AEG Thyro-P 2.4 INDICATIONS 2.4.1 LED INDICATIONS, 2.4.2 RELAY INDICATIONS K1-K2-K3

Page 19

19

The minimum limiting values should ensure minimum modulation via the control angle (for instance minimum heating of the load).

CONTROLLER RESPONSE

If the load resistance changes, for instance due to temperature effect, ageing or load fault, then the values effective on the load change as follows:

UNDERLYING

 

 

LOAD RESISTANCE

 

LOAD RESISTANCE

 

EFFECTIVE*

 

 

 

 

 

DECREASES

 

INCREASES

 

LIMITATIONS

CONTROL

LIMIT

P

ULOAD

ILOAD

P

ULOAD

ILOAD

 

 

 

 

 

U

Urms max

larger

=

larger

smaller

=

smaller

Irms max

Pmax

U2 (UxU)

U

rms max

larger

=

larger

smaller

=

smaller

I

rms max

P

max

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I

Irms max

smaller

smaller

=

larger

larger

=

Urms max

Pmax

I2 (IxI)

I

rms max

smaller

smaller

=

larger

larger

=

U

rms max

P

max

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P

Pmax

=

smaller

larger

=

larger

smaller

Urms max

Irms max

without control

 

larger

=

larger

smaller

=

smaller

Urms max

Irms max

 

 

 

 

 

 

 

 

 

 

Pmax

 

 

*If one of the limits is exceeded, then the signaling relay K2 and the LED „limit“ react (default values of parameter settings).

General modulation limit

Ts=Ts max

 

=max

 

 

TAB. 1

BEHAVIOUR IN CASE OF LOAD CHANGE

2.4 INDICATIONS

2.4.1 LED INDICATIONS

The LEDs on the front side signal the following states:

• ON

green: operating indication, power supply controller board

 

red: RESET active

• CONTROL

modulation percentage indication, flashing*

• LIMIT

limitation is active, relay K2 switches*

•PULSE LOCK Controller Lock active, but load control is continued at pulse limits (default value = 0)*

• FAULT

fault present*

• OVERHEAT

overheating of power section

 

(in case of ..HF types, check ventilator)*

* Default setting

Activation of the integrated semiconductor fuse may be signalled using the fault indicating relay K1 rest current, contactor, otherwise separate supply of the control device required). In case of Power Controllers from model current 495A, additional signalling is performed via an indicator at the semiconductor fuse.

2.4.2 RELAY INDICATIONS K1-K2-K3

The Thyro-P Power Controller is fitted with three relays. Each of these relays has a change over contact in principle be allocated a value in the event register. The following table shows the contac- tor allocation of the relays at the corresponding terminal strips. Presets of parameters by the works (default values) may be found in chapter 3.4.

Image 19