Emerson MSM400 manual Current Output ** Set current Trim-maximum Trim-maximum

Page 57

(pre change) value : this prompts the operator to re-enter the required new value. It is important that the Parameter is re-entered, to ensure that the Working register memory in both the Psion and the MSM400 contain the same data.

If either of the above two Outgoing or Reply Comms Error messages occurs in a Backup menu transfer between registers, it is advisable to repeat the Backup operation to complete the data transfer, or check that the memory has been transferred correctly.

The message “NO RESPONSE FROM TRANSMITTER” Indicates a failure of the power on the loop or a failure of the connection of the SMART interface across the loop or the address of the instrument has been changed. Connection should be re-established if possible.

The message “LOCKED OUT BY BUS ACTIVITY” indicates there are either two secondary masters on the bus or a primary master is continuously trying to access an instrument that does not exist.

The message “INCOMPLETE REPLY” indicates that a start of a message was detected but the message was not completed in the time allowed. This is most likely to be due to a power failure or a loss of connection.

D.11.0Current Loop Checks and Trimming

Introduction

The MSM400 4-20mA control unit has no customer or service engineering adjustable potentiometers on the printed circuit boards. All current trimming of the 4mA and 20mA set points is achieved via the SMART communicator. Because this is a “live” interaction, the access to this function is via the MONITOR functions and screen on the Communicator.

Select “Current – Output” and the screen displayed is

** CURRENT OUTPUT ** Set current Trim-maximum Trim-maximum

These three functions are as follows:

D.11.1Set current

This selection is used for MSM400 transmitters attached to a single 4-20mA loop to check for correct functioning of all the equipment – the MSM400, the communications and the other loop indicators and outputs.

By selecting the “Set-current” option the screen prompts the operator to choose a current value for the loop, for example 12mA.

ENTER NEW VALUE

12-

On pressing “EXE”, the current in the loop is set to this value, and the loop indicators and trips can be checked for function and calibration. The LCD screen changes to suggest selection of a new value if necessary. To abort the procedure press ON/CLEAR

CURRENT OUTPUT = 12 mA

ENTER NEW VALUE

-

Some specific error messages are used to prevent the loop current being set outside the valid 4-20mA

limits.

IP258

57

Image 57
Contents Mobrey Contents Safety Precautions Sensor Connection IVE Neutral Earth Mains DisplayENT Product Description Product Introduction MSM400 Slurry Monitoring SystemUltrasonic Attenuation versus Suspended solids Slurry CharacteristicsMobrey Pipe Section Sensors Suspended Sensor Type MSM433Sensor Type Numbering System Control Unit MSM400 Displays and KeypadKeypad Operation SPECIFICATIONS--MSM400 HartEMC Pipe Section Installation Suspended Sensor InstallationPreliminary Checks Control Unit Sensor CablesTerminal Label Function Sensor Connections Hart Connections and Jumper SettingsRelays Current OutputSafety Precautions Initial Power UPMains Supply Toggle RUN Calibration Setup Monitor Main Menu Toggle RUN Calibration SetupToggle RUN Diagnostic Parameters EX-FACTORY System FeaturesZero Setting Initial Zero Rechecking Zero Calibration Methods Auto CAL Auto CAL Zero Setting ProcedureClear Liquor Press ENT To set 23.1dB 26.2dB Autocal Span Setting ProcedureAuto CAL LAB Values Sample Press ENT to set 33.6dB 44.2dBMaximum % Solids Zero Setting ProcedureSpan CALIBRATION/GRADIENT Methods Calibration Method 1-SLURRY TypeAttenuation VALUE-METHOD Duty Mode Desludge Mode No. of operation Set Default value Max value Hrs & minsStart on Stop on Stop if Do not start if INPUT↓ Output Start Time #1 hm 730 P254 Relay Operation Outputs Current OutputMiddle Display Alarm←−−−−−−− Lower Display Display option parameter number DescriptionSettings Engineering Frequency SETSystem Test Current Output Sensors Hart Smart CommunicationsAppendix A1 Main Menu SUB Menu Parameter DescriptionPar No Diagnostics Alarm ReportLogging EngineeringParameter Description Min Max Default ValueMSM400 Monit Parameter Description Min Max Default ValueFrom list 3.6/21mA/hold last reading Min Max Default Value Ex-Factory Manufacturer’s Code Hart Considerations Appendix A3 Hart and Psion Operating InstructionsSmart Communication with the Mobrey MSM400 Calibration adjustments at operating conditionsFurther customisation using the Smart HHC Handheld Communicator Mobrey CK Hand Held Communicator Assembly InstructionsFig DII. Loop diagram Fig D1 MOBREY-CK* HHC assembly How to connect the Smart Communicator Hand Held Communicator Operation How to drive a Psion based Smart Communicator Mobrey Find Save Diary Calc Time Notes World AlarmTAG Tank D7.0 Introduction and Function menu HelpD7.2 Program Parameters P D7.1 Monitor/Display Parameters DMode KEY Default RegisterWorking Register Safe RegisterHand Held Communicator Registers Select Data Source 10.1Alarm and Error Messages 10.0ERROR Messages on the HHCPrintout or PC transfer of MSM400 programme data Display of Parameter Data 10.2Invalid Data Entry Instrument in Multidrop Mode Password not Open10.3Communication Errors Invalid Action not the Same InstrumentD0 D8 11.0Current Loop Checks and Trimming Current Output ** Set current Trim-maximum Trim-maximum12.0Unknown Instrument Current and USE ↑ & ↓ To Trim the Output13.3Use of multiple Smart Communicators D13.0 Smart Interfaces Compatibility D13.1 IntroductionAbcdef