process the controller requires an ASM control device. An additional burden resistor is used for all controllers. Schematic wiring of Power Controllers for the ASM process can be seen in the following illustration:
Power |
|
Controller 1 | |
D | D |
A | A |
ASM input | |
Iact. val.2 | |
X5.2.16 | X5.2.33 |
Uburden
Power |
|
Controller 2 | |
D | D |
A | A |
ASM input | |
Iact. val.2 | |
twisted/shielded | |
X5.1.13
total burden | Uburden = ( I1 +...+ In ) x Rburden | |
Uburden = 0 | ||
| ||
FIG. 20 ASM WIRING |
|
When using the ASM option, the analog output 2 (X5.2.33 against ground X5.1.13) becomes an output proportionate to the current during the
Rburden [k] = 10V / (n x 20mA) | n = number of Power Controller |
The burden voltage is measured at the ASM input. The Power Controller searches within the clock control the place with the lowest mains load.
Due to this automated, independent procedure, the process chain is ensured through the tempe- rature control circuit and the Power Controller without effects; negative effects like flicker and sub- harmonics of the mains frequency are balanced out during a current dynamic process. In this case,