Emerson GXT3-6000RT208 user manual Checking UPS Status, Checking UPS Functions

Page 39

Maintenance

10.4Checking UPS Status

Emerson recommends checking the UPS operation status every six months.

Check whether the UPS is faulty: Is the Fault Indicator on? Is the UPS sounding an alarm?

Check whether the UPS is operating in Bypass Mode. Normally, the UPS operates in Normal Mode. If it is operating in Bypass Mode, stop and contact your local Emerson representative, or Emerson Channel Support.

Check whether the battery is discharging. When the utility input is normal, the battery should not discharge. If the UPS is operating in Battery Mode, stop and contact your local Emerson rep- resentative or Emerson Channel Support.

10.5Checking UPS Functions

NOTE

UPS function check procedures may interrupt power supply to the connected load.

Emerson recommends checking the UPS functions once every six months.

Back up the load data before conducting the UPS functions check. Procedures are as follows:

1.Press the Standby/Manual Bypass button to check whether the buzzer and indicators are normal.

2.Press the On/Alarm Silence/Manual Battery Test button to check again whether the indicators are on and the UPS is operating normally.

3.Press the On/Alarm Silence/Manual Battery Test button for three seconds after Inverter Mode. The UPS should initiate a battery self-test. Check to determine whether the battery is operating normally. If not, stop and contact your local Emerson representative or Emerson Channel Support.

10.6Replacing the Power Module on 8000 and 10,000VA models

! CAUTION

The UPS must be switched to manual bypass before personnel begin to replace the power module.

NOTICE

During the procedure, the connected load will not be protected from power disturbances, such as spikes, sags and failure.

To remove the UPS power module without shutting off power to the connected load:

1.Place the UPS on internal bypass. This may be done by any of the three following methods:

a.Press the Off button on the front panel one time.

b.Slide the bracket away from the manual bypass switch on the rear of the UPS; this requires loosening the captive screw and sliding the bracket away from the manual bypass switch.

c.Remove the front grille covering the power module.

2.Move the manual bypass breaker on the rear of the UPS to the bypass position; this requires loosening the captive screw and sliding the bracket away from the manual bypass switch (see Figure 7).

3.Open the input circuit breaker on the rear of the UPS (see Figure 7).

4.Open the output circuit breaker on the rear of the UPS (see Figure 7).

5.Remove the top two front plastic bezels by pulling them forward.

6.Remove the power module cover grille and the battery cover grille with the screws securing them to the frame.

7.Disconnect the slotted battery connectors from the internal battery packs.

8.If additional external batteries are used, disconnect the two external battery connectors.

9.Slide power module restraint lever up out of the locked position.

10.Slide the power module out the front, supporting its weight as it is withdrawn.

33

Image 39
Contents Liebert GXT3 208V,5000-10,000VA, 6000RTL630 Page Table of Contents Specifications MaintenanceFigures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction DC-to-DC Converter Rectifier/Power Factor Correction PFC CircuitBattery Charger InverterDynamic Bypass BatteryMajor Components USB Port Liebert Knockouts for HardwiredMaintenance Bypass Breaker Input Input Breaker PD2-HDWR-MBS Main Frame and ElectronicsOutput Breaker Terminal Block Repo ConnectionReceptacles four 5-20R two L6-30 Removable Power Distribution BoxPD2-006 Receptacles four L6-20RInternal battery pack features Internal Battery PacksWHAT’S Included Connectors Spacers Support Bases Install the Main CabinetInstallation and Configuration Tower UPS InstallationQuantity Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately Operation and Display Panel Rotated Clockwise 90 DegreesRetaining latch UPS or battery813mm DepthInstallation and Configuration External battery cabinets connected to 6000VA Liebert GXT3 External Battery Cabinet InstallationPower distribution box removal from 5000 and 6000VA models Connect Input/Output PowerInstall the Power Distribution Box on 5000 and 6000VA Models Distribution Box Electrical Connections Branch circuit breaker ratingsUnit Rating Maximum Breaker Rating Terminal Block Connections Electrical specificationsIT Power System Configuration-LiebertGXT3-6000RTL630Only ConnectorsRemove Screws Configuration Program Features Configuration ProgramWhat You Will Need Standby/Manual Bypass Button ON/Alarm Silence/Manual Battery Test ButtonControls and Indicators Upper indicator for L1 Lower for L2Load Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenLiebert GXT3 has UPS Status Indicators UPS status indicatorsUPS Status Indicator Icon Color Description Startup Checklist for the Liebert GXT3 Initial Startup and Electrical ChecksOperation Put the Liebert GXT3 in Manual Bypass Manual Battery TestDisconnecting Input Power from the Liebert GXT3 Maintenance BypassCommunication Battery Mode ShutdownCommunication Interface Port Terminal BlockOn Battery Low BatteryLiebert IntelliSlot Communication Cards Remote Emergency Power Off Repo switch connection diagramLiebert MultiLink Replacing the Internal Battery Pack MaintenanceBattery Replacement Procedures Precautions Battery ChargingReplacing the Power Module on 8000 and 10,000VA models Checking UPS StatusChecking UPS Functions Maintenance Indicator Diagnosis/Audible alarm UPS SymptomsTroubleshooting IndicatorsTroubleshooting table TroubleshootingAudible Alarm Audible alarm descriptionTroubleshooting table cont’d UPS specifications-5000, 6000, 8000 and 10,000 models SpecificationsModel Number GXT3-6000RTL630 Model Rating UPS specifications-LiebertGXT3-6000RTL630Dimensions, Rack Mount, W X D X H, in. mm Weight, lb kgInternal battery cabinet specifications Operating temperature parametersExternal battery cabinet specifications Model Number Battery ParametersSee Table Environmental Power Distribution Box Model # Batteries Capacity 5kVA 6kVA 8kVA 10kVA 6kVA L630 Battery run time, minutesNumber Load Percent 208/120VAC RT 220VAC TowerAuto-Learning Battery Run Times Page Care NetIs t Twork