2.0SMART COMMUNICATION WITH THE MOBREY MSM400
With a SMART HHC, you can make adjustments and calibrate your MSM400 at any point on the two wire connection to the control unit. You can also make many other adjustments and obtain operational and diagnostic information using the HHC.
Alternatively, Mobrey have a PC based software package called Mobrey
If you have a Mobrey type CK HHC (Psion Organiser based) and the appropriate datapak, refer now to Appendix D for details of assembly, connection and menu structure before reading on to the specific adjustments listed below.
If you have another type of SMART communicator or computer based software tool, you must ensure that the MSM400 Device Description (DD) is correctly loaded or compiled to gain access to all of the MLT parameters. If you do not have the MSM400 DD loaded, you will only be able to access the Universal and Common Practice commands.
Contact or any other HART Host Subscriber to update your communication device with the latest MSM400 DD.
The MSM400 control unit is a SMART instrument using the HART protocol to communicate with external devices.
The Mobrey HHC is a
By connecting the HHC across the two wire loop at any point downstream of the minimum 250 Ohm loop resistance, communication can be established. The MSM400 has integral test pins provided for this purpose. Refer to Appendix D3.0 for details of HHC connection and operation.
The following paragraph details how to
2.1Calibration adjustments at operating conditions.
Important note : Making changes to the position or span of the
4mA point – from the “Program” menu / “Calibrate”
Enter the desired new value of the PV (Process Value), normally the sludge level in % solids, required to give a 4mA output, and confirm when prompted by pressing the “exe” key that this is correct. The new value is now entered and saved.
Note, the 4mA point can be positioned above the 20mA point to reverse the operation of the control unit, thus giving a falling current output with rising sludge level.
20mA point – from the “Program” menu / “Calibrate”
Enter the desired new value of the PV (Process Value), required to give a 20mA output, and confirm when prompted by pressing the “exe” key that this is correct. The new value is now entered and saved.
Damping – from the “Program” menu / “Engineer”
Enter the desired new value in seconds and press “exe” to confirm and save the new value.