TROUBLESHOOTING – GENERATOR

As with any machine, trouble may develop in electrical generators. It may be due to long service or neglect of regular maintenance. Servicing, and checking. Should trouble develop, the follow- ing instructions will be helpful in tracing the cause and making repairs.

SPEED DEVIATIONS:

The generator speed should be maintained at rated nameplate speed. The frequency and volt- age of the generator output depends on speed. If the generator runs slower than rated speed, the voltage will drop off.

NO VOLTAGE

 

CAUSE

CHECK AND REMEDY

Loss of residual magnetism in

Flash Field.

exciter field poles.

 

Open in stator windings

Check for continuity in windings. Return to factory

 

for repair if open

Open or short in rotating rectifiers.

Check rectifiers.

Short Circuited.

Clear lead to restore voltage build–up.

Open in alternator field

Check for continuity and return rotor to factory for

 

repair if field coils are open.

Shorted exciter armature

Check for short and replace if faulty.

Shorted leads between exciter

Test and repair

armature and generator field.

 

LOW VOLTAGE

CAUSE

CHECK AND REMEDY

Excessive load.

Reduce load. With 3 phase generators, the load on

 

each leg should be as evenly balanced as possible

 

and should not exceed the rated current on any leg.

Low Speed.

Check engine for malfunction or system for over-

 

load.

Line loss.

Increase size of line lead wire.

18

Image 21
Contents Baldor Generators OPERATOR’S Manual TowablesPage Safety Warnings FORM# S-PSG-001-3 ```` for Gasoline or Diesel Powered Generator Sets ```` Page Forward \ISO9001\FORMS\SCSD0037.MSW Features & Specifications Page Switchable Connection Information Control Panel Operation Function Page Page Operation PRE-START Procedure Operation Starting Operation Cranking Control LOW Voltage Troubleshooting GeneratorFluctuating Voltage High VoltageOverheating Mechanical Noise Generator Frame Produces Shock When TouchedTroubleshooting Engine Page Magnaplus Generator Table of Contents Specifications Parts List Single Bearing Receiving and Storage SafetyUnpacking and Handling StoragePMG optional Principles of OperationParallel Operation InstallationNonlinear Loading Preparation for USEEND Play Testing Generator MountingTorsional Vibration Environmental Considerations Wiring ConnectionsLOW WYE Connection Double Delta -- Single Phase Connection Operation PRE-START InspectionSTART-UP Shutdown Procedure MaintenanceDrying Windings TestingDiode Testing ServiceGeneral Field FlashingBearing Removal Bearing ReplacementReturned Goods TroubleshootingGenerator Produces LOW VOLTAGE, no Load Generator Produces no VoltageGenerator Produces LOW Voltage When Load Applied Generator Produces Fluctuating VoltageGenerator Produces High Voltage Generator Produces Mechanical Noise Generator is OverheatingSpecifications Parts List Single Bearing Parts List Dual Bearing Towing Vehicle Rules for Safe Trailer OperationTowing Heavy Trailer Loads Electrical Trailer WiringSafety Checks Trailer Light Mounting and Connection Trailer Light KIT Wiring InstructionsLimited Warranty Owner’s Responsibilities Page California Proposition 65 Warning