67
10. SPECIFICATIONS
TYPE VOLTAGE | ...P400... |
| 230 volts | to | 400 volts +10% | ||
| ...P500... |
| 230 volts | to | 500 volts +10% | ||
| ...P690... |
| 500 volts | to | 690 volts +10% | ||
|
|
|
|
|
| ||
MAINS FREQUENCY | all models |
| 45Hz to 65Hz |
|
| ||
LOAD DESCRIPTION | ohmic load (minimum 100W) |
|
| ||||
| ohmic load Rhot/Rcold ratio up to 20 (MOSI operation) | ||||||
| transformer load |
|
| ||||
TRANSFORMER | The induction of the load side transformer should not exceed | ||||||
| 1.45T in case of mains overvoltage when using | ||||||
| |||||||
| approx. 1.3T. |
|
|
| |||
OPERATING MODES | TAKT = full oscillation clock principle = default setting for the | ||||||
|
|
| models 1P, 2P and 3P |
|
| ||
| VAR = | ||||||
| SSSD = |
| |||||
|
|
| „VAR“ und „TAKT“, for the models 1P, 2P and 3P, | ||||
|
|
| i.e. reduced mains surge load |
| |||
SET POINT INPUTS | The Power Controller | ||||||
| The set point inputs are indirectly connected to the mains | ||||||
| (SELV, PELV). |
|
|
| |||
| Set points 1, 2: external set point input |
| |||||
| signal ranges: |
|
|
| |||
| 0(4) | - | 20 | mA | Ri about 250 max. 24mA* | ||
| 0 | - | 5 | V | Ri about 8,8k max. 12V |
| |
| 0 | - | 10 | V | Ri about 5k | max. 12V |
|
| * refer to ”ATTENTION” on page 16 |
| |||||
| Set point 3: connection for fibre optic (LL) from the wuper- | ||||||
| ordinate PC or automation system |
|
| ||||
| Set point 4: set point assignment via RS 232 (for instance LBA) | ||||||
| The four set points are added internally and the total of the | ||||||
| set points, for instance for power control, is proportionate to | ||||||
| output power. For set point 2, there are different valuation | ||||||
| options: it may be added to set point 1 or subtracted from set | ||||||
| point 1. |
|
|
|
|
| |
|
| ||||||
ANALOG OUTPUTS | 3 outputs: signal level | ||||||
| set differently. The maximum burden voltage is 10V | ||||||
CONTROL CHARACTERISTIC | The control characteristic is established by the maximum value | ||||||
| of the dimensions to be controlled and the key values of the | ||||||
| set point. Using these key values, the linear control characte- | ||||||
| ristic may be set at will. |
|
| ||||
| Every controller (for instance temperature controller), whose | ||||||
| output signal is in the range of | ||||||
| easily adapted to the Power Controller. |
| |||||