Emerson GXT3-6000RT208 user manual

Page 2
Image 2
Contents Liebert GXT3 208V,5000-10,000VA, 6000RTL630 Page Table of Contents Maintenance SpecificationsFigures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Inverter Rectifier/Power Factor Correction PFC CircuitBattery Charger DC-to-DC ConverterBattery Dynamic BypassMain Frame and Electronics USB Port Liebert Knockouts for HardwiredMaintenance Bypass Breaker Input Input Breaker PD2-HDWR-MBS Major ComponentsTerminal Block Repo Connection Output BreakerReceptacles four L6-20R Removable Power Distribution BoxPD2-006 Receptacles four 5-20R two L6-30Internal Battery Packs Internal battery pack featuresWHAT’S Included Tower UPS Installation Install the Main CabinetInstallation and Configuration Connectors Spacers Support BasesOperation and Display Panel Rotated Clockwise 90 Degrees Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityDepth UPS or battery813mm Retaining latchInstallation and Configuration External Battery Cabinet Installation External battery cabinets connected to 6000VA Liebert GXT3Connect Input/Output Power Power distribution box removal from 5000 and 6000VA modelsInstall the Power Distribution Box on 5000 and 6000VA Models Unit Rating Maximum Breaker Rating Distribution Box Electrical ConnectionsBranch circuit breaker ratings Electrical specifications Terminal Block ConnectionsRemove Screws IT Power System Configuration-LiebertGXT3-6000RTL630OnlyConnectors What You Will Need Configuration Program FeaturesConfiguration Program Upper indicator for L1 Lower for L2 ON/Alarm Silence/Manual Battery Test ButtonControls and Indicators Standby/Manual Bypass ButtonLiebert GXT3 has Load Level Indicators 4 Green, 1 AmberBattery Level Indicators 5 Green UPS Status Indicator Icon Color Description UPS Status IndicatorsUPS status indicators Operation Startup Checklist for the Liebert GXT3Initial Startup and Electrical Checks Maintenance Bypass Manual Battery TestDisconnecting Input Power from the Liebert GXT3 Put the Liebert GXT3 in Manual BypassTerminal Block Battery Mode ShutdownCommunication Interface Port CommunicationLiebert IntelliSlot Communication Cards On BatteryLow Battery Liebert MultiLink Remote Emergency Power OffRepo switch connection diagram Battery Replacement Procedures Replacing the Internal Battery PackMaintenance Battery Charging PrecautionsChecking UPS Functions Replacing the Power Module on 8000 and 10,000VA modelsChecking UPS Status Maintenance Indicators UPS SymptomsTroubleshooting Indicator Diagnosis/Audible alarmAudible alarm description TroubleshootingAudible Alarm Troubleshooting tableTroubleshooting table cont’d Specifications UPS specifications-5000, 6000, 8000 and 10,000 modelsWeight, lb kg UPS specifications-LiebertGXT3-6000RTL630Dimensions, Rack Mount, W X D X H, in. mm Model Number GXT3-6000RTL630 Model RatingOperating temperature parameters Internal battery cabinet specificationsSee Table Environmental External battery cabinet specifications Model NumberBattery Parameters Power Distribution Box Model # 220VAC Tower Battery run time, minutesNumber Load Percent 208/120VAC RT Batteries Capacity 5kVA 6kVA 8kVA 10kVA 6kVA L630Auto-Learning Battery Run Times Page Twork NetIs t Care