Briggs & Stratton 01648-1 Ground Fault Protection, Testing the GFCI, PowerBOSS, Operation

Page 12
Ground Fault Protection

PowerBOSS™

4500W Portable Generator

OPERATION

 

 

 

Ground Fault Protection

The duplex receptacles are equipped with Ground Fault Circuit Interrupter (GFCI) protection.This device meets applicable federal, state and local codes.The generator’s locking receptacle is not protected by a GFCI.

The GFCI protects against electrical shock that may be caused if your body becomes a path in which electricity travels to reach the ground.This could happen if you touch a “Live” appliance or wire, or are touching plumbing or other materials that connect to the ground.

When protected by a GFCI, one may still feel a shock, but the GFCI should cut current off quickly enough so that a person in normal health should not suffer any serious electrical injury.

Generator produces hazardous voltage/current. WARNING

Generator produces hazardous voltage/current.

Contact with the hot and neutral conductor at the same time can cause electrical shock or burn, even if the circuit is GFCI protected.

Before using the GFCI receptacle,ALWAYS push the test button to insure it works.

Testing the GFCI

Test your GFCI outlet prior to each use, as follows:

Push the black “Test” button.The red “Reset” button should pop out, which should allow no power to reach the outlet. Use a test lamp in each outlet to test this.

Testing the GFCI CAUTION

The “Reset” button does not pop out or the test lamp remains lit when the “Reset” button is popped out.

DO NOT use any outlets on the circuit.

Call or take your generator to a local service center.

If the GFCI tests good, restore power by pressing the

Reset” button firmly until it is fully in place and locks in that position. If the GFCI outlet does not reset properly, do not use the outlet. Call or take your generator to a local service center.

If the GFCI trips by itself at any time, reset and test the outlet. If the reset button does not pop out when the test button is pressed, do not use the outlet. Call or take your generator to a local service center.

12

Image 12
Contents Model / Modelo 01648-1 4500W ADVERTENCIABRIGGS & STRATTON POWER PRODUCTS GROUP, LLC Operator’s Manual Manual del OperarioTABLE OF CONTENTS SAFETY RULESHazard Symbols and Meanings PowerBOSSSAFETY RULES Battery electrolyte fluid contains acid and is extremely causticContact with battery fluid will cause severe chemical burns Generator produces powerful voltageBroken bones, fractures, bruises or sprains could result Severe burns can occur on contactUnintentional sparking can result in fire or electric shock Excessively low speeds impose a heavy loadFEATURES AND CONTROLS KNOW YOUR GENERATOROil Fill 120/240 Volt AC 30 Amp Receptacle Idle Control Switch Recoil Starter Fuel Valve Air Cleaner Choke LeverASSEMBLY Install Wheel KitASSEMBLY Unpacking the GeneratorBEFORE STARTING THE ENGINE Add Engine OilAdd Fuel USING THE GENERATOR Connecting to a Building’s Electrical SystemSystem Ground Generator LocationConnecting Electrical Loads OPERATING THEGENERATOR Starting the EngineCharging a Battery Stopping the EngineOperating Automatic Idle Control RECEPTACLES 120/240 Volt AC, 30 Amp, Locking Receptacle120 Volt AC, 20 Amp, GFCI Duplex Receptacles 12 Volt DC, 10 Amp ReceptacleGround Fault Protection Testing the GFCIGenerator produces hazardous voltage/current COLD WEATHER OPERATION Creating a Temporary Cold Weather ShelterCreating a Permanent Cold Weather Shelter Power Management DONT OVERLOAD GENERATORCapacity SPECIFICATIONS GENERAL MAINTENANCE RECOMMENDATIONSEngine Maintenance Maintenance MinderGenerator Cleaning STORAGEGenerator Storage Other Storage TipsTROUBLESHOOTING TROUBLESHOOTINGProblem CausePowerBOSS BRIGGS & STRATTON POWER PRODUCTS GROUP, LLC JEFFERSON, WI, USA Consumer Use2 years Commercial UseCONSERVE ESTAS INSTRUCCIONES TABLA DE CONTENIDOSDESCRIPCIÓN DEL EQUIPO REGLAS DE SEGURIDADPELIGRO REGLAS DE SEGURIDADUna pequeña chispa puede encender el hidrógeno y causar una explosión Usted puede quedar ciego o sufrir heridas muy gravesPRECAUCIÓN Como resultado, podrían producirse fracturas, contusiones o esguincesQuemaduras severas pueden ocurrir al hacer contacto CUANDO AJUSTE O HAGA REPARACIONES A SU GENERADORPOWERBOSS CONOZCA SU GENERADORCARACTERÍSTICAS Y CONTROLES MONTAJE MONTAJEDesembalaje del Generador Instale el Juego de RuedasANTES DE DARLE ARRANQUE AL MOTOR Agregar Aceite al MotorAgregue Combustible CUANDO AÑADA COMBUSTIBLEUSO DEL GENERADOR OPERACIÓNTierra del Sistema Conexión al Sistema Eléctrico de un EdificioOPERANDO EL GENERADOR Encienda el MotorConexion De Cargas Electricas Figura 15 - Válvulas de CombustibleParado Del Motor Funcionamiento del Control Automatico de Marcha en VacioCarga de la Bateria NO SOBRECARGUE EL GENERADOR.Vea No Sobrecargue GeneradorRECEPTÁCULOS PRECAUCIÓN 120/240 Voltios AC, 30 Amp, Receptáculo de Seguridad120 Volt AC, 20 Amp, GFCI Receptáculos Dobles Tomacorrientes de 12 Voltios DCProtección Contra Fallos de Conexión a Tierra Comprobación del GFCIEl generador produce niveles de tensión/corriente peligrosos OPERACIÓN DURANTE UN CLIMA FRÍO Creación de una Clima Frío Estructura de Protección ProvisionalCreación de una Clima Frío Estructura de Protección Permanente Figura 21 - Clima Frío Estructura de ProtecciónNO SOBRECARGUE GENERADOR CapacidadControl de la Energía EjemploESPECIFICACIONES RECOMENDACIONES GENERALES DE MANTENIMIENTOMANTENIMIENTO Mantenimiento del MotorALMACENAMIENTO ALMACENAMIENTOPara Limpiar el Generador Almacenando el GeneradorDIAGNOSITICOS DE AVERÍAS DIAGNOSITICOS DE AVERÍASEl motor está funcionando pero no existe salida de AC disponsibleBRIGGS & STRATTON POWER PRODUCTS GROUP, LLC JEFFERSON, WI, EE.UU BRIGGS & STRATTON POWER PRODUCTS GROUP, LLCUso del consumidor Uso comercial