Communication

9.0COMMUNICATION

9.1Communication Interface Port

The Liebert® GXT3UPS has a terminal block on the rear of the UPS unit. Several signals are pro- vided on this port and are assigned as follows.

9.2Terminal Block

The terminal block includes eight pins, as shown in Figure 21.

Figure 21 Terminal block communication pin layout

1

Low Battery

Warning

9.2.1Any-Mode Shutdown

2

On-Battery Warning

3 4

Any Mode Battery Mode Shutdown Shutdown

The purpose of Any Mode Shutdown is to shut down the UPS output by turning Off the rectifier, inverter and static switch so that there is no power to the loads.

Any Mode Shutdown can be operated locally or remotely:

Local Any Mode Shutdown can be performed by shorting the pins in Set 3.

Remote Any Mode Shutdown can be performed using a switch connected to the pins in Set 3 and mounted at a remote location.

Activation of the Any Mode Shutdown will be logged as an event in the event history log.

NOTE

Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown. The current limited source for the optocoupler (+12VDC, 50mA) will be available from UPS. The connection to UPS for remote connection will be via terminal block connector.

Any Mode Shutdown wiring must conform to all national, regional and local wiring codes and laws.

! WARNING

When the Auto-enable output option is selected and the UPS output is disabled using the pins in Set 3, the Liebert GXT3’s output can turn On automatically and without warning if the connection of the pins in Set 3 is changed.

9.2.2Battery Mode Shutdown

Battery Mode Shutdown permits shutting down the UPS by turning off the rectifier, inverter and static switch so that there is no power to the load when the UPS is On Battery. The auxiliary power for the UPS will still be active.

Battery Mode Shutdown can be performed locally or remotely:

Local Battery Mode shutdown can be performed by shorting the pins in Set 4.

Remote Battery Mode Shutdown can be performed using a switch connected to the pins in Set 4 and mounted at remote location.

28

Image 34
Contents Liebert GXT3 208V,5000-10,000VA, 6000RTL630 Page Table of Contents Maintenance SpecificationsFigures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Inverter Rectifier/Power Factor Correction PFC CircuitBattery Charger DC-to-DC ConverterBattery Dynamic BypassMain Frame and Electronics USB Port Liebert Knockouts for HardwiredMaintenance Bypass Breaker Input Input Breaker PD2-HDWR-MBS Major ComponentsTerminal Block Repo Connection Output BreakerReceptacles four L6-20R Removable Power Distribution BoxPD2-006 Receptacles four 5-20R two L6-30Internal Battery Packs Internal battery pack featuresWHAT’S Included Tower UPS Installation Install the Main CabinetInstallation and Configuration Connectors Spacers Support BasesOperation and Display Panel Rotated Clockwise 90 Degrees Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityDepth UPS or battery813mm Retaining latchInstallation and Configuration External Battery Cabinet Installation External battery cabinets connected to 6000VA Liebert GXT3Connect Input/Output Power Power distribution box removal from 5000 and 6000VA modelsInstall the Power Distribution Box on 5000 and 6000VA Models Branch circuit breaker ratings Distribution Box Electrical ConnectionsUnit Rating Maximum Breaker Rating Electrical specifications Terminal Block ConnectionsConnectors IT Power System Configuration-LiebertGXT3-6000RTL630OnlyRemove Screws Configuration Program Configuration Program FeaturesWhat You Will Need Upper indicator for L1 Lower for L2 ON/Alarm Silence/Manual Battery Test ButtonControls and Indicators Standby/Manual Bypass ButtonBattery Level Indicators 5 Green Load Level Indicators 4 Green, 1 AmberLiebert GXT3 has UPS status indicators UPS Status IndicatorsUPS Status Indicator Icon Color Description Initial Startup and Electrical Checks Startup Checklist for the Liebert GXT3Operation Maintenance Bypass Manual Battery TestDisconnecting Input Power from the Liebert GXT3 Put the Liebert GXT3 in Manual BypassTerminal Block Battery Mode ShutdownCommunication Interface Port CommunicationLow Battery On BatteryLiebert IntelliSlot Communication Cards Repo switch connection diagram Remote Emergency Power OffLiebert MultiLink Maintenance Replacing the Internal Battery PackBattery Replacement Procedures Battery Charging PrecautionsChecking UPS Status Replacing the Power Module on 8000 and 10,000VA modelsChecking UPS Functions Maintenance Indicators UPS SymptomsTroubleshooting Indicator Diagnosis/Audible alarmAudible alarm description TroubleshootingAudible Alarm Troubleshooting tableTroubleshooting table cont’d Specifications UPS specifications-5000, 6000, 8000 and 10,000 modelsWeight, lb kg UPS specifications-LiebertGXT3-6000RTL630Dimensions, Rack Mount, W X D X H, in. mm Model Number GXT3-6000RTL630 Model RatingOperating temperature parameters Internal battery cabinet specificationsBattery Parameters External battery cabinet specifications Model NumberSee Table Environmental Power Distribution Box Model # 220VAC Tower Battery run time, minutesNumber Load Percent 208/120VAC RT Batteries Capacity 5kVA 6kVA 8kVA 10kVA 6kVA L630Auto-Learning Battery Run Times Page Twork NetIs t Care