Baldor TS25, BALDOR GENERATORS, TS45, TS80, TS175, TS130 manual Maintenance, Shutdown Procedure

Page 37

6.The purpose of this initial test with the regulator out of the circuit is to detect any wiring mistakes without exposing the unit to undue risk. Check all line to line and line to neutral voltages for balanced voltage. If voltages are balanced shut down the set and reconnect the regulator. If voltages are unbalanced, shut down the equipment and check for improper wiring. If the problem persists, consult the factory.

With the regulator de-energized, the residual voltage should be 10 - 25% of rated value. It is recommended that this residual voltage and driver RPM be recorded for use as a future troubleshooting benchmark.

WARNING

QUALIFIED ELECTRICAL PERSONNEL MUST CONDUCT THE FOLLOWING TEST. LETHAL VOLTAGE MAY BE PRESENT AT BOTH THE GENERATOR AND VOLTAGE REGULATOR TERMINALS DURING THIS PROCEDURE. CAUTION MUST BE EXERCISED NOT TO COME INTO PERSONAL CONTACT WITH LIVE TERMINALS, LINKS, OR STUDS. SERIOUS INJURY OR DEATH COULD RESULT.

7.Start the set and adjust the terminal voltage to the desired value by means of the regulator voltage adjustment. If the regulator is equipped with a stability adjustment, follow the instructions in the regulator manual to adjust the stability. Again, check all line to line and line to neutral voltages for balance. It is recommended practice to record the no load excitation (DC voltage to the exciter stator), generator terminal voltage, and driver speed as a benchmark for future troubleshooting.

8.Close the main circuit breaker to the load.

9.Monitor the generator output current to verify that it is at or below nameplate value.

10.Check generator speed (frequency) under load. Adjust as necessary. (Refer to prime mover or governor manuals)

SHUTDOWN PROCEDURE

There are no specific instructions for shutting down the generator; however, several good practices should be observed to prolong equipment life.

1.It is advisable to disconnect all loads (open main circuit breaker or disconnect) prior to shutdown. This is especially important if loads can be damaged by low voltage or low frequency conditions during generator "coast down".

2.Isolate all conditions that could apply voltage to the generator terminals while the generator is at rest. Failure to comply could result in personnel injury or equipment damage.

12

3.If the unit is equipped with space heaters, verify that the heater circuit is energized.

MAINTENANCE

The following maintenance procedures should be followed to ensure long equipment life and satisfactory performance. Maintenance intervals will depend upon operating conditions.

1.Routinely check intake and exhaust air screens to ensure that they are clean and free of debris. Clogged intake air screens will reduce cooling airflow and result in higher operating temperatures. This will reduce generator life and may result in generator damage.

2.All MagnaPLUS generators are equipped with double shielded ball bearings lubricated for the life of the bearing. Every 1,000 hours check the bearing(s) for

smooth, quiet operation. For continuous duty generators, recommended practice is to replace the bearing during major overhauls of the engine.

3.Periodically inspect the unit for any buildup of contamination (dirt, oil, etc.) on the windings. If the wound components have become coated with heavy concentrations of oil and grime, the unit should be disassembled and thoroughly cleaned. This operation is not one that can be accomplished effectively on site, but rather one that should be conducted by an authorized service center equipped with the appropriate apparatus and solvents necessary to properly clean and dry the generator.

WARNING

QUALIFIED ELECTRICAL PERSONNEL MUST CONDUCT THE FOLLOWING TEST. LETHAL VOLTAGE MAY BE PRESENT AT BOTH THE GENERATOR AND VOLTAGE REGULATOR TERMINALS DURING THIS PROCEDURE. CAUTION MUST BE EXERCISED NOT TO COME INTO PERSONAL CONTACT WITH LIVE TERMINALS, LINKS, OR STUDS. SERIOUS INJURY OR DEATH COULD RESULT.

4.Every 2,000 operating hours or in conjunction with scheduled engine maintenance check the DC no load excitation voltage per item #7 in the startup procedure. Compare this voltage with the value recorded during initial startup. If this value of no load excitation voltage is markedly higher than the benchmark reading, it is an indication of problems in the exciter, main field, or the rotating rectifier assembly. Ensure that RPM is the same as initial test.

5.Monitor and record insulation resistance with a 500 volt mega-ohm meter. The minimum acceptable reading is 2 mega-ohms. If the reading drops below the minimum, the generator should be cleaned and dried at an authorized service shop. Consult Marathon Electric for more information.

Image 37
Contents Baldor Generators OPERATOR’S Manual TowablesPage Safety Warnings FORM# S-PSG-001-3 ```` for Gasoline or Diesel Powered Generator Sets ```` Page Forward \ISO9001\FORMS\SCSD0037.MSW Features & Specifications Page Switchable Connection Information Control Panel Operation Function Page Page Operation PRE-START Procedure Operation Starting Operation Cranking Control LOW Voltage Troubleshooting GeneratorHigh Voltage Fluctuating VoltageOverheating Mechanical Noise Generator Frame Produces Shock When TouchedTroubleshooting Engine Page Magnaplus Generator Table of Contents Specifications Parts List Single Bearing Receiving and Storage SafetyUnpacking and Handling StoragePMG optional Principles of OperationParallel Operation InstallationNonlinear Loading Preparation for USEGenerator Mounting END Play TestingTorsional Vibration Environmental Considerations Wiring Connections LOW WYE Connection Double Delta -- Single Phase Connection PRE-START Inspection OperationSTART-UP Shutdown Procedure MaintenanceDrying Windings TestingDiode Testing ServiceGeneral Field FlashingBearing Removal Bearing ReplacementReturned Goods TroubleshootingGenerator Produces LOW VOLTAGE, no Load Generator Produces no VoltageGenerator Produces Fluctuating Voltage Generator Produces LOW Voltage When Load AppliedGenerator Produces High Voltage Generator Produces Mechanical Noise Generator is OverheatingSpecifications Parts List Single Bearing Parts List Dual Bearing Towing Vehicle Rules for Safe Trailer OperationTowing Heavy Trailer Loads Electrical Trailer WiringSafety Checks Trailer Light Mounting and Connection Trailer Light KIT Wiring InstructionsLimited Warranty Owner’s Responsibilities Page California Proposition 65 Warning