4.13 SYNCHRONIZATION
By standard, each power section is fi tted with a transformer for an input voltage of up to 690V.
After fi ltering, the synchronization signal for control of the thyristors is generated from the secondary
voltage. The connections are wired by the works. This includes the following terminals:
TERMINAL STRIP X7
X7.1
X7.2
NAME
12
11
current transformer phase L1
14
13
sync phase L1
16
15
load voltage phase L1
22
21
current tranformer phase L2
24
23
sync phase L2
26
25
load voltage phase L2
32
31
current tranformer phase L3
34
33
sync phase L3
36
35
load voltage phase L3
TAB. 21 TERMINAL STRIP X7
For the synchronization the following jumpers are necessary on the componentry of the control
device.
THYRO-P
SHORT CIRCUIT JUMPER
1P
X507
X508
2P
X507
-
3P
-
-