Emerson MSM400 manual Terminal Label Function

Page 13

4.6ELECTRICAL CONNECTIONS

All field wiring connections are accessible by removing the lower lid, which is secured by two screws. Note that it is the responsibility of the installer to observe all local regulations and approval requirements, and to use cable to suit the environmental requirements of the particular application. Obtain and check any hazardous area work permits required before applying power to the MSM400.

The diagram below shows the layout of external connection terminals: all terminal blocks are suitable for wires 0.5mm2 to 2.5mm2 (26-12 AWG). Insulation should be stripped back 7mm.

Ensure wiring is suitable for the load current and the insulation is suitable for the voltage, temperature and environment of the installation.

Note that in intrinsically safe systems, apparatus connected to the MSM400 must not be supplied from a voltage greater than 250V rms or 250V DC.

FUSE 200mA

K7941

Figure 9: Connection Terminal Layout

Note that not all of the labelled terminals are functional in this version of the MSM400. The functions available are listed below :

CONNECTION DESCRIPTIONS :

Terminal

Label

Function

 

 

1

RX

A

Sensor Cable

 

 

2

RX

B

Sensor Cable

 

 

3

RX

SCN

Screen for 1+2

 

 

4

TX

SCN

Screen for 5+6

 

 

5

TX

A

Sensor Cable

 

 

6

TX

B

Sensor Cable

 

 

7

TRIGGER 0V

Ground ref for Trigger inputs

 

8

TRIGGER D1

Digital input No 1

 

 

10

TRIGGER 5V

5 V output

 

 

16

I out Io

Current output (4-20mA)

 

17

I out 0V

Current output zero ref terminal

 

18

I out 24V

Current output 24 V DC loop power : refer to Fig. 10

19-21

RELAY 1

NC-C-NO Relay output

terminals for Relay 1

 

22-24

RELAY 2

NC-C-NO Relay output

terminals for Relay 2

 

25

DC out 24V

Output of 24 VDC for powering external devices.

26

DC out 0V

Ref for DC output

 

 

27

DC in 24V

Positive supply at 24VDC to the MSM400--ie DC power input

28

DC in 0V

Ref terminal for DC supply input

 

29

Mains L

AC power input 115/230V, Live terminal

NB: SELECT 115 or 230V

30

Mains N

AC power input 115/230V, Neural terminal

ON SWITCH ABOVE

31

Mains E

Protective Earth (PE)

 

THESE TERMINALS

NOTE 1 The sensors are symmetrical, so either of the two cable pairs can be chosen as "Tx" or "Rx

IP258

13

Image 13
Contents Mobrey Contents Safety Precautions Display Sensor Connection IVE Neutral Earth MainsENT Product Description Product Introduction MSM400 Slurry Monitoring SystemUltrasonic Attenuation versus Suspended solids Slurry CharacteristicsMobrey Pipe Section Sensors Suspended Sensor Type MSM433Sensor Type Numbering System MSM400 Displays and Keypad Control UnitKeypad Operation Hart SPECIFICATIONS--MSM400EMC Suspended Sensor Installation Pipe Section InstallationPreliminary Checks Control Unit Sensor CablesTerminal Label Function Sensor Connections Hart Connections and Jumper SettingsRelays Current OutputInitial Power UP Safety PrecautionsMains Supply Toggle RUN Calibration Setup Monitor Main Menu Toggle RUN Calibration SetupToggle RUN EX-FACTORY System Features Diagnostic ParametersZero Setting Initial Zero Rechecking Zero Calibration Methods Auto CAL Auto CAL Zero Setting ProcedureClear Liquor Press ENT To set 23.1dB 26.2dB Autocal Span Setting ProcedureAuto CAL LAB Values Sample Press ENT to set 33.6dB 44.2dBMaximum % Solids Zero Setting ProcedureSpan CALIBRATION/GRADIENT Methods Calibration Method 1-SLURRY TypeAttenuation VALUE-METHOD No. of operation Set Default value Max value Hrs & mins Duty Mode Desludge ModeStart on Stop on Stop if Do not start if INPUT↓ Output Start Time #1 hm 730 P254 Relay Operation Outputs Current OutputMiddle Display Alarm←−−−−−−− Lower Display Display option parameter number DescriptionEngineering Frequency SET SettingsSystem Test Current Output Sensors Hart Smart CommunicationsMain Menu SUB Menu Parameter Description Appendix A1Par No Diagnostics Alarm ReportLogging EngineeringParameter Description Min Max Default ValueMSM400 Monit Parameter Description Min Max Default ValueFrom list 3.6/21mA/hold last reading Min Max Default Value Ex-Factory Manufacturer’s Code Hart Considerations Appendix A3 Hart and Psion Operating InstructionsSmart Communication with the Mobrey MSM400 Calibration adjustments at operating conditionsFurther customisation using the Smart HHC Handheld Communicator Mobrey CK Hand Held Communicator Assembly InstructionsFig DII. Loop diagram Fig D1 MOBREY-CK* HHC assembly How to connect the Smart Communicator Hand Held Communicator Operation How to drive a Psion based Smart Communicator Mobrey Find Save Diary Calc Time Notes World AlarmTAG Tank D7.0 Introduction and Function menu HelpD7.2 Program Parameters P D7.1 Monitor/Display Parameters DMode KEY Default RegisterWorking Register Safe RegisterHand Held Communicator Registers Select Data Source 10.1Alarm and Error Messages 10.0ERROR Messages on the HHCPrintout or PC transfer of MSM400 programme data Display of Parameter Data10.2Invalid Data Entry Instrument in Multidrop Mode Password not Open10.3Communication Errors Invalid Action not the Same InstrumentD0 D8 11.0Current Loop Checks and Trimming Current Output ** Set current Trim-maximum Trim-maximum12.0Unknown Instrument Current and USE ↑ & ↓ To Trim the Output13.3Use of multiple Smart Communicators D13.0 Smart Interfaces Compatibility D13.1 IntroductionAbcdef