AEG Thyro-P 3.1.3 LBA SUBMENUS

Page 27

Sprache/language Main menu

Open/save data

Set points/curve

Parameters

 

27

MAIN MENU

FUNCTION

Language

selection operating language

Load/store data

load and store data

Set points/characteristics

set point processing

Parameter

display and modification of parameters

Operation display

select operation display

Last function

energy and operating hours

TAB. 6 LBA MAIN MENU

 

3.1.3 LBA SUBMENUS

The first six lines of the above main menu contain the names of the sub-menus. These are shown below, with explanations, in the sequence they are contained in the menu.

= Main menu (appears after plugging in the LBA)

 

Submenu

Menu

 

next submenu

Default

User

Remarks

 

 

 

 

 

 

 

 

 

 

Value

Value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sprache/language

 

 

 

 

 

 

 

Deutsch

 

 

 

 

x

 

 

 

 

English

 

 

 

 

 

 

 

 

 

Francais

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Open/save data

 

 

 

Loading, storing,

copying of parameter sets

 

 

Thyro-P -> LBA

1

 

 

 

 

 

 

LBA

-> Thyro-P

2

 

 

Parameter from LBA-EEPROM to Thyro-P RAM

 

 

Store in LBA

 

 

 

Parameter from LBA-RAM to LBA-EEPROM

 

 

 

 

 

 

 

Save Thyro-P

 

 

 

Parameter from Thyro-P RAM to Thyro-P EEPROM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Open data again

 

 

 

 

 

 

 

Thyro-P

->

LBA

 

 

 

Store parameters from Thyro-P in LBA

 

 

waiting

time

 

 

 

Observe waiting time! OK key during charging releases

 

 

 

 

 

 

 

 

the parameter lock

 

 

ASIC-SW

 

 

 

 

 

Shows production date of controller software

 

 

Code LBA

 

 

 

 

 

Shows version of

LBA software

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

Save data again

 

 

 

 

 

 

 

LBA

-> Thyro-P

 

 

 

Store parameters from LBA in Thyro-P

 

 

waiting

time

 

 

 

Observe waiting time!

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set points/curve

 

 

 

Remark: Display is refreshed after max. 10 sec.

 

 

motor pot.

 

 

 

0

Display and modification set point 4

 

 

Term. (10)

 

 

 

 

Display set point 1

 

 

Term. (11)

 

 

 

 

Display set point 2

 

 

Master(bus)

 

 

 

 

Display set point 3 (bus)

 

 

Act.pwr.tot:xx,xxmA

 

 

 

Display total set

point

 

 

Absolute set points

 

 

 

During active circuit set point is displayed

 

 

 

 

 

 

 

 

in a submenue depending on control mode

 

 

STD,LOC,REMOTE,ANA

 

 

STD

Choice of set point inputs

 

 

ADD,IADD, PRO,IPRO

 

 

ADD

SW1+SW2, SW1-SW2, SW1*SW2%/100%, SW1*(1-SW2%/100%)

 

 

5V,10V,mA term(10)

 

 

mA

Selection signal type for set point 1*

 

 

5V,10V,mA term(11)

 

 

5V

Selection signal type for set point 2*

 

 

Ctrl.start1 4.00mA

 

 

0.3mA

Control start set point SW1

 

 

Ctrl.end1

20.00mA

 

 

20.0mA

Control start set point SW1

 

 

Ctrl.start2 20.00V

 

 

0.07V

Control start set point SW2

 

 

Ctrl.end2

10.00V

 

 

5.0V

Control end set point SW2

 

 

 

 

 

 

 

 

* refer to ”ATTENTION” on page 16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adress

 

 

 

 

 

 

 

 

 

Bus+LL-compound xxx

 

 

100

xxx for fibre optic 001 - 998

 

 

 

 

 

 

 

 

in case of Profibus DP 001 - 125

 

 

 

 

 

 

 

 

000 and 999 have specific functions

 

 

 

 

 

 

 

 

 

 

Image 27