Ignitor Thermocouple Remove Shipping Materials Appliance SetupTop and Rear Vent Conversion At the TOP of the appliance, with exceptions notedReplace Burner Orifice for Horizontal Vent Configurations Accessories Grille Cover Plate Installation059 53 DMS 096 41DMS Fronts are shipped attached to the face Front InstallationFor Both Quartet and Solitaire Fronts Quartet Door AlignmentPositioning the Logs Hearth Legs InstallationQty Description Blower Installation Glass Door Assembly InstallationMineral Wool Blower from frontPage Blower 26 Blower Wiring DiagramShutter Adjustment Damper AdjustmentFor TOP or Rear Vent Installations Make adjustmentBefore Lighting Appliance Operating InstructionsControls Lighting Appliance For Your Safety Read Before LightingInitial Break-in Procedure Frequently Asked QuestionsAfter Appliance is Lit Symptom Possible Cause Corrective Action TroubleshootingBe Placed in this Opening After servicing Maintaining and Servicing ApplianceNecessary. USE Caution When CLEANING/HANDLING Ceramic Burner Maintenance Tasks InspectDate of Service Performed By Description of Service Service and Maintenance LogReference Materials Appliance Dimension DiagramVent Components Diagram Miscellaneous Vent Components ListItem # Description RD. Service Parts ListRD. Service Parts cont’d Service Parts cont’d Cast Parts Individual Pieces AccessoriesWarranty Policy This page Intentionally Left Blank January 28 Quadra-Fire · Sapphire · 250-7233E Contact Information SapphireDealer Telephone