Quadra-Fire SAPPH-D-CWL, 839-1460, 839-1390, 839-1440 How to Use the Vent Graph Venting Guidelines

Page 11

D. How to Use the Vent Graph

E. Venting Guidelines

1.Measure the distance from the top of appliance to the center of the 90° elbow. On the graph below, draw a horizontal line from that measurement on the vertical axis across until it intersects with the slanted line.

2.From the point of this intersection, draw a vertical line to the bottom of the graph.

3.The point at which this line meets the bottom line of the graph is the maximum length of the horizontal run.

Example 1: If the vertical dimension from the top of the appliance to the center of the 90° elbow is 7 ft. (2m), the horizontal run to the base of the temination cap must not exceed 13 ft.- 2 in. (4m).

Example 2: If the vertical dimension from the top of the appliance is 21 ft. (6m), the horizontal run to the base of the termination cap must not exceed 7 ft.- 3in. (2m).

4.Each 90° elbow is equivalent to 3 ft. (914mm) of vent pipe and each 45° elbow is equivalent to 1 ft. (305mm) of vent pipe, and must be subtracted from vent pipe run. A single vertical to horizontal 90° elbow is already calculated into the allowable 15 ft. (5m) run. Each additional 90° elbow reduces the maximum horizontal distance by 3 ft. (914mm).

Example: The use of 3 elbows would reduce the allowable horizontal run to 9 ft. (3 - 1 = 2 elbows x 3 ft. = 6 ft.; 15 ft. max. - 6 ft.= 9 ft. max.)

Notes: The maximum horizontal vent run is 15 ft. (5m) when the vertical vent rise is 10 ft. (3m).

The minimum horizontal vent run is 11 in. (279mm).

Minimum wall thickness is 4 in. (102mm). Maximum wall thickness is 20 in. (508mm).

Horizontal sections require a 1/4 in. (6mm) rise for every 12 in. (305mm) of horizontal travel.

Exterior Vent Diameter = 6-5/8 in. (168mm); Inner Vent Diameter = 4 in. (101mm).

Horizontal sections require noncombustible support every 3 ft. (914mm), e.g. plumbing tape.

EXCEPTION FOR REAR VENT KIT (Snorkel Kit #844-8921), HORIZONTAL INSTALLATION:

When installing the Sapphire in a rear vent configuration with no vertical rise: a snorkel kit must be used, and a derating orifice must be installed. The appropriate orifice is supplied with the rear vent kit.

For any vertical rise when rear venting, a minimum of 2 ft. (610mm) vertical must be used prior to any horizontal run.

The maximum horizontal vent run is 2 ft. (610mm).

The maximum horizontal vent run with a 45° elbow is 14 in. (356mm).

No external minimum rise is required. The minimum horizontal vent run is 11 in. (279mm).

NOTE: IF YOUR INSTALLATION FALLS WITHIN A SHADED AREA ON THE GRAPH, THE DAMPER MUST BE USED.

NOTE: In the Commonwealth of Massachusetts, the word damper shall be replaced with the words flue restrictor.

TOP VENT GRAPH

REAR VENTING WITH VERTICAL RISE

 

30'

 

 

 

 

 

 

 

 

 

30'

 

 

 

 

 

 

28'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28'

 

 

 

 

 

 

26'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26'

 

 

 

 

 

 

24'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EX. 2

 

 

 

 

 

 

 

 

 

24'

 

 

 

 

 

22'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20'

 

 

 

 

 

 

18'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VERTICAL DISTANCE

 

 

 

 

 

 

 

 

 

18'

 

 

 

 

 

16'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FROM APPLIANCE

14'

 

 

 

 

 

 

 

 

 

16'

 

 

 

 

 

TOP TO 90° ELBOW

 

 

 

 

 

 

 

 

 

14'

 

 

 

 

 

 

12'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EX. 1

10'

 

 

 

 

 

 

 

 

 

12'

 

 

 

 

 

