Emerson GXT3-6000RT208 user manual Manual Battery Test, Put the Liebert GXT3 in Manual Bypass

Page 33

Operation

8.3Manual Battery Test

To initiate a manual battery test, press the On/Alarm Silence/Manual Battery Test button for at least half a second while the UPS is operating from utility power with no alarm conditions present.

If only the first two of the five LED segments illuminate, allow the UPS to recharge the batteries for 24 hours.

Retest the batteries after 24 hours of charging.

After the batteries have been retested, if only two of the five Battery LEDs illuminate, contact your local Emerson representative or Emerson Network Power Channel Support.

If none of the five Battery LEDs illuminate during a manual battery test, check the battery con- nection and allow the UPS to recharge the batteries for 1 hour, then initiate a manual battery test again.

If none of the five Battery LEDs illuminate during the second manual battery test, replace batter- ies and contact your local Emerson representative or Emerson Channel Support.

8.4Put the Liebert® GXT3in Manual Bypass

Press the Standby/Manual Bypass button and hold it for about 2 seconds while the UPS is in Utility (AC) Mode. The UPS will transfer the connected loads to the internal bypass. If the internal bypass is not available because of utility power problems, pressing this button once will be ignored. Bypass operation is indicated by an audible alarm and illuminated amber Bypass indicator. (If other indica- tors are illuminated, refer to 11.0 - Troubleshooting.)

8.5Shut Down the Liebert GXT3

1.Transfer the UPS to manual bypass by pressing the Standby/Manual Bypass button and holding it for about 2 seconds.

If manual bypass is not available, disregard the first step.

2.Press the Standby/Manual Bypass button twice within four seconds, each time holding it for about two seconds.

Power to the connected loads is now Off.

8.6Disconnecting Input Power from the Liebert GXT3

1.After the UPS has been shut down as detailed in 8.5 - Shut Down the Liebert GXT3, turn off the Output Circuit Breaker.

2.Wait 30 seconds and verify that all indicators have turned Off and the fan has stopped; this indicates that the power-off is complete.

3.Turn the external battery cabinet breaker switch to the Off position if the UPS has an external battery cabinet.

After powering off the UPS, the UPS ceases output and the load is powered Off.

8.7Maintenance Bypass

Maintenance Bypass Mode is used when maintenance or replacement is required. To place the unit in Maintenance Bypass:

1.Place the UPS on internal bypass. This may be done by either of the following methods:

a.Press the Off button on the front panel one time.

b.Slide the bracket away from the manual bypass breaker on the rear of the UPS. This requires loosening the captive screw and sliding the bracket up and away from the Manual Bypass breaker.

2.Move the Manual Bypass breaker on the rear of the UPS to the bypass position. This requires loosening the captive screw and sliding the bracket up and away from the Manual Bypass breaker.

27

Image 33
Contents Liebert GXT3 208V,5000-10,000VA, 6000RTL630 Page Table of Contents Specifications MaintenanceFigures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Battery Charger Rectifier/Power Factor Correction PFC CircuitInverter DC-to-DC ConverterDynamic Bypass BatteryMaintenance Bypass Breaker Input Input Breaker PD2-HDWR-MBS USB Port Liebert Knockouts for HardwiredMain Frame and Electronics Major ComponentsOutput Breaker Terminal Block Repo ConnectionPD2-006 Removable Power Distribution BoxReceptacles four L6-20R Receptacles four 5-20R two L6-30Internal battery pack features Internal Battery PacksWHAT’S Included Installation and Configuration Install the Main CabinetTower UPS Installation Connectors Spacers Support BasesInstalling the Adjustable Rack-Mount Kit-Sold Separately Rack-Mount UPS InstallationOperation and Display Panel Rotated Clockwise 90 Degrees Quantity813mm UPS or batteryDepth Retaining latchInstallation and Configuration External battery cabinets connected to 6000VA Liebert GXT3 External Battery Cabinet InstallationPower distribution box removal from 5000 and 6000VA models Connect Input/Output PowerInstall the Power Distribution Box on 5000 and 6000VA Models Distribution Box Electrical Connections Branch circuit breaker ratingsUnit Rating Maximum Breaker Rating Terminal Block Connections Electrical specificationsIT Power System Configuration-LiebertGXT3-6000RTL630Only ConnectorsRemove Screws Configuration Program Features Configuration ProgramWhat You Will Need Controls and Indicators ON/Alarm Silence/Manual Battery Test ButtonUpper indicator for L1 Lower for L2 Standby/Manual Bypass ButtonLoad Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenLiebert GXT3 has UPS Status Indicators UPS status indicatorsUPS Status Indicator Icon Color Description Startup Checklist for the Liebert GXT3 Initial Startup and Electrical ChecksOperation Disconnecting Input Power from the Liebert GXT3 Manual Battery TestMaintenance Bypass Put the Liebert GXT3 in Manual BypassCommunication Interface Port Battery Mode ShutdownTerminal Block CommunicationOn Battery Low BatteryLiebert IntelliSlot Communication Cards Remote Emergency Power Off Repo switch connection diagramLiebert MultiLink Replacing the Internal Battery Pack MaintenanceBattery Replacement Procedures Precautions Battery ChargingReplacing the Power Module on 8000 and 10,000VA models Checking UPS StatusChecking UPS Functions Maintenance Troubleshooting UPS SymptomsIndicators Indicator Diagnosis/Audible alarmAudible Alarm TroubleshootingAudible alarm description Troubleshooting tableTroubleshooting table cont’d UPS specifications-5000, 6000, 8000 and 10,000 models SpecificationsDimensions, Rack Mount, W X D X H, in. mm UPS specifications-LiebertGXT3-6000RTL630Weight, lb kg Model Number GXT3-6000RTL630 Model RatingInternal battery cabinet specifications Operating temperature parametersExternal battery cabinet specifications Model Number Battery ParametersSee Table Environmental Power Distribution Box Model # Number Load Percent 208/120VAC RT Battery run time, minutes220VAC Tower Batteries Capacity 5kVA 6kVA 8kVA 10kVA 6kVA L630Auto-Learning Battery Run Times Page Is t NetTwork Care