Emerson MSM400 manual Mobrey

Page 1

Instruction Leaflet

IP258

November 2004

Level

Mobrey

MSM400 Intelligent Suspended Solids Monitor

Software Version 1.1

www.mobrey.com

Image 1
Contents Mobrey Contents Safety Precautions Display Sensor Connection IVE Neutral Earth MainsENT Product Description Product Introduction MSM400 Slurry Monitoring SystemUltrasonic Attenuation versus Suspended solids Slurry CharacteristicsMobrey Pipe Section Sensors Suspended Sensor Type MSM433Sensor Type Numbering System MSM400 Displays and Keypad Control UnitKeypad Operation Hart SPECIFICATIONS--MSM400EMC Suspended Sensor Installation Pipe Section InstallationPreliminary Checks Control Unit Sensor CablesTerminal Label Function Sensor Connections Hart Connections and Jumper SettingsRelays Current OutputInitial Power UP Safety PrecautionsMains Supply Toggle RUN Calibration Setup Monitor Main Menu Toggle RUN Calibration SetupToggle RUN EX-FACTORY System Features Diagnostic ParametersZero Setting Initial Zero Rechecking Zero Calibration Methods Auto CAL Auto CAL Zero Setting ProcedureClear Liquor Press ENT To set 23.1dB 26.2dB Autocal Span Setting ProcedureAuto CAL LAB Values Sample Press ENT to set 33.6dB 44.2dBMaximum % Solids Zero Setting ProcedureSpan CALIBRATION/GRADIENT Methods Calibration Method 1-SLURRY TypeAttenuation VALUE-METHOD No. of operation Set Default value Max value Hrs & mins Duty Mode Desludge ModeStart on Stop on Stop if Do not start if INPUT↓ Output Start Time #1 hm 730 P254 Relay Operation Outputs Current OutputMiddle Display Alarm←−−−−−−− Lower Display Display option parameter number DescriptionEngineering Frequency SET SettingsSystem Test Current Output Sensors Hart Smart CommunicationsMain Menu SUB Menu Parameter Description Appendix A1Par No Diagnostics Alarm ReportLogging EngineeringParameter Description Min Max Default ValueMSM400 Monit Parameter Description Min Max Default ValueFrom list 3.6/21mA/hold last reading Min Max Default Value Ex-Factory Manufacturer’s Code Hart Considerations Appendix A3 Hart and Psion Operating InstructionsSmart Communication with the Mobrey MSM400 Calibration adjustments at operating conditionsFurther customisation using the Smart HHC Handheld Communicator Mobrey CK Hand Held Communicator Assembly InstructionsFig DII. Loop diagram Fig D1 MOBREY-CK* HHC assembly How to connect the Smart Communicator Hand Held Communicator Operation How to drive a Psion based Smart Communicator Mobrey Find Save Diary Calc Time Notes World AlarmTAG Tank D7.0 Introduction and Function menu HelpD7.2 Program Parameters P D7.1 Monitor/Display Parameters DMode KEY Default RegisterWorking Register Safe RegisterHand Held Communicator Registers Select Data Source 10.1Alarm and Error Messages 10.0ERROR Messages on the HHCPrintout or PC transfer of MSM400 programme data Display of Parameter Data10.2Invalid Data Entry Instrument in Multidrop Mode Password not Open10.3Communication Errors Invalid Action not the Same InstrumentD0 D8 11.0Current Loop Checks and Trimming Current Output ** Set current Trim-maximum Trim-maximum12.0Unknown Instrument Current and USE ↑ & ↓ To Trim the Output13.3Use of multiple Smart Communicators D13.0 Smart Interfaces Compatibility D13.1 IntroductionAbcdef