AEG Thyro-P manual ADADADAD

Page 57

57

process the controller requires an ASM control device. An additional burden resistor is used for all controllers. Schematic wiring of Power Controllers for the ASM process can be seen in the following illustration:

Power

 

Controller 1

D

D

A

A

ASM input

0-20mA

Iact. val.2

X5.2.16

X5.2.33

Uburden

Power

 

Controller 2

D

D

A

A

ASM input

0-20mA

Iact. val.2

twisted/shielded

X5.1.13

total burden

Uburden = ( I1 +...+ In ) x Rburden

Uburden = 0 -10 volts

 

FIG. 20 ASM WIRING

 

When using the ASM option, the analog output 2 (X5.2.33 against ground X5.1.13) becomes an output proportionate to the current during the on-period TS. All Power Controllers connected to synchronization work on the same external burden. The burden resistor is calculated approximately as

Rburden [k] = 10V / (n x 20mA)

n = number of Power Controller

The burden voltage is measured at the ASM input. The Power Controller searches within the clock control the place with the lowest mains load.

Due to this automated, independent procedure, the process chain is ensured through the tempe- rature control circuit and the Power Controller without effects; negative effects like flicker and sub- harmonics of the mains frequency are balanced out during a current dynamic process. In this case, unfavorableshort-term overlapping may occur, for instance after set point jumps or voltage swing. The application document ASM-procedure gives further information on this.

Image 57