(pre change) value : this prompts the operator to
If either of the above two Outgoing or Reply Comms Error messages occurs in a Backup menu transfer between registers, it is advisable to repeat the Backup operation to complete the data transfer, or check that the memory has been transferred correctly.
The message “NO RESPONSE FROM TRANSMITTER” Indicates a failure of the power on the loop or a failure of the connection of the SMART interface across the loop or the address of the instrument has been changed. Connection should be
The message “LOCKED OUT BY BUS ACTIVITY” indicates there are either two secondary masters on the bus or a primary master is continuously trying to access an instrument that does not exist.
The message “INCOMPLETE REPLY” indicates that a start of a message was detected but the message was not completed in the time allowed. This is most likely to be due to a power failure or a loss of connection.
D.11.0Current Loop Checks and Trimming
Introduction
The MSM400
Select “Current – Output” and the screen displayed is
** CURRENT OUTPUT ** Set current Trim-maximum Trim-maximum
These three functions are as follows:
D.11.1Set current
This selection is used for MSM400 transmitters attached to a single
By selecting the
ENTER NEW VALUE
12-
On pressing “EXE”, the current in the loop is set to this value, and the loop indicators and trips can be checked for function and calibration. The LCD screen changes to suggest selection of a new value if necessary. To abort the procedure press ON/CLEAR
CURRENT OUTPUT = 12 mA
ENTER NEW VALUE
-
Some specific error messages are used to prevent the loop current being set outside the valid
limits.
IP258
57