AEG Thyro-P - page 43

Page 43

 

 

 

43

TERMINAL STRIP X5 IN THE CONTROL DEVICE

 

X5.1

FUNCTION

X5.2

FUNCTION

5

+5V

5

+5V

13

ground 5V

10

set point 1

13

ground 5V

11

set point 2

13

ground 5V

32

analog output 1

13

ground 5V

33

analog output 2

13

ground 5V

34

analog output 3

13

ground 5V

16

ASM input

21

-15V

17

GSE connection

14

ground 24V

12

RESET

14

ground 24V

15

controller lock

14

ground 24V

18

SYT9 connection

14

ground 24V

19

QUIT

20

+24V*

20

+24V*

* Loading: IX5.1.20 + IX5.2.20 + IX21.9 max. 80mA TAB. 19 TERMINAL STRIP X5

Terminal strip X6 in the control device

At the terminal strip X6, wiring between the control device A70 and the control cards A1, A3 and

A5 of the power section is performed by the works. Allocation of the terminal strip is as follows:

X6Name

11thyristor L1 neg.

12+5V

13thyristor L1 pos.

21thyristor L2 neg.

22+5V

23thyristor L2 pos.

31thyristor L3 neg.

32+5V

33thyristor L3 pos.

41input temperature sensor

42ground temperature sensor

TAB. 20 TERMINAL STRIP X6

Each thyristor is controlled by 20mA current supply switching to ground.

The ventilator monitor is connected to the terminals X6.41 and X6.42 in separately ventilated devices (..HF). The temperature of the power section is monitored using a PT 1000 temperature sensor. In case of overheating of the power section, for instance caused by outage of the ventilator, a fault indication is generated and the alarm relay is activated (default values). The temperature may be enquired by the interfaces.

Image 43