AEG Thyro-P - page 53

Page 53

53

X21

ASSIGNMENT

1  

PE (potential earthing)

2  

ground M1

3  

input 0/M1

4  

input 1/M1

5  

ground M24  

/ 24V supply for the Profi bus card

6  

ground M2

7  

input 2/M2

8  

input 3/M2  

/ special function = Motorpoti enable

9  

+24V  

 

/ 24V supply for the Profi bus card

 

* Loading: I

X5.1.20

 + I

X5.2.20

 + I

X21.9

 

≤

 max. 80mA

TAB. 25  PIN ASSIGNMENT X21

The inputs 0 and 1 refer to ground M1, the inputs 2 and 3 refer to ground M2. To connect simple

transmitters like limit switches, etc., a 24V power supply is also available. The input IN3 (PIN 8) is

taken up by a special function.

Therefore, connection could for instance be as follows:

FIG. 17  SPECIAL FUNCTION MOTORPOTI

local: Switch closed

remote: Switch open

Image 53