OPERATION

The prime mover utilized in this power generating system is controlled via an engine control module. Starting is accomplished by commanding the control to ”start” the engine. This command can be given by a number of controls.

?The operator control mounted on the front panel.

?The remote controls via the transfer switch or remote start terminal closure.

Initially, the system may be started and operated by placing the operator control in the ”manual/run” position. To cease operation, return the switch to the ”off” position.

NOTE: Clear unit of all loose objects and perform all ”pre–start” procedures before operating generator system.

ENGINE CONTROL MODULE:

The engine control module (ECM) is a microprocessor– based module that monitors the control and safety inputs and provides all the required START and STOP functions automatically.

The following front panel controls and instruments are wired into the microprocessor through the ECM terminal blocks:

1.Run–Off–Auto Switch

a.* ”Run” – run position causes the generator set to start and run immediately.

b.* ”Auto” – auto position allows unit to be controlled via any remote single–pole ”dry” contact (transfer switch, etc.). Contact closure causes the unit to start and run, while contact opening causes unit to shut down after a preset cool down period.

c.”Off” – unit operation is terminated.

*– units equipped with Isuzu engines may have a time delay glow plug cycle before starting.

2.Lamp Test

Push button energizes all alarm lights simultaneously. This feature is disabled with the run–stop–auto switch in the ”stop” position, and has no other effect on unit operation.

SAFETY INPUTS

1. Low Oil Pressure Shutdown – (LOP)

Monitoring of oil pressure begins for a preset time after unit starts and remains in effect until unit is shut down (except as noted in ”loss of frequency input” below). The LOP signal is derived from an oil pressure switch gauge mounted on the control panel

2.High Temperature Shutdown – (HT)

The engine temperature monitoring begins immediately with the start signal. However, if engine temperature is excessive prior to start (i.e., heat soak after shutdown), the unit is permitted to start.

The high temperature condition is permitted to exist for up to 60 seconds after the unit is running before shutdown when alarm occurs. If the excessive temperature condition is corrected within that time period, the HT circuit reverts to normal monitoring. The HT signal is derived from a monitoring device located on the prime mover.

16

Image 19
Contents Baldor Generators OPERATOR’S Manual TowablesPage Safety Warnings FORM# S-PSG-001-3 ```` for Gasoline or Diesel Powered Generator Sets ```` Page Forward \ISO9001\FORMS\SCSD0037.MSW Features & Specifications Page Switchable Connection Information Control Panel Operation Function Page Page Operation PRE-START Procedure Operation Starting Operation Cranking Control LOW Voltage Troubleshooting GeneratorHigh Voltage Fluctuating VoltageOverheating Mechanical Noise Generator Frame Produces Shock When TouchedTroubleshooting Engine Page Magnaplus Generator Table of Contents Specifications Parts List Single Bearing Storage SafetyReceiving and Storage Unpacking and HandlingPMG optional Principles of OperationPreparation for USE InstallationParallel Operation Nonlinear LoadingGenerator Mounting END Play TestingTorsional Vibration Environmental Considerations Wiring ConnectionsLOW WYE Connection Double Delta -- Single Phase Connection PRE-START Inspection OperationSTART-UP Shutdown Procedure MaintenanceDrying Windings TestingField Flashing ServiceDiode Testing GeneralBearing Removal Bearing ReplacementReturned Goods TroubleshootingGenerator Produces LOW VOLTAGE, no Load Generator Produces no VoltageGenerator Produces Fluctuating Voltage Generator Produces LOW Voltage When Load AppliedGenerator Produces High Voltage Generator Produces Mechanical Noise Generator is OverheatingSpecifications Parts List Single Bearing Parts List Dual Bearing Towing Vehicle Rules for Safe Trailer OperationTowing Heavy Trailer Loads Electrical Trailer WiringSafety Checks Trailer Light Mounting and Connection Trailer Light KIT Wiring InstructionsLimited Warranty Owner’s Responsibilities Page California Proposition 65 Warning