Emerson MSM400 manual Current and USE ↑ & ↓ To Trim the Output, 12.0Unknown Instrument

Page 58

D11.2

Trim Current

If the procedure shown above suggests that there is a calibration difference between the MSM400 output and other current monitoring equipment on the loop, it will be necessary to use a calibrated meter to establish which unit is in error. Using the “Set current” routine of the MSM400 can be instructed to provide outputs between 4 and 20mA that the MSM400 considers correct. If these are in error, the “Trim current” routine is used as follows:

The “Trim current” selection sets the current output of the MSM400 either at maximum (supposed to be 20mA) or minimum (supposed to be 4mA) depending on the option selected.

For maximum the display shows:

CURRENT OUTPUT IS

NOW 20mA. MEASURE

CURRENT AND USE &

TO TRIM THE OUTPUT

Follow the instructions and if the current output is in error, i.e. not 20mA, use the ↑ and ↓ arrows as trimming signals to adjust the value to be exactly 20mA. Each press of the arrow causes an audible signal and adjusts the output value by a discrete step. (approx 6μA)

This process should then be repeated for the 4mA setting. Once the current output is seen to be correct the ON/CLEAR key is used to escape.

Mode Cancelled Warning

If while trimming or fixing the current the analog output returns to its normal mode the message FIXED CURRENT MODE CANCELLED will be displayed. This could occur for three reasons, master has sent the appropriate command, the MSM400 has been powered off then on again, or the output in fixed current mode has been at the same value for 20 minutes.

D.12.0Unknown Instrument

This limited support for unknown control unit is provided so that the identification and basic performance of any control unit can be obtained without having to change to another HHC. This is of particular use in multi-drop networks where all the currently occupied addresses need to be identified when selecting an address for an additional control unit on the loop.

If the control unit detected is not an MSM400, MSP100 or MLT100 then Unknown instrument is displayed and an access to the parameters is prompted for. If this is selected then the parameters that are present on all transmitters are uploaded, after first setting up any files that are required.

If the instrument conforms to revision 5 or higher of the HART protocol then the manufacturer of the instrument will be available. If it is of an earlier revision then only the model number will be available.

IP258

58

Image 58
Contents Mobrey Contents Safety Precautions Display Sensor Connection IVE Neutral Earth MainsENT Product Introduction MSM400 Slurry Monitoring System Product DescriptionSlurry Characteristics Ultrasonic Attenuation versus Suspended solidsSuspended Sensor Type MSM433 Mobrey Pipe Section SensorsSensor Type Numbering System MSM400 Displays and Keypad Control UnitKeypad Operation Hart SPECIFICATIONS--MSM400EMC Suspended Sensor Installation Pipe Section InstallationPreliminary Checks Sensor Cables Control UnitTerminal Label Function Relays Hart Connections and Jumper SettingsSensor Connections Current OutputInitial Power UP Safety PrecautionsMains Supply Main Menu Toggle RUN Calibration Setup Toggle RUN Calibration Setup MonitorToggle RUN EX-FACTORY System Features Diagnostic ParametersZero Setting Initial Zero Calibration Methods Auto CAL Auto CAL Zero Setting Procedure Rechecking ZeroAutocal Span Setting Procedure Clear Liquor Press ENT To set 23.1dB 26.2dBSample Press ENT to set 33.6dB 44.2dB Auto CAL LAB ValuesSpan CALIBRATION/GRADIENT Methods Zero Setting ProcedureMaximum % Solids Calibration Method 1-SLURRY TypeAttenuation VALUE-METHOD No. of operation Set Default value Max value Hrs & mins Duty Mode Desludge ModeStart on Stop on Stop if Do not start if INPUT↓ Output Start Time #1 hm 730 P254 Outputs Current Output Relay Operation←−−−−−−− Lower Display AlarmMiddle Display Display option parameter number DescriptionEngineering Frequency SET SettingsSystem Test Current Output Hart Smart Communications SensorsMain Menu SUB Menu Parameter Description Appendix A1Par No Logging Alarm ReportDiagnostics EngineeringMin Max Default Value Parameter DescriptionParameter Description Min Max Default Value MSM400 MonitFrom list 3.6/21mA/hold last reading Min Max Default Value Ex-Factory Manufacturer’s Code Appendix A3 Hart and Psion Operating Instructions Hart ConsiderationsCalibration adjustments at operating conditions Smart Communication with the Mobrey MSM400Further customisation using the Smart HHC Hand Held Communicator Assembly Instructions Handheld Communicator Mobrey CKFig DII. Loop diagram Fig D1 MOBREY-CK* HHC assembly How to connect the Smart Communicator Hand Held Communicator Operation Mobrey Find Save Diary Calc Time Notes World Alarm How to drive a Psion based Smart CommunicatorTAG Tank Help D7.0 Introduction and Function menuD7.1 Monitor/Display Parameters D D7.2 Program Parameters PWorking Register Default RegisterMode KEY Safe RegisterHand Held Communicator Registers Select Data Source Printout or PC transfer of MSM400 programme data 10.0ERROR Messages on the HHC10.1Alarm and Error Messages Display of Parameter Data10.2Invalid Data Entry 10.3Communication Errors Password not OpenInstrument in Multidrop Mode Invalid Action not the Same InstrumentD0 D8 Current Output ** Set current Trim-maximum Trim-maximum 11.0Current Loop Checks and TrimmingCurrent and USE ↑ & ↓ To Trim the Output 12.0Unknown InstrumentD13.0 Smart Interfaces Compatibility D13.1 Introduction 13.3Use of multiple Smart CommunicatorsAbcdef