Emerson MSM400 manual Alarm, Middle Display, ←−−−−−−− Lower Display, Backlight

Page 28

c) ALARM

The relays can be set for alarm mode conditions by selecting the option in SETUP – OUTPUT – RELAY – Relay * mode. See the section below titled ALARM.

7.4ALARM

There are six different alarms in the SETUP - OUTPUT - ALARM menu. Each alarm can be set to operate a relay, or drive the current output, or both, or neither to the following states.

1.Current output - 3.6mA, 21mA, Hold as defined in “Alarm action” in the CURRENT OUTPUT menu.

2.Relay outputs – The relays energise in the alarm condition

The relays or current output must be set up for alarm or fault action for this function to operate. The effects of each alarm action are shown in the list below :

1.Memory fault

2.PV out of limits

3.Current saturated

4.Temperature out of limits - this refers to the temperature within the control housing.

5.Digital input 1 active

7.5DISPLAY

The display has 3 sections which can be programmed to display a selection of variables. Each section has a parameter which is used to select the variable which is displayed. They are located in SET-OUTPUT-DISPLAY. The required option is selected from the list as shown below.

 

11:59 0

←−− UPPER DISPLAY

0

12.35

0

MIDDLE DISPLAY

0

←−−−−−−−−−

 

 

←−−−−−−− LOWER DISPLAY

 

 

 

 

 

Display option parameter number

Description

 

 

 

 

 

 

D800

PV process value

 

 

 

 

 

 

D801

Sludge density

 

 

 

 

 

 

D805

% Current out

 

 

 

 

 

 

D806

Current output (mA)

 

 

 

 

 

 

D821

RL1 run time

 

 

 

 

 

 

D822

RL2 run time

 

 

 

 

 

 

D844

Control unit temperature

 

 

 

 

 

 

D850

Attenuation at 1 MHz

 

 

 

 

 

 

D851

Attenuation at 3.3 MHz

 

 

 

 

 

 

D860

Sensor frequency

 

 

 

 

 

 

P730

Date

 

 

 

 

 

 

P731

Time

 

 

 

 

 

 

Bargraph

Please note that the bargraph only works on the

 

 

 

lower display and it shows % current output.

 

 

 

 

 

7.6 BACKLIGHT

 

 

 

 

IP258

28

Image 28
Contents Mobrey Contents Safety Precautions Display Sensor Connection IVE Neutral Earth MainsENT Product Introduction MSM400 Slurry Monitoring System Product DescriptionSlurry Characteristics Ultrasonic Attenuation versus Suspended solidsSuspended Sensor Type MSM433 Mobrey Pipe Section SensorsSensor Type Numbering System MSM400 Displays and Keypad Control UnitKeypad Operation Hart SPECIFICATIONS--MSM400EMC Suspended Sensor Installation Pipe Section InstallationPreliminary Checks Sensor Cables Control UnitTerminal Label Function Hart Connections and Jumper Settings Sensor ConnectionsRelays Current OutputInitial Power UP Safety PrecautionsMains Supply Main Menu Toggle RUN Calibration Setup Toggle RUN Calibration Setup MonitorToggle RUN EX-FACTORY System Features Diagnostic ParametersZero Setting Initial Zero Calibration Methods Auto CAL Auto CAL Zero Setting Procedure Rechecking ZeroAutocal Span Setting Procedure Clear Liquor Press ENT To set 23.1dB 26.2dBSample Press ENT to set 33.6dB 44.2dB Auto CAL LAB ValuesZero Setting Procedure Maximum % SolidsSpan CALIBRATION/GRADIENT Methods Calibration Method 1-SLURRY TypeAttenuation VALUE-METHOD No. of operation Set Default value Max value Hrs & mins Duty Mode Desludge ModeStart on Stop on Stop if Do not start if INPUT↓ Output Start Time #1 hm 730 P254 Outputs Current Output Relay OperationAlarm Middle Display←−−−−−−− Lower Display Display option parameter number DescriptionEngineering Frequency SET SettingsSystem Test Current Output Hart Smart Communications SensorsMain Menu SUB Menu Parameter Description Appendix A1Par No Alarm Report DiagnosticsLogging EngineeringMin Max Default Value Parameter DescriptionParameter Description Min Max Default Value MSM400 MonitFrom list 3.6/21mA/hold last reading Min Max Default Value Ex-Factory Manufacturer’s Code Appendix A3 Hart and Psion Operating Instructions Hart ConsiderationsCalibration adjustments at operating conditions Smart Communication with the Mobrey MSM400Further customisation using the Smart HHC Hand Held Communicator Assembly Instructions Handheld Communicator Mobrey CKFig DII. Loop diagram Fig D1 MOBREY-CK* HHC assembly How to connect the Smart Communicator Hand Held Communicator Operation Mobrey Find Save Diary Calc Time Notes World Alarm How to drive a Psion based Smart CommunicatorTAG Tank Help D7.0 Introduction and Function menuD7.1 Monitor/Display Parameters D D7.2 Program Parameters PDefault Register Mode KEYWorking Register Safe RegisterHand Held Communicator Registers Select Data Source 10.0ERROR Messages on the HHC 10.1Alarm and Error MessagesPrintout or PC transfer of MSM400 programme data Display of Parameter Data10.2Invalid Data Entry Password not Open Instrument in Multidrop Mode10.3Communication Errors Invalid Action not the Same InstrumentD0 D8 Current Output ** Set current Trim-maximum Trim-maximum 11.0Current Loop Checks and TrimmingCurrent and USE ↑ & ↓ To Trim the Output 12.0Unknown InstrumentD13.0 Smart Interfaces Compatibility D13.1 Introduction 13.3Use of multiple Smart CommunicatorsAbcdef