Emerson GXT3-6000RT208 user manual Maintenance

Page 40

Maintenance

Figure 25 Removing power module from Liebert® GXT38000 and 10,000VA models

Power module pulled part of the way out of an 8000 or 10,000VA unit

11.Insert the replacement UPS power module.

12.Slide the power module restraint lever back into the locked position.

13.Reconnect the slotted internal battery connectors.

14.Reconnect the external battery cables, if used.

15.Reattach both front cover grilles.

16.Reattach the front plastic bezels.

17.Close the input circuit breaker on the rear of the UPS (see Figure 7).

18.Close the output circuit breaker on the rear of the UPS (see Figure 7).

19.Move the bypass breaker on the rear of the UPS back to the INVERTER position (see Figure 7).

20.Slide the bracket back next to the manual bypass breaker and tighten its thumbscrew.

21.Press the On button on the front panel one time to return the UPS to Normal Mode operation (see Figure 18).

NOTE

The power module restraint lever must be fully engaged for the UPS to operate in Normal Mode.

34

Image 40
Contents Liebert GXT3 208V,5000-10,000VA, 6000RTL630 Page Table of Contents Maintenance SpecificationsFigures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Rectifier/Power Factor Correction PFC Circuit Battery ChargerInverter DC-to-DC ConverterBattery Dynamic BypassUSB Port Liebert Knockouts for Hardwired Maintenance Bypass Breaker Input Input Breaker PD2-HDWR-MBSMain Frame and Electronics Major ComponentsTerminal Block Repo Connection Output BreakerRemovable Power Distribution Box PD2-006Receptacles four L6-20R Receptacles four 5-20R two L6-30Internal Battery Packs Internal battery pack featuresWHAT’S Included Install the Main Cabinet Installation and ConfigurationTower UPS Installation Connectors Spacers Support BasesRack-Mount UPS Installation Installing the Adjustable Rack-Mount Kit-Sold SeparatelyOperation and Display Panel Rotated Clockwise 90 Degrees QuantityUPS or battery 813mmDepth Retaining latchInstallation and Configuration External Battery Cabinet Installation External battery cabinets connected to 6000VA Liebert GXT3Connect Input/Output Power Power distribution box removal from 5000 and 6000VA modelsInstall the Power Distribution Box on 5000 and 6000VA Models Branch circuit breaker ratings Distribution Box Electrical ConnectionsUnit Rating Maximum Breaker Rating Electrical specifications Terminal Block ConnectionsConnectors IT Power System Configuration-LiebertGXT3-6000RTL630OnlyRemove Screws Configuration Program Configuration Program FeaturesWhat You Will Need ON/Alarm Silence/Manual Battery Test Button Controls and IndicatorsUpper indicator for L1 Lower for L2 Standby/Manual Bypass ButtonBattery Level Indicators 5 Green Load Level Indicators 4 Green, 1 AmberLiebert GXT3 has UPS status indicators UPS Status IndicatorsUPS Status Indicator Icon Color Description Initial Startup and Electrical Checks Startup Checklist for the Liebert GXT3Operation Manual Battery Test Disconnecting Input Power from the Liebert GXT3Maintenance Bypass Put the Liebert GXT3 in Manual BypassBattery Mode Shutdown Communication Interface PortTerminal Block CommunicationLow Battery On BatteryLiebert IntelliSlot Communication Cards Repo switch connection diagram Remote Emergency Power OffLiebert MultiLink Maintenance Replacing the Internal Battery PackBattery Replacement Procedures Battery Charging PrecautionsChecking UPS Status Replacing the Power Module on 8000 and 10,000VA modelsChecking UPS Functions Maintenance UPS Symptoms TroubleshootingIndicators Indicator Diagnosis/Audible alarmTroubleshooting Audible AlarmAudible alarm description Troubleshooting tableTroubleshooting table cont’d Specifications UPS specifications-5000, 6000, 8000 and 10,000 modelsUPS specifications-LiebertGXT3-6000RTL630 Dimensions, Rack Mount, W X D X H, in. mmWeight, lb kg Model Number GXT3-6000RTL630 Model RatingOperating temperature parameters Internal battery cabinet specificationsBattery Parameters External battery cabinet specifications Model NumberSee Table Environmental Power Distribution Box Model # Battery run time, minutes Number Load Percent 208/120VAC RT220VAC Tower Batteries Capacity 5kVA 6kVA 8kVA 10kVA 6kVA L630Auto-Learning Battery Run Times Page Net Is tTwork Care