Emerson MSM400 manual Appendix A3 Hart and Psion Operating Instructions, Hart Considerations

Page 38

APPENDIX A3 : HART and PSION Operating Instructions

1.0.HART CONSIDERATIONS

Special Considerations for HART

If the HART communications facility built into the control unit will be used at the time of installation or during its future working life, then it is essential that a resistive load of at least 250 Ohms is connected in the supply cable. This may be provided by other devices in the loop (Chart recorder, meter, etc.) or more usually by installing a standard 270 Ohm 0.25W resistor in series with control unit. In this way the master device will be able to signal to the control unit without the power supply short-circuiting the data.

In addition, excessive cable capacitance will attenuate the HART signalling and so the capacitance must

anyway be limited if HART communications is to be used. The RC time constant for the network must not exceed 65µs, e.g. if the network resistance is, say, 650Ω then the maximum network capacitance is 0.1µF.

HART transmitters are often given a Cn number where n is the multiple of 5000pF which the device presents to the network. In the case of MSM400 the value of n is 1 since its capacitance is below 5000pF.

Total loop resistance and capacitance

Additional equipment such as indicators or recorders may be inserted in the loop subject to the resistance and capacitance limits discussed above.

Cable trays

It is recommended that HART signal cables are not run alongside power cables.

1.1Multi-drop installations (MSM400 in HART digital mode)

Up to 15 transmitters may be connected in parallel with each other, and each must be set to a different HART address between 1 and 15. When HART transmitters are connected in multi-drop mode, each control unit draws a fixed current of 4mA.

Compatibility with other HART instruments.

Any HART instrument, regardless of the manufacturer, may be connected in parallel with another to create a multi-drop network. They may be combined with separately powered, current sourcing or sinking devices but care must be taken to ensure that the HART signal current passes through the 250W minimum impedance to establish communications. For full details of HART instrument availability, refer to the HART Communication Foundation publications or individual manufacturers' literature.

Handheld Communicators

A handheld communicator (HHC) may be connected across the network (downstream of the minimum 250 Ohm loop resistance) to programme or interrogate a HART control unit. Some HHC’s support only a subset of a transmitter’s functions, and will thus only access the control units Universal and Common Practice commands. However, the MSM400 is fully supported by the MOBREY-CK1 HHC and by the UNIVERSAL 275 HHC (provided the 275 is loaded with the transmitter’s Device

Description – contact Mobrey Measurement or the HART Communications Foundation for details).

IP258

38

Image 38
Contents Mobrey Contents Safety Precautions ENT Sensor Connection IVE Neutral Earth MainsDisplay Product Introduction MSM400 Slurry Monitoring System Product DescriptionSlurry Characteristics Ultrasonic Attenuation versus Suspended solidsSuspended Sensor Type MSM433 Mobrey Pipe Section SensorsSensor Type Numbering System Keypad Operation Control UnitMSM400 Displays and Keypad EMC SPECIFICATIONS--MSM400Hart Preliminary Checks Pipe Section InstallationSuspended Sensor Installation Sensor Cables Control UnitTerminal Label Function Relays Hart Connections and Jumper SettingsSensor Connections Current OutputMains Supply Safety PrecautionsInitial Power UP Main Menu Toggle RUN Calibration Setup Toggle RUN Calibration Setup MonitorToggle RUN Zero Setting Initial Zero Diagnostic ParametersEX-FACTORY System Features Calibration Methods Auto CAL Auto CAL Zero Setting Procedure Rechecking ZeroAutocal Span Setting Procedure Clear Liquor Press ENT To set 23.1dB 26.2dBSample Press ENT to set 33.6dB 44.2dB Auto CAL LAB ValuesSpan CALIBRATION/GRADIENT Methods Zero Setting ProcedureMaximum % Solids Calibration Method 1-SLURRY TypeAttenuation VALUE-METHOD Start on Stop on Stop if Do not start if Duty Mode Desludge ModeNo. of operation Set Default value Max value Hrs & mins INPUT↓ Output Start Time #1 hm 730 P254 Outputs Current Output Relay Operation←−−−−−−− Lower Display AlarmMiddle Display Display option parameter number DescriptionSystem Test Current Output SettingsEngineering Frequency SET Hart Smart Communications SensorsPar No Appendix A1Main Menu SUB Menu Parameter Description Logging Alarm ReportDiagnostics EngineeringMin Max Default Value Parameter DescriptionParameter Description Min Max Default Value MSM400 Monit From list 3.6/21mA/hold last reading Min Max Default Value Ex-Factory Manufacturer’s Code Appendix A3 Hart and Psion Operating Instructions Hart ConsiderationsCalibration adjustments at operating conditions Smart Communication with the Mobrey MSM400Further customisation using the Smart HHC Hand Held Communicator Assembly Instructions Handheld Communicator Mobrey CKFig DII. Loop diagram Fig D1 MOBREY-CK* HHC assembly How to connect the Smart Communicator Hand Held Communicator Operation Mobrey Find Save Diary Calc Time Notes World Alarm How to drive a Psion based Smart CommunicatorTAG Tank Help D7.0 Introduction and Function menuD7.1 Monitor/Display Parameters D D7.2 Program Parameters PWorking Register Default RegisterMode KEY Safe RegisterHand Held Communicator Registers Select Data Source Printout or PC transfer of MSM400 programme data 10.0ERROR Messages on the HHC10.1Alarm and Error Messages Display of Parameter Data10.2Invalid Data Entry 10.3Communication Errors Password not OpenInstrument in Multidrop Mode Invalid Action not the Same InstrumentD0 D8 Current Output ** Set current Trim-maximum Trim-maximum 11.0Current Loop Checks and TrimmingCurrent and USE ↑ & ↓ To Trim the Output 12.0Unknown InstrumentD13.0 Smart Interfaces Compatibility D13.1 Introduction 13.3Use of multiple Smart CommunicatorsAbcdef