AEG Thyro-P 2.3 CONTROL TYPES, 2.3.1 CONTROLLED VALUE

Page 18

18

The prerequisite for a set point to infl uence the total set point value is that it must be enabled by

the set point Enable Register. Set point 1 and 2 can be linked using the following functions. The

result of this link is called set point (1,2).

Set point link

ADD 

    Set point (1,2) = Set point 1 + Set point 2

IADD

    Set point (1,2) = Set point 1 - Set point 2

_Pro

 

Set point (1,2) = Set point 1 * Set point 2 [%]

                                                                    100%

_IPro

  Set point (1,2) = Set point 1 * (1 -  Set point 2 [%] )

                                                                            100%

VALUE RANGE OF SET POINT (1,2)

For the link result of set point (1,2) the following value range applies:

0 

울

  Set point (1,2) 

울

 Set point max (U

max

, I

max

, P

max

).

SET POINT ENABLE REGISTER

The set point Enable Register (AD_P_SW_ENABLE, adr. 94) enables the 4 set points to be shut off

or enabled independently. Only enabled set point inputs are part of the effective total set point

value.

The shut off or inactive set points are shown by the LBA and can thus, if necessary, be checked

before connecting.

The set point Enable Register can be changed from all service units (Bus, Thyro-Tool Familiy, LBA).

Example:

8    4    2    1 

VALUE  ABBR. 

EXPLANATION

1    1    1    1 

15 

STD 

Standard (all ON)

1    0    0    0 

8 

LOC 

Motor poti-set point 4 (LOCAL)

0    1    0    0 

4 

REMOTE 

Bus set point 3

0    0    1    1 

3 

ANA  

Analog-set points 1,2

0    0    0    0 

0 

 

All set points inactive

2.3 CONTROL TYPES

Thyro-P has fi ve control types effective as underlying controls. Mains voltage variations and load

changes are directly and therefore quickly adjusted by bypassing of the slow temperature control

system.

Before commissioning of the Power Controller and selection of a control type, you should be

familiar with the operating procedure respectively the effect for application.

2.3.1 CONTROLLED VALUE

The controlled value effective on the load is proportionate to the total set point, depending on the

control type:

CONTROL TYPE 

CONTROL VALUE (PROPORTIONATE TO THE TOTAL SET POINT)

P control 

output (active) power, P

U control 

output voltage, U

rms

U

2

 control 

output voltage, U

2

rms

I control 

output current, I

rms

I

2

 control 

output current, I

2

rms

LIMITING OF SIGNALS

Independent of the control type set, additionally minimum and maximum limiting values may be

set. For this purpose, also refer to Fig. 1 control characteristic.

The maximum limiting values determine the maximum modulation of the load.

Image 18