Emerson GXT3-6000RT208 Liebert IntelliSlot Communication Cards, On Battery, Low Battery

Page 35

Communication

Activation of the Battery Mode Shutdown will be logged as an event in the event history log.

NOTE

Remote Power Off will be performed by NO contact.

The current limited source for the optocoupler (+12VDC, 50mA) will be available from UPS.

The connection to the Liebert® GXT3for remote connection will be via terminal block connector.

Battery Mode Shutdown wiring must conform to all national, regional and local wiring codes and laws.

This signal must last for 1.5 seconds or longer.

A battery shutdown signal will not cause an immediate shutdown. It will start a 2-minute shutdown timer. This timer cannot be stopped once triggered. If the utility power returns during this countdown, the Liebert GXT3 will still shut down and must remain shut down for 10 seconds. Whether the UPS turns back On when the power is restored depends on the auto-restart setting.

9.2.3On Battery

On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery this dry contact will be closed.

9.2.4Low Battery

Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery and has reached the Low Battery Warning time selected in the configuration pro- gram, this dry contact will be closed.

NOTE

The rated values for the dry contacts for the On Battery and Low Battery signals are:

Rated Voltage: 30V (AC or DC)

Rated Current: 300mA

9.3Liebert IntelliSlot® Communication Cards

The Liebert IntelliSlot port accepts three optional cards:

Liebert IntelliSlot SNMP Card

Liebert IntelliSlot Relay Card

Liebert IntelliSlot 485 Card.

The Liebert IntelliSlot SNMP Card provides SNMP monitoring and control of the UPS across the net- work.

The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom-wired applications and delivers support for built-in shutdown for AS/400 systems.

The Liebert IntelliSlot 485 Card is used to connect the UPS and computer system.

Follow instructions provided with the Liebert IntelliSlot card to configure Liebert MultiLink®, the UPS or any additional ancillary product for the Liebert GXT3. These instructions are available at

multilink.liebert.com

29

Image 35
Contents Liebert GXT3 208V,5000-10,000VA, 6000RTL630 Page Table of Contents Specifications MaintenanceFigures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction DC-to-DC Converter Rectifier/Power Factor Correction PFC CircuitBattery Charger InverterDynamic Bypass BatteryMajor Components USB Port Liebert Knockouts for HardwiredMaintenance Bypass Breaker Input Input Breaker PD2-HDWR-MBS Main Frame and ElectronicsOutput Breaker Terminal Block Repo ConnectionReceptacles four 5-20R two L6-30 Removable Power Distribution BoxPD2-006 Receptacles four L6-20RInternal battery pack features Internal Battery PacksWHAT’S Included Connectors Spacers Support Bases Install the Main CabinetInstallation and Configuration Tower UPS InstallationQuantity Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately Operation and Display Panel Rotated Clockwise 90 DegreesRetaining latch UPS or battery813mm DepthInstallation and Configuration External battery cabinets connected to 6000VA Liebert GXT3 External Battery Cabinet InstallationPower distribution box removal from 5000 and 6000VA models Connect Input/Output PowerInstall the Power Distribution Box on 5000 and 6000VA Models Unit Rating Maximum Breaker Rating Distribution Box Electrical ConnectionsBranch circuit breaker ratings Terminal Block Connections Electrical specificationsRemove Screws IT Power System Configuration-LiebertGXT3-6000RTL630OnlyConnectors What You Will Need Configuration Program FeaturesConfiguration Program Standby/Manual Bypass Button ON/Alarm Silence/Manual Battery Test ButtonControls and Indicators Upper indicator for L1 Lower for L2Liebert GXT3 has Load Level Indicators 4 Green, 1 AmberBattery Level Indicators 5 Green UPS Status Indicator Icon Color Description UPS Status IndicatorsUPS status indicators Operation Startup Checklist for the Liebert GXT3Initial Startup and Electrical Checks Put the Liebert GXT3 in Manual Bypass Manual Battery TestDisconnecting Input Power from the Liebert GXT3 Maintenance BypassCommunication Battery Mode ShutdownCommunication Interface Port Terminal BlockLiebert IntelliSlot Communication Cards On BatteryLow Battery Liebert MultiLink Remote Emergency Power OffRepo switch connection diagram Battery Replacement Procedures Replacing the Internal Battery PackMaintenance Precautions Battery ChargingChecking UPS Functions Replacing the Power Module on 8000 and 10,000VA modelsChecking UPS Status Maintenance Indicator Diagnosis/Audible alarm UPS SymptomsTroubleshooting IndicatorsTroubleshooting table TroubleshootingAudible Alarm Audible alarm descriptionTroubleshooting table cont’d UPS specifications-5000, 6000, 8000 and 10,000 models SpecificationsModel Number GXT3-6000RTL630 Model Rating UPS specifications-LiebertGXT3-6000RTL630Dimensions, Rack Mount, W X D X H, in. mm Weight, lb kgInternal battery cabinet specifications Operating temperature parametersSee Table Environmental External battery cabinet specifications Model NumberBattery Parameters Power Distribution Box Model # Batteries Capacity 5kVA 6kVA 8kVA 10kVA 6kVA L630 Battery run time, minutesNumber Load Percent 208/120VAC RT 220VAC TowerAuto-Learning Battery Run Times Page Care NetIs t Twork