SWITCHABLE

ELECTRICAL CONNECTION INFORMATION

WARNING: High voltage may be present at receptacles and load studs while engine is operating – DANGER of electrical shock is present. Use extreme care.

LOAD RECEPTACLES

1.Voltage is present in 120/240 volt switch position only.

2.Load wires may be brought into receptacle compartment through access door at control station.

HARD WIRE LOAD TERMINAL BLOCK

1.Voltage available at load block is outlined in chart below.

2.Cables must be brought into load block compartment through access hole in base of trailer.

3.Opening load block door will cause load disconnect to trip.

4.Do not start engine with load turned “on”. Allow engine to come up to speed and warm up (1).

5.If left unattended, lock all doors to prevent tampering or injury.

AVAILABLE VOLTAGE:

 

SWITCH POSITION

STUD

277/480

1–2–3 = 480 VAC, 3 Phase

 

1–N, 2–N, 3–N = 277 VAC, 1 Phase

120/240

1–2–3 = 240 VAC, 3 Phase

 

2–3 = 240 VAC, 1 Phase

 

2–N, 3–N = 120 VAC, 1 Phase

 

1–N = 180 – 200 VAC, Wild Leg

120/208

1–2–3 = 208 VAC, 3 Phase

 

2–3 = 208 VAC, 1 Phase

 

1–N, 2–N, 3–N = 120 VAC, 1 Phase

 

 

NOTE: To prevent damage to loads and generator, select voltage switch position prior to starting engine.

NOTE: Upon switching voltage selector switch, adjust voltage and adjust rheostat (located on engine control panel) for proper voltage.

Revised: October 3, 2002

D:\ISO9001\FORMS\MSW’98bbk

Effective: April 23, 1999

 

Form#: S–PSG–001–15

 

9

Image 12
Contents Baldor Generators Towables OPERATOR’S ManualPage Safety Warnings FORM# S-PSG-001-3 ```` for Gasoline or Diesel Powered Generator Sets ```` Page Forward \ISO9001\FORMS\SCSD0037.MSW Features & Specifications Page Switchable Connection Information Control Panel Operation Function Page Page Operation PRE-START Procedure Operation Starting Operation Cranking Control Troubleshooting Generator LOW VoltageFluctuating Voltage High VoltageOverheating Generator Frame Produces Shock When Touched Mechanical NoiseTroubleshooting Engine Page Magnaplus Generator Table of Contents Specifications Parts List Single Bearing Safety Receiving and StorageUnpacking and Handling StoragePrinciples of Operation PMG optionalInstallation Parallel OperationNonlinear Loading Preparation for USEEND Play Testing Generator MountingTorsional Vibration Wiring Connections Environmental ConsiderationsLOW WYE Connection Double Delta -- Single Phase Connection Operation PRE-START InspectionSTART-UP Maintenance Shutdown ProcedureTesting Drying WindingsService Diode TestingGeneral Field FlashingBearing Replacement Bearing RemovalTroubleshooting Returned GoodsGenerator Produces no Voltage Generator Produces LOW VOLTAGE, no LoadGenerator Produces LOW Voltage When Load Applied Generator Produces Fluctuating VoltageGenerator Produces High Voltage Generator is Overheating Generator Produces Mechanical NoiseSpecifications Parts List Single Bearing Parts List Dual Bearing Rules for Safe Trailer Operation Towing VehicleElectrical Trailer Wiring Towing Heavy Trailer LoadsSafety Checks Trailer Light KIT Wiring Instructions Trailer Light Mounting and ConnectionLimited Warranty Owner’s Responsibilities Page California Proposition 65 Warning