Baldor BALDOR GENERATORS Generator Produces no Voltage, Generator Produces LOW VOLTAGE, no Load

Page 42

WARNING

HIGH VOLTAGES MAY BE PRESENT AT THE GENERATOR’S TERMINALS WHEN THE UNIT IS RUNNING. SOME ACCESSORY EQUIPMENT SUCH AS SPACE HEATERS MAY BE ENERGIZED FROM AN OUTSIDE POWER SOURCE WHEN THE UNIT IS AT REST. TOOLS, EQUIPMENT, CLOTHING AND YOUR BODY MUST BE KEPT CLEAR OF ROTATING PARTS AND ELECTRICAL CONNECTIONS. SPECIAL PRECAUTIONS MUST BE TAKEN DURING TROUBLESHOOTING SINCE PROTECTIVE COVERS AND SAFETY DEVICES MAY BE REMOVED OR DISABLED TO GAIN ACCESS AND PERFORM TESTS. BE CAREFUL. SERIOUS PERSONAL INJURY OR DEATH CAN RESULT FROM THESE HAZARDS. CONSULT QUALIFIED PERSONNEL WITH ANY QUESTIONS.

GENERATOR PRODUCES NO VOLTAGE

CAUSE

CHECK AND REMEDY

Voltmeter off or defective

Check voltage with a separate meter at the generator terminals.

Incorrect or defective connections

Verify generator connections. See drawings supplied with the generator or lead

 

connection diagrams in this manual. Inspect all wiring for loose connections, open

 

circuits, grounds, and short circuits.

Loss of residual

Flash the field. Refer to field flashing in the service section. If the generator is equipped

 

with a PMG, field flashing is not necessary -- check regulator fuse and input power from

 

the PMG.

Defective diodes, suppressor, or

Test the generator using the 12 volt battery test as specified in the testing section. If the

windings

results indicate generator problems, perform insulation, continuity, and diode tests as

 

specified in the testing section.

Regulator protection operating

Adjust regulator. Consult regulator manual.

Regulator inoperative

Adjust or replace regulator. Consult regulator manual.

GENERATOR PRODUCES LOW VOLTAGE, NO LOAD

CAUSE

Underspeed operation Voltmeter off or defective Incorrect or defective connections

CHECK AND REMEDY

Check speed using a tachometer or frequency meter.

Check voltage with a separate meter at the generator terminals.

Verify generator connections. See drawings supplied with the generator or lead connection diagrams in this manual. Inspect all wiring for grounds, open circuits and short circuits.

Loss of regulator power

Check regulator fuse and input power. Input power is produced by the generator’s

 

residual voltage or from an optional PMG.

Regulator adjustment

Adjust regulator settings. Consult regulator manual.

Regulator incorrectly connected

Review the generator connection diagram or reference the regulator manual.

Defective diodes, suppressor, or

Test the generator using the 12 volt battery test as specified in the testing section. If the

windings

results indicate generator problems, perform insulation, continuity, and diode tests as

 

specified in the testing section.

Regulator inoperative

Adjust or replace regulator. Consult regulator manual.

17

Image 42
Contents Baldor Generators Towables OPERATOR’S ManualPage Safety Warnings FORM# S-PSG-001-3 ```` for Gasoline or Diesel Powered Generator Sets ```` Page Forward \ISO9001\FORMS\SCSD0037.MSW Features & Specifications Page Switchable Connection Information Control Panel Operation Function Page Page Operation PRE-START Procedure Operation Starting Operation Cranking Control Troubleshooting Generator LOW VoltageFluctuating Voltage High VoltageOverheating Generator Frame Produces Shock When Touched Mechanical NoiseTroubleshooting Engine Page Magnaplus Generator Table of Contents Specifications Parts List Single Bearing Unpacking and Handling SafetyReceiving and Storage StoragePrinciples of Operation PMG optionalNonlinear Loading InstallationParallel Operation Preparation for USEEND Play Testing Generator MountingTorsional Vibration Wiring Connections Environmental ConsiderationsLOW WYE Connection Double Delta -- Single Phase Connection Operation PRE-START InspectionSTART-UP Maintenance Shutdown ProcedureTesting Drying WindingsGeneral ServiceDiode Testing Field FlashingBearing Replacement Bearing RemovalTroubleshooting Returned GoodsGenerator Produces no Voltage Generator Produces LOW VOLTAGE, no LoadGenerator Produces LOW Voltage When Load Applied Generator Produces Fluctuating VoltageGenerator Produces High Voltage Generator is Overheating Generator Produces Mechanical NoiseSpecifications Parts List Single Bearing Parts List Dual Bearing Rules for Safe Trailer Operation Towing VehicleElectrical Trailer Wiring Towing Heavy Trailer LoadsSafety Checks Trailer Light KIT Wiring Instructions Trailer Light Mounting and ConnectionLimited Warranty Owner’s Responsibilities Page California Proposition 65 Warning