Baldor TS130, BALDOR GENERATORS Mechanical Noise, Generator Frame Produces Shock When Touched

Page 23

 

OVERHEATING (continued)

CAUSE

CHECK AND REMEDY

High room temperature.

Improve ventilation.

Insufficient circulation.

Provide cross–ventilation.

Low power factory.

Reduce inductive loads or install power factor im-

 

provement capacitors.

Unbalanced load

The load on each leg should be as evenly balanced

 

as possible and should not exceed the rated cur-

 

rent on any leg.

Dry bearing.

Replace bearing.

 

MECHANICAL NOISE

CAUSE

CHECK AND REMEDY

Defective bearing.

Replace bearing.

Rotor scrubbing on stator.

Bad bearing; replace. Bent shaft, return to factory.

 

Loosen end bell, tighten; loose drive discs, tighten.

Loose laminations.

Return to factory.

Loose or misaligned coupling.

Tighten or align.

GENERATOR FRAME PRODUCES SHOCK WHEN TOUCHED

CAUSE

CHECK AND REMEDY

Static charge.

Ground generator frame.

Grounded armature or field coil.

Return to factory for repair.

20

Image 23
Contents Baldor Generators OPERATOR’S Manual TowablesPage Safety Warnings FORM# S-PSG-001-3 ```` for Gasoline or Diesel Powered Generator Sets ```` Page Forward \ISO9001\FORMS\SCSD0037.MSW Features & Specifications Page Switchable Connection Information Control Panel Operation Function Page Page Operation PRE-START Procedure Operation Starting Operation Cranking Control LOW Voltage Troubleshooting GeneratorOverheating Fluctuating VoltageHigh Voltage Mechanical Noise Generator Frame Produces Shock When TouchedTroubleshooting Engine Page Magnaplus Generator Table of Contents Specifications Parts List Single Bearing Storage SafetyReceiving and Storage Unpacking and HandlingPMG optional Principles of OperationPreparation for USE InstallationParallel Operation Nonlinear LoadingTorsional Vibration END Play TestingGenerator Mounting Environmental Considerations Wiring ConnectionsLOW WYE Connection Double Delta -- Single Phase Connection START-UP OperationPRE-START Inspection Shutdown Procedure MaintenanceDrying Windings TestingField Flashing ServiceDiode Testing GeneralBearing Removal Bearing ReplacementReturned Goods TroubleshootingGenerator Produces LOW VOLTAGE, no Load Generator Produces no VoltageGenerator Produces High Voltage Generator Produces LOW Voltage When Load AppliedGenerator Produces Fluctuating Voltage Generator Produces Mechanical Noise Generator is OverheatingSpecifications Parts List Single Bearing Parts List Dual Bearing Towing Vehicle Rules for Safe Trailer OperationTowing Heavy Trailer Loads Electrical Trailer WiringSafety Checks Trailer Light Mounting and Connection Trailer Light KIT Wiring InstructionsLimited Warranty Owner’s Responsibilities Page California Proposition 65 Warning