Installation and Configuration
5.2External Battery Cabinet Installation
! WARNING
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power supplies before working within.
Ensure that the Liebert® GXT3™ is shut down and power has been disconnected before beginning any work on or in the unit.
! CAUTION
The external battery cabinet(s) are heavy (see Table 11). Take proper precautions when lifting them.
Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed on one side of the UPS in a tower config- uration or stacked beneath the UPS in a rack configuration.
Figure 12 External battery cabinets connected to 6000VA Liebert GXT3
6000VA Liebert GXT3
Battery Cabinet
Cable connects battery cabinet to 6000VA Liebert GXT3
Second connector permits adding more battery cabinets to 6000VA Liebert GXT3
1.Inspect the external battery cabinet for freight damage. Report damage to the carrier and your local dealer or Emerson representative.
2.Optional
3.Securing hardware and slide rails are sold separately. Please contact your local dealer or Emerson representative for these additional options and any assistance needed. Fasten the slides into position with the screws per the instructions included with the slide rails.
4.Use the enclosed support bases for the tower option to prevent
5.Put the UPS in Bypass Mode by pressing the bypass button on the front of the unit and holding it about 2 seconds.
6.Verify the External Battery Cabinet breaker is in the Off position.
7.Connect the supplied external battery cabinet cable to the rear of the external battery cabinet, then to the rear of the UPS.
8.Turn the External Battery Cabinet breaker to the On position.
9.Press the On button on the front of the UPS for 4 seconds to return the unit to Inverter Mode.
10.Verify the circuit breaker on the External Battery Cabinet is in the On position.
11.Use the included configuration program to program the UPS for the number of external battery cabinets connected. Instructions for the configuration program are in 6.0 - Configuration Program.
12.The UPS is now equipped with additional backup battery run time. For approximate battery run times, refer to Table 14.
NOTE
When removing the External Battery Cabinet, the circuit breaker on the rear of the cabinet must be turned off before disconnecting the cable.