AEG Thyro-P - page 85

Page 85

85

IN DETAIL:

CONDITIONS FOR USE OF THE DEVICE

Built-in unit

 

EN 50 178

 

General requirements

 

EN 60146-1-1

 

Design, vertical installation

 

 

 

Operating conditions

 

EN 60 146-1-1; K. 2.5

 

Operating location, industry sector

 

CISPR 6

 

Temperature performance

 

EN 60 146-1-1; K 2.2

 

Storage temperature

 

-25°C - +55°C

 

Transport temperature

 

-25°C - +70°C

 

Operating temperature

 

-10°C - +35°C for external cooling ( 280A)

 

 

-10°C - +45°C for self air cooling

 

 

 

-10°C - +55°C for reduced type current -2%/°C

with UL applications

 

up to 40°C

 

Load class

1

EN 60 146-1-1 T.2

 

Humidity class

B

EN 50 178 Tab. 7

 

Overvoltage voltage category ÜIII

 

EN 50 178 Tab. 3

 

Degree of pollution

2

EN 50 178 Tab. 2

 

Air pressure

 

900mbar

≤ 1000m above zero level

Safe isolation

 

 

 

up to 500V mains voltage:

 

EN 50 178 chap. 3

 

Air and creeping distances according

casing/mains potential

≥ 5.3mm

to DIN EN 50178

 

 

 

 

 

casing/control potential

≥ 5.3mm

 

 

mains voltage/control

≥ 7.2mm and 10mm

 

 

potential

in the power section

 

 

interface/control potential

≥ 2.5mm

 

 

mains voltage/interface

≥ 7.2mm

 

 

mains voltage among themselves

≥ 5.5mm

Test voltage

 

EN 50 178 Tab 18

 

Tests according to

 

EN 60 146-1-1 4.

 

EMV noise emission

 

EN 61000-6-4

 

Moise suppression (control device)

 

 

 

 

class A

CISPR 11

 

EMV noise resistance

 

EN 61000-6-2

 

Compatibility level

class 3

EN 61000-2-4

 

ESD

≥ 8 kV

EN 61000-4-2

 

Electromagnetic fields

≥ 10V/m

EN 61000-4-3

 

Burst on mains lines

≥ 2kV

EN 61000-4-4

 

Burst on control lines

≥ 0.5kV

 

 

Surge on mains lines

≥ 2kV

EN 61000-4-5

 

Surge on control lines

≥ 0.5kV

 

 

Line-conducted

 

EN 61000-4-6

 

Further norms are observed, for instance voltage dips according to 61000-4-11 are ignored by the control device, or registered by triggering of monitoring. Generally, an automated start is made after the mains returns within tolerances.

Therefore, the conditions of the norm EN 61326 (controller standard) are also observed, even though this norm by its structure is not applicable to power electronics > 10 respectively > 25A.