Briggs & Stratton Power Products Home Generator System
Owners Manual
A switch on the control panel is labeled “Set Exercise” (depicted on page 10).The specific day and the specific time of day this switch is pressed is programmed into the control board memory.This date and time is then used to automatically initiate the system exercise cycle.
To perform the Set Exercise procedure:
1.Choose the day and time you want your Home Generator System to exercise.
2.On that day and time, set the AUTO/OFF/MANUAL switch to OFF.
3.Press and hold down the “Set Exercise” switch until the Diagnostic LED turns on (about five seconds).
4.Hold the switch down until the Diagnostic LED turns off. Release the Set Exercise switch.
5.Set the AUTO/OFF/MANUAL switch to AUTO. “Set Exercise” is complete.
For example, if you press the “Set Exercise” switch on Sunday morning at 10:00 AM, the unit will run an exercise cycle the following Sunday at 10:00 AM.
NOTE: “Set Exercise” will only work if the unit is in the Automatic mode and this exact procedure is followed.The exerciser does not need to be
If you want to change the day and time the unit exercises, simply perform the “Set Exercise” procedure at the exact weekday and time you want it to take place.
SPECIFICATIONS
Generator
Model . . . . . . . . . . . . . . . . . . . .
Rated Maximum Power (LP*). . . 10.0 kW
Rated Maximum Load Current:
at 240 Volts . . . . . . . . . . . . . . . 41.7 Amps
at 120 Volts . . . . . . . . . . . . . . . 83.3 Amps
Rated AC Voltage . . . . . . . . . . . . 120/240 Volts Rated Frequency . . . . . . . . . . . . 60 Hz at 3600 rpm Phase . . . . . . . . . . . . . . . . . . . . . Single Phase Power Factor . . . . . . . . . . . . . . . 1.0
NG Fuel Supply Pressure. . . . .
LP Fuel Supply Pressure. . . . . .
Normal Operating Range . . . .
Output Sound Level . . . . . . . . 70 dB(A) at 23 ft. (7 m) at full load
Shipping Weight . . . . . . . . . . . . 482 lbs.
*Natural gas rating will depend on specific fuel but typical derates are between 10 to 20% off the LP gas rating.
Transfer Switch
Maximum Circuits . . . . . . . . . . . 10
Maximum Load/Circuit:
from Generator . . . . . . . . . . . 41.7 Amps from Load Center. . . . . . . . . . 50 Amps
Maximum Watts . . . . . . . . . . . . . 10,000