Installation and Configuration

5.3.4Install the Power Distribution Box on 8000 and 10,000VA Models

1.With the cover or distribution box removed, press the UPS and distribution box connectors together. Ensure that the connectors are fully seated.

2.Align the screw holes and press the power distribution box onto the UPS, making sure that the tabs at the bottom of the box fit into the slots on the UPS.

3.Attach the box to the UPS by installing screws into the two holes at the top of the box.

4.Tighten the screws.

5.Turn the output and input breakers On.

6.Start the UPS according to startup instructions.

7.Verify that the UPS lamp is illuminated.

5.3.5Distribution Box Electrical Connections

Electrical connections are made through a removable power distribution box that attaches to the rear of the UPS.

PD2-HDWR, PD2-HDWR-MBS, PD2-001, PD2-002, PD2-003, PD2-004, PD2-005 and PD2-006 models fit the 5000 and 6000VA models of the Liebert® GXT3

PD2-L630 fits the GXT3-6000RTL630

PD2-101, PD2-102, PD2-103, PD2-104, PD2-105 and PD2-106 models fit the 8000 and 10,000VA models of the Liebert GXT3

The installer must provide an upstream branch circuit breaker. The input circuit breaker on the dis- tribution box and the output circuit breaker on the rear of the power distribution box disconnect all power between the main cabinet and the distribution box.

Models equipped with a manual bypass breaker pass bypass power directly to the bypass breaker from the input terminal block. The input circuit breaker on the distribution box does not disconnect power from the manual bypass breaker.

Table 1 Branch circuit breaker ratings

Unit Rating Maximum Breaker Rating

5000VA

6000VA

8000VA

D Type 30A Long Delay

D Type 60A Long Delay

10,000VA

Figure 15 Distribution box electrical connections diagram

UPS

Input

Output

CB

CB

Maintenance

Bypass Breaker

Input Output

Indicator Indicator

Utility Input

Output

Distribution

POD

 

 

 

 

 

UPS

 

 

 

 

 

 

Input

 

 

 

 

 

Output

 

Output

 

 

 

 

 

 

 

 

 

 

 

 

 

CB

 

 

 

 

 

CB

 

 

 

 

Maintenance

 

 

 

 

Terminal

 

 

Bypass Breaker

 

 

 

 

Block

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Optional

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

 

 

 

Input

Output

 

 

Distribution

 

 

 

 

 

Plate

 

 

Indicator

Indicator

 

 

 

 

 

 

 

Utility Input

External

Branch CB Distribution Box Electrical Connections

for 5000 and 6000VA Models

External

Branch CB Distribution Box Electrical Connections for 8000 and 10,000VA Models

19

Image 25
Contents Liebert GXT3 208V,5000-10,000VA, 6000RTL630 Page Table of Contents Specifications MaintenanceFigures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Battery Charger Rectifier/Power Factor Correction PFC CircuitInverter DC-to-DC ConverterDynamic Bypass BatteryMaintenance Bypass Breaker Input Input Breaker PD2-HDWR-MBS USB Port Liebert Knockouts for HardwiredMain Frame and Electronics Major ComponentsOutput Breaker Terminal Block Repo ConnectionPD2-006 Removable Power Distribution BoxReceptacles four L6-20R Receptacles four 5-20R two L6-30Internal battery pack features Internal Battery PacksWHAT’S Included Installation and Configuration Install the Main CabinetTower UPS Installation Connectors Spacers Support BasesInstalling the Adjustable Rack-Mount Kit-Sold Separately Rack-Mount UPS InstallationOperation and Display Panel Rotated Clockwise 90 Degrees Quantity813mm UPS or batteryDepth Retaining latchInstallation and Configuration External battery cabinets connected to 6000VA Liebert GXT3 External Battery Cabinet InstallationPower distribution box removal from 5000 and 6000VA models Connect Input/Output PowerInstall the Power Distribution Box on 5000 and 6000VA Models Branch circuit breaker ratings Distribution Box Electrical ConnectionsUnit Rating Maximum Breaker Rating Terminal Block Connections Electrical specificationsConnectors IT Power System Configuration-LiebertGXT3-6000RTL630OnlyRemove Screws Configuration Program Configuration Program FeaturesWhat You Will Need Controls and Indicators ON/Alarm Silence/Manual Battery Test ButtonUpper indicator for L1 Lower for L2 Standby/Manual Bypass ButtonBattery Level Indicators 5 Green Load Level Indicators 4 Green, 1 AmberLiebert GXT3 has UPS status indicators UPS Status IndicatorsUPS Status Indicator Icon Color Description Initial Startup and Electrical Checks Startup Checklist for the Liebert GXT3Operation Disconnecting Input Power from the Liebert GXT3 Manual Battery TestMaintenance Bypass Put the Liebert GXT3 in Manual BypassCommunication Interface Port Battery Mode ShutdownTerminal Block CommunicationLow Battery On BatteryLiebert IntelliSlot Communication Cards Repo switch connection diagram Remote Emergency Power OffLiebert MultiLink Maintenance Replacing the Internal Battery PackBattery Replacement Procedures Precautions Battery ChargingChecking UPS Status Replacing the Power Module on 8000 and 10,000VA modelsChecking UPS Functions Maintenance Troubleshooting UPS SymptomsIndicators Indicator Diagnosis/Audible alarmAudible Alarm TroubleshootingAudible alarm description Troubleshooting tableTroubleshooting table cont’d UPS specifications-5000, 6000, 8000 and 10,000 models SpecificationsDimensions, Rack Mount, W X D X H, in. mm UPS specifications-LiebertGXT3-6000RTL630Weight, lb kg Model Number GXT3-6000RTL630 Model RatingInternal battery cabinet specifications Operating temperature parametersBattery Parameters External battery cabinet specifications Model NumberSee Table Environmental Power Distribution Box Model # Number Load Percent 208/120VAC RT Battery run time, minutes220VAC Tower Batteries Capacity 5kVA 6kVA 8kVA 10kVA 6kVA L630Auto-Learning Battery Run Times Page Is t NetTwork Care