8'

 

 

 

 

 

 

 

 

 

10'

 

 

 

 

 

 

6'

 

 

 

 

 

 

 

 

 

8'

 

 

 

 

 

 

4'

 

 

 

 

 

 

 

 

 

6'

 

 

 

 

 

 

2'

 

 

 

 

 

 

 

 

 

4'

 

 

 

 

 

 

0'

11"

2'

4'

6'

8'

10'

12'

14'

15'

2'

 

 

 

 

 

 

(MIN)

 

 

 

 

 

 

(MAX)

0'

 

 

 

 

 

 

 

 

TOTAL HORIZONTAL RUN TO BASE OF THE

 

2'

4'

6'

8'

10'

 

 

 

 

 

 

 

 

TERMINATION CAP (EXCLUDING ELBOWS)

 

(MIN)

 

 

 

 

(MAX)

Figure 5.2

January 28, 2008

Quadra-Fire · Sapphire · 250-7233E

Page 11

Image 11
Contents Do not Discard this Manual What to do if you smell gasSolitaire Front Quartet FrontQuadra-Fire · Sapphire · 250-7233F January 28 Table of Contents 1Listing and Code Approvals Manufacturer Requirements Requirements for the Commonwealth of MassachusettsBELOW. Keep Clear of ALL Obstructions Tools and Supplies Needed Getting StartedClearances Appliance Location and ClearancesSelecting Appliance Location Vent Termination Minimum Clearances 4Termination LocationsAlcove Applications Measuring Standards Vent InformationVenting Components Use of ElbowsTOP Vent Graph Rear Venting with Vertical Rise How to Use the Vent Graph Venting GuidelinesStep Type B Rear Installations for Use with Rear Vent KitType a Up & Out Installations for Top Vent Configurations Horizontal TerminationElbow in Corner Installation 203mm 178mm 152mm Direct Vent Pipe Vertical TerminationStep Twist-lock the vent cap and seal Cathedral Ceiling Class a Metal Chimney Ft m Existing Masonry ChimneyCap Flex Liner Flex Coupler Sheet Metal Screws Converting to LP Gas Gas InformationFuel Conversions Propane Natural GAS Pressure Gas PressuresCheck for GAS Leaks Gas ConnectionWire Size Max. Length Recommendation for WireConnecting to the Appliance Standing Pilot Ignition System WiringThermopile GAS Pilot Ignitor Thermocouple At the TOP of the appliance, with exceptions noted Appliance SetupRemove Shipping Materials Top and Rear Vent ConversionReplace Burner Orifice for Horizontal Vent Configurations 059 53 DMS 096 41DMS Grille Cover Plate InstallationAccessories Quartet Door Alignment Front InstallationFronts are shipped attached to the face For Both Quartet and Solitaire FrontsQty Description Hearth Legs InstallationPositioning the Logs Blower from front Glass Door Assembly InstallationBlower Installation Mineral WoolPage Blower 26 Blower Wiring DiagramMake adjustment Damper AdjustmentShutter Adjustment For TOP or Rear Vent InstallationsControls Operating InstructionsBefore Lighting Appliance Lighting Appliance For Your Safety Read Before LightingAfter Appliance is Lit Frequently Asked QuestionsInitial Break-in Procedure Symptom Possible Cause Corrective Action TroubleshootingBe Placed in this Opening After servicing Maintaining and Servicing ApplianceNecessary. USE Caution When CLEANING/HANDLING Ceramic Burner Maintenance Tasks InspectDate of Service Performed By Description of Service Service and Maintenance LogReference Materials Appliance Dimension DiagramVent Components Diagram Miscellaneous Vent Components ListItem # Description RD. Service Parts ListRD. Service Parts cont’d Service Parts cont’d Cast Parts Individual Pieces AccessoriesWarranty Policy This page Intentionally Left Blank January 28 Quadra-Fire · Sapphire · 250-7233E Dealer Telephone SapphireContact Information