Emerson GXT3-6000RT208 user manual External Battery Cabinet Installation

Page 22

Installation and Configuration

5.2External Battery Cabinet Installation

! WARNING

Risk of electric shock. Can cause injury or death.

Disconnect all local and remote electric power supplies before working within.

Ensure that the Liebert® GXT3is shut down and power has been disconnected before beginning any work on or in the unit.

! CAUTION

The external battery cabinet(s) are heavy (see Table 11). Take proper precautions when lifting them.

Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed on one side of the UPS in a tower config- uration or stacked beneath the UPS in a rack configuration.

Figure 12 External battery cabinets connected to 6000VA Liebert GXT3

6000VA Liebert GXT3

Battery Cabinet

Cable connects battery cabinet to 6000VA Liebert GXT3

Second connector permits adding more battery cabinets to 6000VA Liebert GXT3

1.Inspect the external battery cabinet for freight damage. Report damage to the carrier and your local dealer or Emerson representative.

2.Optional rack-mount handles are shipped with the external battery cabinet and may be installed at this time if desired.

3.Securing hardware and slide rails are sold separately. Please contact your local dealer or Emerson representative for these additional options and any assistance needed. Fasten the slides into position with the screws per the instructions included with the slide rails.

4.Use the enclosed support bases for the tower option to prevent tip-over. One additional set of support base extensions ships with each external battery cabinet.

5.Put the UPS in Bypass Mode by pressing the bypass button on the front of the unit and holding it about 2 seconds.

6.Verify the External Battery Cabinet breaker is in the Off position.

7.Connect the supplied external battery cabinet cable to the rear of the external battery cabinet, then to the rear of the UPS.

8.Turn the External Battery Cabinet breaker to the On position.

9.Press the On button on the front of the UPS for 4 seconds to return the unit to Inverter Mode.

10.Verify the circuit breaker on the External Battery Cabinet is in the On position.

11.Use the included configuration program to program the UPS for the number of external battery cabinets connected. Instructions for the configuration program are in 6.0 - Configuration Program.

12.The UPS is now equipped with additional backup battery run time. For approximate battery run times, refer to Table 14.

NOTE

When removing the External Battery Cabinet, the circuit breaker on the rear of the cabinet must be turned off before disconnecting the cable.

16

Image 22
Contents Liebert GXT3 208V,5000-10,000VA, 6000RTL630 Page Table of Contents Maintenance SpecificationsFigures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Inverter Rectifier/Power Factor Correction PFC CircuitBattery Charger DC-to-DC ConverterBattery Dynamic BypassMain Frame and Electronics USB Port Liebert Knockouts for HardwiredMaintenance Bypass Breaker Input Input Breaker PD2-HDWR-MBS Major ComponentsTerminal Block Repo Connection Output BreakerReceptacles four L6-20R Removable Power Distribution BoxPD2-006 Receptacles four 5-20R two L6-30Internal Battery Packs Internal battery pack featuresWHAT’S Included Tower UPS Installation Install the Main CabinetInstallation and Configuration Connectors Spacers Support BasesOperation and Display Panel Rotated Clockwise 90 Degrees Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityDepth UPS or battery813mm Retaining latchInstallation and Configuration External Battery Cabinet Installation External battery cabinets connected to 6000VA Liebert GXT3Connect Input/Output Power Power distribution box removal from 5000 and 6000VA modelsInstall the Power Distribution Box on 5000 and 6000VA Models Branch circuit breaker ratings Distribution Box Electrical ConnectionsUnit Rating Maximum Breaker Rating Electrical specifications Terminal Block ConnectionsConnectors IT Power System Configuration-LiebertGXT3-6000RTL630OnlyRemove Screws Configuration Program Configuration Program FeaturesWhat You Will Need Upper indicator for L1 Lower for L2 ON/Alarm Silence/Manual Battery Test ButtonControls and Indicators Standby/Manual Bypass ButtonBattery Level Indicators 5 Green Load Level Indicators 4 Green, 1 AmberLiebert GXT3 has UPS status indicators UPS Status IndicatorsUPS Status Indicator Icon Color Description Initial Startup and Electrical Checks Startup Checklist for the Liebert GXT3Operation Maintenance Bypass Manual Battery TestDisconnecting Input Power from the Liebert GXT3 Put the Liebert GXT3 in Manual BypassTerminal Block Battery Mode ShutdownCommunication Interface Port CommunicationLow Battery On BatteryLiebert IntelliSlot Communication Cards Repo switch connection diagram Remote Emergency Power OffLiebert MultiLink Maintenance Replacing the Internal Battery PackBattery Replacement Procedures Battery Charging PrecautionsChecking UPS Status Replacing the Power Module on 8000 and 10,000VA modelsChecking UPS Functions Maintenance Indicators UPS SymptomsTroubleshooting Indicator Diagnosis/Audible alarmAudible alarm description TroubleshootingAudible Alarm Troubleshooting tableTroubleshooting table cont’d Specifications UPS specifications-5000, 6000, 8000 and 10,000 modelsWeight, lb kg UPS specifications-LiebertGXT3-6000RTL630Dimensions, Rack Mount, W X D X H, in. mm Model Number GXT3-6000RTL630 Model RatingOperating temperature parameters Internal battery cabinet specificationsBattery Parameters External battery cabinet specifications Model NumberSee Table Environmental Power Distribution Box Model # 220VAC Tower Battery run time, minutesNumber Load Percent 208/120VAC RT Batteries Capacity 5kVA 6kVA 8kVA 10kVA 6kVA L630Auto-Learning Battery Run Times Page Twork NetIs t Care