The minimum limiting values should ensure minimum modulation via the control angle (for instance minimum heating of the load).
CONTROLLER RESPONSE
If the load resistance changes, for instance due to temperature effect, ageing or load fault, then the values effective on the load change as follows:
UNDERLYING |
|
| LOAD RESISTANCE |
| LOAD RESISTANCE |
| EFFECTIVE* |
| ||||||
|
|
|
| DECREASES |
| INCREASES |
| LIMITATIONS | ||||||
CONTROL | LIMIT | P | ULOAD | ILOAD | P | ULOAD | ILOAD |
|
|
|
|
| ||
U | Urms max | larger | = | larger | smaller | = | smaller | Irms max | Pmax | |||||
U2 (UxU) | U | rms max | larger | = | larger | smaller | = | smaller | I | rms max | P | max | ||
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| |||||
I | Irms max | smaller | smaller | = | larger | larger | = | Urms max | Pmax | |||||
I2 (IxI) | I | rms max | smaller | smaller | = | larger | larger | = | U | rms max | P | max | ||
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| |||||
P | Pmax | = | smaller | larger | = | larger | smaller | Urms max | Irms max | |||||
without control |
| larger | = | larger | smaller | = | smaller | Urms max | Irms max | |||||
|
|
|
|
|
|
|
|
|
| Pmax |
|
| ||
*If one of the limits is exceeded, then the signaling relay K2 and the LED „limit“ react (default values of parameter settings).
General modulation limit | Ts=Ts max |
| =max |
|
|
TAB. 1 | BEHAVIOUR IN CASE OF LOAD CHANGE |
2.4 INDICATIONS
2.4.1 LED INDICATIONS
The LEDs on the front side signal the following states:
• ON | green: operating indication, power supply controller board |
| red: RESET active |
• CONTROL | modulation percentage indication, flashing* |
• LIMIT | limitation is active, relay K2 switches* |
•PULSE LOCK Controller Lock active, but load control is continued at pulse limits (default value = 0)*
• FAULT | fault present* |
• OVERHEAT | overheating of power section |
| (in case of ..HF types, check ventilator)* |
* Default setting
Activation of the integrated semiconductor fuse may be signalled using the fault indicating relay K1 rest current, contactor, otherwise separate supply of the control device required). In case of Power Controllers from model current 495A, additional signalling is performed via an indicator at the semiconductor fuse.
2.4.2 RELAY INDICATIONS
The