| 43 |
TERMINAL STRIP X5 IN THE CONTROL DEVICE |
| ||
X5.1 | FUNCTION | X5.2 | FUNCTION |
5 | +5V | 5 | +5V |
13 | ground 5V | 10 | set point 1 |
13 | ground 5V | 11 | set point 2 |
13 | ground 5V | 32 | analog output 1 |
13 | ground 5V | 33 | analog output 2 |
13 | ground 5V | 34 | analog output 3 |
13 | ground 5V | 16 | ASM input |
21 | 17 | GSE connection | |
14 | ground 24V | 12 | RESET |
14 | ground 24V | 15 | controller lock |
14 | ground 24V | 18 | SYT9 connection |
14 | ground 24V | 19 | QUIT |
20 | +24V* | 20 | +24V* |
* Loading: IX5.1.20 + IX5.2.20 + IX21.9 max. 80mA TAB. 19 TERMINAL STRIP X5
Terminal strip X6 in the control device
At the terminal strip X6, wiring between the control device A70 and the control cards A1, A3 and
A5 of the power section is performed by the works. Allocation of the terminal strip is as follows:
X6Name
11thyristor L1 neg.
12+5V
13thyristor L1 pos.
21thyristor L2 neg.
22+5V
23thyristor L2 pos.
31thyristor L3 neg.
32+5V
33thyristor L3 pos.
41input temperature sensor
42ground temperature sensor
TAB. 20 TERMINAL STRIP X6
Each thyristor is controlled by 20mA current supply switching to ground.
The ventilator monitor is connected to the terminals X6.41 and X6.42 in separately ventilated devices (..HF). The temperature of the power section is monitored using a PT 1000 temperature sensor. In case of overheating of the power section, for instance caused by outage of the ventilator, a fault indication is generated and the alarm relay is activated (default values). The temperature may be enquired by the interfaces.