Specifications
Table 8 | UPS | |
| Model Number |
|
|
|
|
| Model Rating | 4200W/6000VA |
|
| |
Dimensions, Rack Mount, W X D X H, in. (mm) |
| |
| Unit | 16.9 x 22.6 x 8.5 (430 x 574 x 217) |
| Shipping | 20.9 x 29.3 x 14.8 (530 x 745 x 377) |
|
| |
Weight, lb (kg) |
| |
| Unit | 51.8 (23.5) |
|
|
|
| Shipping | 66.1 (30) |
Input AC Parameters |
| |
| Nominal Operating Frequency | 50 or 60Hz (Factory Default, 60) |
|
|
|
| Factory Default VAC | 208VAC |
| User Configurable VAC | 208/220/230/240VAC |
| (may be modified with configuration program) | |
|
| |
Operating Voltage Range Without Battery Operation | 176 – 280VAC | |
|
|
|
| Maximum Allowable VAC | 280VAC |
| Input Frequency Without Battery Operation | 40 - 70Hz |
|
|
|
| Input Power Connection | |
|
| |
Output AC Parameters |
| |
| Factory Default VAC | 208 |
| Output Connections | (2) |
| (on | |
|
| |
| Frequency | 50Hz or 60Hz, Nominal |
| Waveform | Sinewave |
|
| |
Duration Inverter Will Support Rated Load |
| |
|
|
|
| 105% to 130% | 1 Minute |
|
|
|
| 131% to 150% | 10 seconds |
| 151% to 200% | 1 second |
|
|
|
| >200% (impact load) | At least 5 cycles |
|
| |
Bypass Protection Limits |
| |
| Disable Bypass Operation | If input voltage exceeds ±15% of the nominal voltage |
| If input voltage returns to within ±10% of nominal output voltage | |
|
|
|
| Disable Bypass Operation | When the input frequency prevents synchronous operation |
|
| |
Environmental |
| |
| Operating Temp, °F (°C) | 32 to 104 (0 to 40); see Table 9 |
| Storage Temp, °F (°C) | 5 to 122 |
|
|
|
| Humidity | 0% to 95% Relative Humidity, |
|
|
|
| Operating Elevation | Up to 10,000 ft. (3000m) at 77°F (25°C) without derating |
| Audible Noise | Less than 55dBA at 3.2ft. (1m) rear; |
| Less than 50dBA at 3.2ft. (1m) front and sides | |
|
| |
Agency |
|
|
| Safety | UL 1778, |
| EMI/EMC | FCC Class A |
|
|
|
| ESD | |
|
|
|
| Radiated Susceptibility | |
| Electrical Fast Transient | |
|
|
|
| Surge Immunity | |
|
|
|
| Transportation | ISTA Procedure 1A |
|
|
|
39