Emerson MSM400 manual Outputs Current Output, Relay Operation

Page 27

7.1OUTPUTS

7.2CURRENT OUTPUT

The operation of the current output is set up by four different parameters and is always controlled by the process variable (PV), which is normally % suspended solids. These are found in SETUP – OUTPUT – CURRENT OUTPUT.

1.Lower range value (Low range val)

This is the value of PV which corresponds to the minimum current output, either 0 or 4mA

2.Upper range value (Up range val)

This is the value of PV which corresponds to the maximum current output, 20mA.

3.Alarm action

This is the value to which the current output is driven under alarm conditions and is selectable from a list.

3.6mA

21mA

Hold (i.e. hold last reading)

For alarm conditions see the section below titled ALARM.

4.0-20mA or 4-20mA setting (0/4-20mA)

This parameter sets the current output range to either 0-20mA or 4-20 and is selected from a list.

5.If required the 4-20mA can be trimmed using an external calibration meter. (For details see Section 7.8)

7.3RELAY OPERATION

The MSM400 controller offers various options for operating the relays.

There are 2 relays that are programmable to different modes, set point operation, de-sludge, alarm and fault. The mode of operation is selected through the SETUP – OUTPUT – RELAY – Relay Mode menu. The default mode for Relay 1 is set point operation and Relay 2 default mode is alarm.

a) SET POINT OPERATION

It is possible to program both relays for set point operation. These are found in SETUP – OUTPUT – RELAY. The process value (PV) controls the relays.

1.Relay on point (RL* On Point)

This is the value of PV at which each relay will turn on

2.Relay off point (RL* Off Point)

This is the value of PV at which each relay will turn off

3.Relay minimum on time (RL* Min ON)

This is the minimum time that the relay will stay on for and this takes priority over the maximum on time.

4.Relay maximum on time (RL* Max ON)

This is the maximum time that the relay will stay on for.

It is important to note that this function only operates when the minimum off time is set to a non zero value.

5.Relay minimum off time (RL* Min OFF)

Once the relay has turned off this is the minimum time before the relay will turn on again. (*=1or 2 i.e. relay one or two)

If both on and off parameters are set to zero then relay is turned off.

If the on and off points are equal (non-zero) the relay is on when PV is above the set point and off when below. If both minimum and maximum on times are set to zero (default) then they are not used.

(See also the example in “NAVIGATION IN THE MENU SYSTEM”).

b) DESLUDGE

When in desludge mode the relays operate as explained above.

IP258

27

Image 27
Contents Mobrey Contents Safety Precautions Sensor Connection IVE Neutral Earth Mains DisplayENT Product Description Product Introduction MSM400 Slurry Monitoring SystemUltrasonic Attenuation versus Suspended solids Slurry CharacteristicsMobrey Pipe Section Sensors Suspended Sensor Type MSM433Sensor Type Numbering System Control Unit MSM400 Displays and KeypadKeypad Operation SPECIFICATIONS--MSM400 HartEMC Pipe Section Installation Suspended Sensor InstallationPreliminary Checks Control Unit Sensor CablesTerminal Label Function Current Output Hart Connections and Jumper SettingsSensor Connections RelaysSafety Precautions Initial Power UPMains Supply Toggle RUN Calibration Setup Monitor Main Menu Toggle RUN Calibration SetupToggle RUN Diagnostic Parameters EX-FACTORY System FeaturesZero Setting Initial Zero Rechecking Zero Calibration Methods Auto CAL Auto CAL Zero Setting ProcedureClear Liquor Press ENT To set 23.1dB 26.2dB Autocal Span Setting ProcedureAuto CAL LAB Values Sample Press ENT to set 33.6dB 44.2dBCalibration Method 1-SLURRY Type Zero Setting ProcedureMaximum % Solids Span CALIBRATION/GRADIENT MethodsAttenuation VALUE-METHOD Duty Mode Desludge Mode No. of operation Set Default value Max value Hrs & mins Start on Stop on Stop if Do not start if INPUT↓ Output Start Time #1 hm 730 P254 Relay Operation Outputs Current OutputDisplay option parameter number Description AlarmMiddle Display ←−−−−−−− Lower DisplaySettings Engineering Frequency SETSystem Test Current Output Sensors Hart Smart CommunicationsAppendix A1 Main Menu SUB Menu Parameter DescriptionPar No Engineering Alarm ReportDiagnostics LoggingParameter Description Min Max Default ValueMSM400 Monit Parameter Description Min Max Default ValueFrom list 3.6/21mA/hold last reading Min Max Default Value Ex-Factory Manufacturer’s Code Hart Considerations Appendix A3 Hart and Psion Operating InstructionsSmart Communication with the Mobrey MSM400 Calibration adjustments at operating conditionsFurther customisation using the Smart HHC Handheld Communicator Mobrey CK Hand Held Communicator Assembly InstructionsFig DII. Loop diagram Fig D1 MOBREY-CK* HHC assembly How to connect the Smart Communicator Hand Held Communicator Operation How to drive a Psion based Smart Communicator Mobrey Find Save Diary Calc Time Notes World AlarmTAG Tank D7.0 Introduction and Function menu HelpD7.2 Program Parameters P D7.1 Monitor/Display Parameters DSafe Register Default RegisterMode KEY Working RegisterHand Held Communicator Registers Select Data Source Display of Parameter Data 10.0ERROR Messages on the HHC10.1Alarm and Error Messages Printout or PC transfer of MSM400 programme data10.2Invalid Data Entry Invalid Action not the Same Instrument Password not OpenInstrument in Multidrop Mode 10.3Communication ErrorsD0 D8 11.0Current Loop Checks and Trimming Current Output ** Set current Trim-maximum Trim-maximum12.0Unknown Instrument Current and USE ↑ & ↓ To Trim the Output13.3Use of multiple Smart Communicators D13.0 Smart Interfaces Compatibility D13.1 IntroductionAbcdef