CONTROL PANEL OPERATION

AND FUNCTION

A.MASTER CONTROL SWITCH This switch controls the starting and stopping of the engine via the engine control logic circuitry.

With this switch in the “Manual” mode, the engine will start and run immediately after a 10 – 20 second time delay.

CAUTION: Please note that once the engine has been told to start, the gen set should be treated as though it is operational, even though the start delay has not yet allowed the engine to crank.

With this switch in the “Automatic” mode, the engine can be started and stopped from a remote contact. (Standard switch, transfer switch, etc.) There is a time delay, to cool down, of 60–90 seconds when the unit is shut down from the remote contacts while the Master Control Switch is in the “Automatic Mode.

With this switch in the “Off” position, the engine will immediately stop. The position must also be utilized to clear fault shut–down conditions.

B.PANEL LIGHTS – By turning on the panel light switch, the panel lights will be energized and will illuminate the control panel. The fuse next to the switch is to protect this circuit from damage due to excessive current.

C.FIELD AND CONTROLLER FUSES – These fuses protect the internal workings of the generator set.

D.GAUGES – These gauges monitor some of the more critical operating parameters of the engine as well as the run time of the generator set.

The Voltmeter displays the charging rate that is currently being produced by the engine’s alternator to facilitate the charging of the battery. This gauge should normally be above 12.5V whenever the unit is running. If you ever notice the gauge is reading below 12V while the engine is running please contact the service department at Baldor Generators.

The Temperature Gauge monitors and displays the operating temperature of the engines coolant. The point at which a fault shut–down will occur is approximately 230° F.

The Oil Pressure Gauge displays and monitors the current operating pressure of the engine’s oil

system. The trip point at which a fault shutdown will occur is approximately 15 PSI or below.

Fuel level is checked by the owner or is usually a separately supplied fuel tank.

The Hour Meter accumulates and displays the total running time of the generator set.

11

Image 14
Contents Baldor Generators Towables OPERATOR’S ManualPage Safety Warnings FORM# S-PSG-001-3 ```` for Gasoline or Diesel Powered Generator Sets ```` Page Forward \ISO9001\FORMS\SCSD0037.MSW Features & Specifications Page Switchable Connection Information Control Panel Operation Function Page Page Operation PRE-START Procedure Operation Starting Operation Cranking Control Troubleshooting Generator LOW VoltageOverheating Fluctuating VoltageHigh Voltage Generator Frame Produces Shock When Touched Mechanical NoiseTroubleshooting Engine Page Magnaplus Generator Table of Contents Specifications Parts List Single Bearing Unpacking and Handling SafetyReceiving and Storage StoragePrinciples of Operation PMG optionalNonlinear Loading InstallationParallel Operation Preparation for USETorsional Vibration END Play TestingGenerator Mounting Wiring Connections Environmental ConsiderationsLOW WYE Connection Double Delta -- Single Phase Connection START-UP OperationPRE-START Inspection Maintenance Shutdown ProcedureTesting Drying WindingsGeneral ServiceDiode Testing Field FlashingBearing Replacement Bearing RemovalTroubleshooting Returned GoodsGenerator Produces no Voltage Generator Produces LOW VOLTAGE, no LoadGenerator Produces High Voltage Generator Produces LOW Voltage When Load AppliedGenerator Produces Fluctuating Voltage Generator is Overheating Generator Produces Mechanical NoiseSpecifications Parts List Single Bearing Parts List Dual Bearing Rules for Safe Trailer Operation Towing VehicleElectrical Trailer Wiring Towing Heavy Trailer LoadsSafety Checks Trailer Light KIT Wiring Instructions Trailer Light Mounting and ConnectionLimited Warranty Owner’s Responsibilities Page California Proposition 65 Warning