Emerson GXT3-6000RT208 user manual Install the Power Distribution Box on 5000 and 6000VA Models

Page 24

Installation and Configuration

5.3.2Remove the Power Distribution Cover from 8000 and 10,000VA Models

1.Shut down the Liebert® GXT3by pressing the Standby/Manual Bypass button twice while the UPS is in Bypass Mode, each time holding the button down for about 2 seconds. (For help, refer to 8.5 - Shut Down the Liebert GXT3.)

2.Loosen the captive screw over the maintenance bypass breaker (see Figure 5 for the breaker’s location).

3.Turn the maintenance bypass breaker On.

NOTICE

The load is unprotected from disturbances in the power supply while the UPS is on bypass.

4.Turn the output and input breakers Off.

5.Support the power distribution box and remove the two screws at the top of the box.

6.Remove the cover or power distribution box from the UPS and set it aside.

7.If removing a power distribution box, carefully pull apart the power distribution box connector and the UPS connector.

Figure 14 Power distribution box removal from 8000 and 10,000VA models

Extract screws at these places

Pigtails removed for clarity

Tabs slip into slots on UPS

5.3.3Install the Power Distribution Box on 5000 and 6000VA Models

1.Align the connectors and press the power distribution box onto the UPS.

2.Hold the box firmly against the UPS and tighten the captive screws except the one over the maintenance bypass breaker.

3.Turn the output and input breakers On.

4.Start the UPS according to startup instructions.

5.Verify that the UPS lamp is illuminated.

6.Turn the maintenance bypass breaker Off.

7.Insert the maintenance bypass cover behind the captive screw and tighten the screw.

NOTE

The maintenance bypass breaker cover must be installed behind the captive screw and the screw must be tightened for the UPS to operate in inverter mode.

18

Image 24
Contents Liebert GXT3 208V,5000-10,000VA, 6000RTL630 Page Table of Contents Maintenance SpecificationsFigures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Rectifier/Power Factor Correction PFC Circuit Battery ChargerInverter DC-to-DC ConverterBattery Dynamic BypassUSB Port Liebert Knockouts for Hardwired Maintenance Bypass Breaker Input Input Breaker PD2-HDWR-MBSMain Frame and Electronics Major ComponentsTerminal Block Repo Connection Output BreakerRemovable Power Distribution Box PD2-006Receptacles four L6-20R Receptacles four 5-20R two L6-30Internal Battery Packs Internal battery pack featuresWHAT’S Included Install the Main Cabinet Installation and ConfigurationTower UPS Installation Connectors Spacers Support BasesRack-Mount UPS Installation Installing the Adjustable Rack-Mount Kit-Sold SeparatelyOperation and Display Panel Rotated Clockwise 90 Degrees QuantityUPS or battery 813mmDepth Retaining latchInstallation and Configuration External Battery Cabinet Installation External battery cabinets connected to 6000VA Liebert GXT3Connect Input/Output Power Power distribution box removal from 5000 and 6000VA modelsInstall the Power Distribution Box on 5000 and 6000VA Models Distribution Box Electrical Connections Branch circuit breaker ratingsUnit Rating Maximum Breaker Rating Electrical specifications Terminal Block ConnectionsIT Power System Configuration-LiebertGXT3-6000RTL630Only ConnectorsRemove Screws Configuration Program Features Configuration ProgramWhat You Will Need ON/Alarm Silence/Manual Battery Test Button Controls and IndicatorsUpper indicator for L1 Lower for L2 Standby/Manual Bypass ButtonLoad Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenLiebert GXT3 has UPS Status Indicators UPS status indicatorsUPS Status Indicator Icon Color Description Startup Checklist for the Liebert GXT3 Initial Startup and Electrical ChecksOperation Manual Battery Test Disconnecting Input Power from the Liebert GXT3Maintenance Bypass Put the Liebert GXT3 in Manual BypassBattery Mode Shutdown Communication Interface PortTerminal Block CommunicationOn Battery Low BatteryLiebert IntelliSlot Communication Cards Remote Emergency Power Off Repo switch connection diagramLiebert MultiLink Replacing the Internal Battery Pack MaintenanceBattery Replacement Procedures Battery Charging PrecautionsReplacing the Power Module on 8000 and 10,000VA models Checking UPS StatusChecking UPS Functions Maintenance UPS Symptoms TroubleshootingIndicators Indicator Diagnosis/Audible alarmTroubleshooting Audible AlarmAudible alarm description Troubleshooting tableTroubleshooting table cont’d Specifications UPS specifications-5000, 6000, 8000 and 10,000 modelsUPS specifications-LiebertGXT3-6000RTL630 Dimensions, Rack Mount, W X D X H, in. mmWeight, lb kg Model Number GXT3-6000RTL630 Model RatingOperating temperature parameters Internal battery cabinet specificationsExternal battery cabinet specifications Model Number Battery ParametersSee Table Environmental Power Distribution Box Model # Battery run time, minutes Number Load Percent 208/120VAC RT220VAC Tower Batteries Capacity 5kVA 6kVA 8kVA 10kVA 6kVA L630Auto-Learning Battery Run Times Page Net Is tTwork Care