Troubleshooting
11.0TROUBLESHOOTING
This section indicates various UPS symptoms a user may encounter and provides a troubleshooting guide in the event the UPS develops a problem. Use the following information to determine whether external factors caused the problem and how to remedy the situation.
11.1UPS Symptoms
The following symptoms indicate the Liebert® GXT3™ is malfunctioning:
•The relative indicators illuminate, indicating the UPS has detected a problem.
•An alarm buzzer sounds, alerting the user that the UPS requires attention.
11.1.1Indicators
In addition to the fault indicator being illuminated, one or more of LED segments of battery level indi- cator will also be illuminated to provide a diagnostic aid to the user, as shown in Figure 26. The descriptions are listed in Table 4.
Figure 26 Battery level indicator
|
|
|
|
|
|
|
|
| |
|
|
| A | B | C | D | E |
| |
Table 4 | Indicator descriptions |
|
|
|
|
| |||
|
|
|
|
|
|
|
| ||
Indicator |
|
| Diagnosis/Audible alarm |
|
|
|
| ||
|
|
|
|
|
| ||||
A - E |
| On bypass from output overload | |||||||
|
|
|
|
|
| ||||
A |
| On bypass due to overtemperature condition | |||||||
|
|
|
|
|
| ||||
B |
| On bypass due to DC bus overvoltage | |||||||
|
|
|
|
|
| ||||
C |
| On bypass due to DC/DC power supply failure | |||||||
|
|
|
|
|
|
| |||
D |
| PFC failure |
|
|
| ||||
|
|
|
|
|
| ||||
E |
| On bypass due to inverter failure | |||||||
|
|
|
|
|
| ||||
A&B |
| UPS Failure (includes | |||||||
| charger failure) and continuous alarm |
|
|
| |||||
|
|
|
|
| |||||
A&C |
| UPS failed battery test | |||||||
|
|
|
|
|
|
| |||
A&D |
| Maintance bypass switch on (continuous) |
|
|
| ||||
|
|
|
|
|
| ||||
A&E |
| Bypass feedback |
|
| |||||
|
|
|
|
|
| ||||
B&C |
| REPO (one | |||||||
|
|
|
|
|
|
|
|
| |
B&E |
| Short circuit on the output |
|
|
|
|
| ||
|
|
|
|
|
| ||||
C&E |
| UPS shutdown by command from communication (USB port or Liebert® IntelliSlot® port) (no | |||||||
| audible) |
|
|
|
|
| |||
|
|
|
|
|
|
| |||
Utility LED flash |
|
|
|
|
| ||||
|
|
|
|
| |||||
Battery Indicator | Internal battery source not available (continuous horn); check battery connection, power down | ||||||||
Flashing | and reboot UPS |
|
|
|
|
| |||
Bypass Indicator | Utility power voltage or frequency is out of tolerance; bypass is unavailable | ||||||||
Flashing | |||||||||
|
|
|
|
|
|
| |||
A - E indicators are shown in Figure 26 |
|
|
|
|
|
35