Emerson GXT3-6000RT208 user manual Battery Charging, Precautions

Page 38

Maintenance

Figure 24 Pulling out the battery packs

5000 & 6000 VA models

8000VA / 10,000VA model

Internal Battery Pack (one of 2)

Internal

Battery

Pack

 

Battery

 

 

Handle

 

Battery

 

 

Handle

Each model has two

 

Pull Out with Battery Handle

battery packs

Pull Out with Battery Handle

 

 

6.Unpack a new internal battery pack. Take care not to destroy the packing.

Compare the new and old internal battery packs to make sure they are the same type and model. If they are the same, proceed with Step 7; if they are different, stop and contact your local Emer- son representative or Emerson Channel Support.

7.Line up and slide in the new internal battery pack.

8.Repeat Steps 6 and 7 if replacing both battery packs. Each model has two battery packs

9.Reconnect the battery plugs and battery receptacles.

10.Gently push the battery wire into the UPS battery compartment.

11.Reattach the front battery door with the six screws.

12.Reattach the front plastic bezel cover to the UPS.

NOTE

The internal battery pack is hot-swappable. However, caution should be exercised because the load is unprotected from disturbances and power failures during this procedure. Do not replace the battery while the UPS is operating in Battery Mode. This will result in a loss of output power and will drop the connected load.

10.2Battery Charging

The batteries are valve-regulated, nonspillable, lead acid and should be kept charged to attain their design life. The Liebert® GXT3charges the batteries continuously when it is connected to the utility input power.

If the Liebert GXT3 will be stored for a long time, Emerson recommends connecting the UPS to input power for at least 24 hours every four to six months to ensure full recharge of the batteries.

10.3Precautions

Although the Liebert GXT3 has been designed and manufactured to ensure personal safety, improper use can result in electrical shock or fire. To ensure safety, observe the following precautions:

Turn Off and unplug the Liebert GXT3 before cleaning it.

Wear rubber gloves and boots.

Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.

Never block or insert any objects into the ventilation holes or other openings of the UPS.

Do not place the Liebert GXT3 power cord where it might be damaged.

32

Image 38
Contents Liebert GXT3 208V,5000-10,000VA, 6000RTL630 Page Table of Contents Maintenance SpecificationsFigures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Inverter Rectifier/Power Factor Correction PFC CircuitBattery Charger DC-to-DC ConverterBattery Dynamic BypassMain Frame and Electronics USB Port Liebert Knockouts for HardwiredMaintenance Bypass Breaker Input Input Breaker PD2-HDWR-MBS Major ComponentsTerminal Block Repo Connection Output BreakerReceptacles four L6-20R Removable Power Distribution BoxPD2-006 Receptacles four 5-20R two L6-30Internal Battery Packs Internal battery pack featuresWHAT’S Included Tower UPS Installation Install the Main CabinetInstallation and Configuration Connectors Spacers Support BasesOperation and Display Panel Rotated Clockwise 90 Degrees Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityDepth UPS or battery813mm Retaining latchInstallation and Configuration External Battery Cabinet Installation External battery cabinets connected to 6000VA Liebert GXT3Connect Input/Output Power Power distribution box removal from 5000 and 6000VA modelsInstall the Power Distribution Box on 5000 and 6000VA Models Unit Rating Maximum Breaker Rating Distribution Box Electrical ConnectionsBranch circuit breaker ratings Electrical specifications Terminal Block ConnectionsRemove Screws IT Power System Configuration-LiebertGXT3-6000RTL630OnlyConnectors What You Will Need Configuration Program FeaturesConfiguration Program Upper indicator for L1 Lower for L2 ON/Alarm Silence/Manual Battery Test ButtonControls and Indicators Standby/Manual Bypass ButtonLiebert GXT3 has Load Level Indicators 4 Green, 1 AmberBattery Level Indicators 5 Green UPS Status Indicator Icon Color Description UPS Status IndicatorsUPS status indicators Operation Startup Checklist for the Liebert GXT3Initial Startup and Electrical Checks Maintenance Bypass Manual Battery TestDisconnecting Input Power from the Liebert GXT3 Put the Liebert GXT3 in Manual BypassTerminal Block Battery Mode ShutdownCommunication Interface Port CommunicationLiebert IntelliSlot Communication Cards On BatteryLow Battery Liebert MultiLink Remote Emergency Power OffRepo switch connection diagram Battery Replacement Procedures Replacing the Internal Battery PackMaintenance Battery Charging PrecautionsChecking UPS Functions Replacing the Power Module on 8000 and 10,000VA modelsChecking UPS Status Maintenance Indicators UPS SymptomsTroubleshooting Indicator Diagnosis/Audible alarmAudible alarm description TroubleshootingAudible Alarm Troubleshooting tableTroubleshooting table cont’d Specifications UPS specifications-5000, 6000, 8000 and 10,000 modelsWeight, lb kg UPS specifications-LiebertGXT3-6000RTL630Dimensions, Rack Mount, W X D X H, in. mm Model Number GXT3-6000RTL630 Model RatingOperating temperature parameters Internal battery cabinet specificationsSee Table Environmental External battery cabinet specifications Model NumberBattery Parameters Power Distribution Box Model # 220VAC Tower Battery run time, minutesNumber Load Percent 208/120VAC RT Batteries Capacity 5kVA 6kVA 8kVA 10kVA 6kVA L630Auto-Learning Battery Run Times Page Twork NetIs t Care