Page 23

Installation and Configuration

NOTE

If the UPS is to be shipped or stored for an extended time, the connector should be disconnected. This will minimize any standby current drain on the batteries and help attain their design life.

5.3Connect Input/Output Power

! WARNING

Risk of electric shock. Can cause injury or death.

Disconnect all local and remote electric power supplies before working within. Ensure that the Liebert® GXT3is shut down and power has been disconnected before beginning any work on or in the unit.

The Liebert GXT3-5000RT208, Liebert GXT3-6000RT208and Liebert GXT3-6000RTL630are shipped with a power distribution box attached. The Liebert GXT3-8000RT208and Liebert GXT3-10000RT208are shipped with a cover plate over the power distribution connector.

Follow the instructions below for removal and installation.

NOTE

Do not operate the UPS with the power distribution box removed. To shut off all power to this box and to the load, utility input power must be disconnected.

5.3.1Remove the Power Distribution Box from 5000 and 6000VA Models

1.Put the Liebert GXT3 in maintenance bypass by pressing the Standby/Manual Bypass button while the UPS is in Utility (AC) Mode and holding the button for about 2 seconds. (For help, refer to 8.4 - Put the Liebert® GXT3in Manual Bypass.)

2.Loosen the captive screw over the maintenance bypass breaker (see Figure 13 for the breaker’s location).

3.Turn the maintenance bypass breaker On.

NOTICE

The load is unprotected from disturbances in the power supply while the UPS is on bypass.

4.Turn the output and input breakers Off.

5.Loosen other captive screws until the power distribution box releases.

6.Remove the power distribution box from the UPS and set it aside.

7.Loosen the screws over the plastic cover for the connector on the rear of the panel.

8.Slide the plastic cover over the connector and tighten the screws.

Figure 13 Power distribution box removal from 5000 and 6000VA models

Extract these four captive screws

Pigtails removed for clarity

Maintenance Bypass Breaker

17

Image 23
Contents Liebert GXT3 208V,5000-10,000VA, 6000RTL630 Page Table of Contents Specifications MaintenanceFigures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction DC-to-DC Converter Rectifier/Power Factor Correction PFC CircuitBattery Charger InverterDynamic Bypass BatteryMajor Components USB Port Liebert Knockouts for HardwiredMaintenance Bypass Breaker Input Input Breaker PD2-HDWR-MBS Main Frame and ElectronicsOutput Breaker Terminal Block Repo ConnectionReceptacles four 5-20R two L6-30 Removable Power Distribution BoxPD2-006 Receptacles four L6-20RInternal battery pack features Internal Battery PacksWHAT’S Included Connectors Spacers Support Bases Install the Main CabinetInstallation and Configuration Tower UPS InstallationQuantity Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately Operation and Display Panel Rotated Clockwise 90 DegreesRetaining latch UPS or battery813mm DepthInstallation and Configuration External battery cabinets connected to 6000VA Liebert GXT3 External Battery Cabinet InstallationPower distribution box removal from 5000 and 6000VA models Connect Input/Output PowerInstall the Power Distribution Box on 5000 and 6000VA Models Unit Rating Maximum Breaker Rating Distribution Box Electrical ConnectionsBranch circuit breaker ratings Terminal Block Connections Electrical specificationsRemove Screws IT Power System Configuration-LiebertGXT3-6000RTL630OnlyConnectors What You Will Need Configuration Program FeaturesConfiguration Program Standby/Manual Bypass Button ON/Alarm Silence/Manual Battery Test ButtonControls and Indicators Upper indicator for L1 Lower for L2Liebert GXT3 has Load Level Indicators 4 Green, 1 AmberBattery Level Indicators 5 Green UPS Status Indicator Icon Color Description UPS Status IndicatorsUPS status indicators Operation Startup Checklist for the Liebert GXT3Initial Startup and Electrical Checks Put the Liebert GXT3 in Manual Bypass Manual Battery TestDisconnecting Input Power from the Liebert GXT3 Maintenance BypassCommunication Battery Mode ShutdownCommunication Interface Port Terminal BlockLiebert IntelliSlot Communication Cards On BatteryLow Battery Liebert MultiLink Remote Emergency Power OffRepo switch connection diagram Battery Replacement Procedures Replacing the Internal Battery PackMaintenance Precautions Battery ChargingChecking UPS Functions Replacing the Power Module on 8000 and 10,000VA modelsChecking UPS Status Maintenance Indicator Diagnosis/Audible alarm UPS SymptomsTroubleshooting IndicatorsTroubleshooting table TroubleshootingAudible Alarm Audible alarm descriptionTroubleshooting table cont’d UPS specifications-5000, 6000, 8000 and 10,000 models SpecificationsModel Number GXT3-6000RTL630 Model Rating UPS specifications-LiebertGXT3-6000RTL630Dimensions, Rack Mount, W X D X H, in. mm Weight, lb kgInternal battery cabinet specifications Operating temperature parametersSee Table Environmental External battery cabinet specifications Model NumberBattery Parameters Power Distribution Box Model # Batteries Capacity 5kVA 6kVA 8kVA 10kVA 6kVA L630 Battery run time, minutesNumber Load Percent 208/120VAC RT 220VAC TowerAuto-Learning Battery Run Times Page Care NetIs t Twork