Emerson MSM400 manual Main Menu Toggle RUN Calibration Setup, Toggle RUN Calibration Setup Monitor

Page 16

5.0PROGRAMMING

5.1The operation of the MSM400 is controlled by means of programmable parameters. These are stored in memory and may be set by the user to define variables such as calibration scale factors, set points, and modes of operation. The parameters are accessed using the keypad, by means of a menu system as shown below. (Parameters may also be edited remotely using the HART protocol. See Appendix N). For a full listing of the menu structure refer to Appendix A1.

5.2Navigation in the menu system

From the main display, pressing any key except ESC will enter the menu system. The top level menu contains the list of available menu items:

TOGGLE RUN

CALIBRATION

SETUP

MONITOR

To move up and down the list, use the UP and DOWN arrows until the required menu item is highlighted, then use the ENT or RIGHT arrow key to select it. The presence of additional menu items off the screen is indicated by up and down arrows on the right hand side of the display

The next level of the menu is then displayed and the required option can again be selected as above.

Continue until the required parameter is displayed and select it using the ENT key. (Note that menu groups are in upper case letters, parameters are in upper and lower case.)

The parameter may now be modified. Numeric values are edited one digit at a time, the LEFT and RIGHT arrows select each digit by highlighting them and the UP and DOWN arrows increment and decrement each digit. Some parameters e.g. “PV Units” are in the form of a list. These are edited in a similar way, selecting with the RIGHT arrow and using the UP and DOWN arrows to scroll through the list

When the displayed value is correct, press the ENT key to store it.

Scrolling

When a parameter is displayed but no digit is selected, the UP and DOWN arrow keys will scroll to the next parameter in numeric order. This provides an alternative method of accessing parameters without using the menu facility.

Example: Relay 1 set point programming.

To programme the relay, follow the simple steps shown below;

1.To alter any menu option the padlock icon in the top left of the display must be open. This is done using the TOGGLE RUN menu.

2.To access TOGGLE RUN from the normal display, press any key except ESC to display the main menu. The down arrow (↓) shown on the screen indicates that there are further options. (including MONITOR)

 

MAIN MENU

0

 

TOGGLE RUN

0

CALIBRATION

SETUP

IP258

16

Image 16
Contents Mobrey Contents Safety Precautions Display Sensor Connection IVE Neutral Earth MainsENT Product Introduction MSM400 Slurry Monitoring System Product DescriptionSlurry Characteristics Ultrasonic Attenuation versus Suspended solidsSuspended Sensor Type MSM433 Mobrey Pipe Section SensorsSensor Type Numbering System MSM400 Displays and Keypad Control UnitKeypad Operation Hart SPECIFICATIONS--MSM400EMC Suspended Sensor Installation Pipe Section InstallationPreliminary Checks Sensor Cables Control Unit Terminal Label Function Hart Connections and Jumper Settings Sensor ConnectionsRelays Current OutputInitial Power UP Safety PrecautionsMains Supply Main Menu Toggle RUN Calibration Setup Toggle RUN Calibration Setup MonitorToggle RUN EX-FACTORY System Features Diagnostic ParametersZero Setting Initial Zero Calibration Methods Auto CAL Auto CAL Zero Setting Procedure Rechecking ZeroAutocal Span Setting Procedure Clear Liquor Press ENT To set 23.1dB 26.2dBSample Press ENT to set 33.6dB 44.2dB Auto CAL LAB ValuesZero Setting Procedure Maximum % SolidsSpan CALIBRATION/GRADIENT Methods Calibration Method 1-SLURRY TypeAttenuation VALUE-METHOD No. of operation Set Default value Max value Hrs & mins Duty Mode Desludge ModeStart on Stop on Stop if Do not start if INPUT↓ Output Start Time #1 hm 730 P254 Outputs Current Output Relay OperationAlarm Middle Display←−−−−−−− Lower Display Display option parameter number DescriptionEngineering Frequency SET SettingsSystem Test Current Output Hart Smart Communications SensorsMain Menu SUB Menu Parameter Description Appendix A1Par No Alarm Report DiagnosticsLogging EngineeringMin Max Default Value Parameter DescriptionParameter Description Min Max Default Value MSM400 MonitFrom list 3.6/21mA/hold last reading Min Max Default Value Ex-Factory Manufacturer’s Code Appendix A3 Hart and Psion Operating Instructions Hart ConsiderationsCalibration adjustments at operating conditions Smart Communication with the Mobrey MSM400Further customisation using the Smart HHC Hand Held Communicator Assembly Instructions Handheld Communicator Mobrey CKFig DII. Loop diagram Fig D1 MOBREY-CK* HHC assembly How to connect the Smart Communicator Hand Held Communicator Operation Mobrey Find Save Diary Calc Time Notes World Alarm How to drive a Psion based Smart CommunicatorTAG Tank Help D7.0 Introduction and Function menuD7.1 Monitor/Display Parameters D D7.2 Program Parameters PDefault Register Mode KEYWorking Register Safe RegisterHand Held Communicator Registers Select Data Source 10.0ERROR Messages on the HHC 10.1Alarm and Error MessagesPrintout or PC transfer of MSM400 programme data Display of Parameter Data10.2Invalid Data Entry Password not Open Instrument in Multidrop Mode10.3Communication Errors Invalid Action not the Same InstrumentD0 D8 Current Output ** Set current Trim-maximum Trim-maximum 11.0Current Loop Checks and TrimmingCurrent and USE ↑ & ↓ To Trim the Output 12.0Unknown InstrumentD13.0 Smart Interfaces Compatibility D13.1 Introduction 13.3Use of multiple Smart CommunicatorsAbcdef