Appendix D

D.HANDHELD COMMUNICATOR – MOBREY – CK*

D.1.0. Hand Held Communicator – Assembly Instructions

The MOBREY-CK* SMART Hand Held Communicator is supplied as a kit of items (Figure DI) which are assembled as follows:

D.1.1 Remove the lower sliding cover (1) of the Psion organiser (2) completely to expose the battery compartment lid

(3) at the base of the keypad, and the two slots for Datapaks behind the right hand side of the keypad.

D.1.2 Remove the lower of the two blank Datapak mouldings and insert the preprogrammed Mobrey SMART Datapak (4), pressing the unit home. This lower slot is the “C” slot in Psion Organiser memory.

D.1.3 Remove the battery compartment lid (3) and insert the 9V battery (5), positive terminal first. Replace the battery compartment lid (3) and the lower sliding cover (1) over the base of the Psion Organiser. Leave the keyboard exposed.

D.1.4 At the top of the Psion Organiser above the LCD, slide the cover across to the right to expose the connector. Insert the MOBREY SMART interface unit (6) in this slot.

D.1.5 The lead used to connect the MSM400 cabling is plugged into the MOBREY SMART interface unit. On the MOBREY-CK1 and MOBREY-CK3 this is via a 3.5mm jack plug. On the -CK2 a multi pin plug is used. The latter also has the hook-on connectors built into the leads instead of push on crocodile clips.

D.1.6 The MOBREY SMART Interface Unit has another socket at the top left hand side for connection of a standard Psion external power unit as an alternative to battery operation.

D.2.0. Notes

D.2.1 Although it is possible to insert two Datapaks into the HHC, this is not recommended as a conflict between them can occur.

D.2.2 The MOBREY-CK* Datapaks enable communication with both MSP100 ultrasonic level transmitters and MSM400 displacement level transmitters, and also gives generic support for all other HART transmitters.

D.2.3 When not in use, remove the Mobrey SMART Interface unit from the HHC to prolong battery life.

D.3.0. Requirements for loop powered SMART Operation (Refer to Fig. DII)

D.3.1 The MSM400 control unit requires a DC supply voltage of 2.5 volts at its terminals for satisfactory operation (V3).

D.3.2 Resistance between any two SMART Interface connection points must exceed 250 ohms. (R1).

D.3.3 For the minimum DC supply voltage (V1) to be calculated, the voltage drops in the loop at 20mA must be assessed. The absolute minimum value of V1 will therefore be 7.5 volts, since 5 volts is required for the voltage drop across R1 at 20mA. (See Note 2 below).

D.3.4 If R1 is 250 ohms or more the SMART communicator can be connected between B1-B2, or C1-C2, or D1-D2 or E1-E2. It is also allowable to connect across the SMART Load resistor R1, on B1-A1, or across any resistance in the circuit that exceeds 250 ohms.

D.3.5 The current loop load resistance R2 can be considered to be part of the 250 ohms needed as the SMART Load resistor. In this case R1 + R2 must exceed 250 ohms, and the communicator can be connected between C1-C2, D1-D2, E1-E2, or C1-A1.

IP258

41

Image 41
Contents Mobrey Contents Safety Precautions ENT Sensor Connection IVE Neutral Earth MainsDisplay Product Description Product Introduction MSM400 Slurry Monitoring SystemUltrasonic Attenuation versus Suspended solids Slurry CharacteristicsMobrey Pipe Section Sensors Suspended Sensor Type MSM433Sensor Type Numbering System Keypad Operation Control UnitMSM400 Displays and Keypad EMC SPECIFICATIONS--MSM400Hart Preliminary Checks Pipe Section InstallationSuspended Sensor Installation Control Unit Sensor CablesTerminal Label Function Sensor Connections Hart Connections and Jumper SettingsRelays Current OutputMains Supply Safety PrecautionsInitial Power UP Toggle RUN Calibration Setup Monitor Main Menu Toggle RUN Calibration SetupToggle RUN Zero Setting Initial Zero Diagnostic ParametersEX-FACTORY System Features Rechecking Zero Calibration Methods Auto CAL Auto CAL Zero Setting ProcedureClear Liquor Press ENT To set 23.1dB 26.2dB Autocal Span Setting ProcedureAuto CAL LAB Values Sample Press ENT to set 33.6dB 44.2dBMaximum % Solids Zero Setting ProcedureSpan CALIBRATION/GRADIENT Methods Calibration Method 1-SLURRY TypeAttenuation VALUE-METHOD Start on Stop on Stop if Do not start if Duty Mode Desludge ModeNo. of operation Set Default value Max value Hrs & mins INPUT↓ Output Start Time #1 hm 730 P254 Relay Operation Outputs Current OutputMiddle Display Alarm←−−−−−−− Lower Display Display option parameter number DescriptionSystem Test Current Output SettingsEngineering Frequency SET Sensors Hart Smart CommunicationsPar No Appendix A1Main Menu SUB Menu Parameter Description Diagnostics Alarm ReportLogging EngineeringParameter Description Min Max Default ValueMSM400 Monit Parameter Description Min Max Default ValueFrom list 3.6/21mA/hold last reading Min Max Default Value Ex-Factory Manufacturer’s Code Hart Considerations Appendix A3 Hart and Psion Operating InstructionsSmart Communication with the Mobrey MSM400 Calibration adjustments at operating conditionsFurther customisation using the Smart HHC Handheld Communicator Mobrey CK Hand Held Communicator Assembly InstructionsFig DII. Loop diagram Fig D1 MOBREY-CK* HHC assembly How to connect the Smart Communicator Hand Held Communicator Operation How to drive a Psion based Smart Communicator Mobrey Find Save Diary Calc Time Notes World AlarmTAG Tank D7.0 Introduction and Function menu HelpD7.2 Program Parameters P D7.1 Monitor/Display Parameters DMode KEY Default RegisterWorking Register Safe RegisterHand Held Communicator Registers Select Data Source 10.1Alarm and Error Messages 10.0ERROR Messages on the HHCPrintout or PC transfer of MSM400 programme data Display of Parameter Data10.2Invalid Data Entry Instrument in Multidrop Mode Password not Open10.3Communication Errors Invalid Action not the Same InstrumentD0 D8 11.0Current Loop Checks and Trimming Current Output ** Set current Trim-maximum Trim-maximum12.0Unknown Instrument Current and USE ↑ & ↓ To Trim the Output13.3Use of multiple Smart Communicators D13.0 Smart Interfaces Compatibility D13.1 IntroductionAbcdef