AEG Thyro-P 4.12 OTHER CONNECTIONS AND TERMINAL STRIPS

Page 42

42

In case of the Power Controller type 2P, the voltage transformers output the voltages L1-L2 and

L3-L1. To achieve a good resolution of the voltage measurement, 3 measuring ranges are provided. Selection of the ranges is performed by means of 4-pin bars, which have been set to the Power Controller type voltage by the works. The pin bars are found on the control device A70 above the terminal X7.

MAINS

SHORT CIRCUIT JUMPERS

MAX.

VOLTAGE

X501, X502, X503

MEASURING

230V

1 - 2

253V

400V

2 - 3

440V

500V respectively 690V

3 - 4

760V

TAB. 17 VOLTAGE MEASUREMENT JUMPER

If the jumpers are changed, then a change of parameters is required.

Hardware parameters

Type

voltage

U_TYP

U eff

max

UEMA

X501-3,1-2,2-3,3-4

TYP-BEREICH

Mains voltage

U_NETZ_ANW

 

 

(Thyro-Tool Family)

REMARK

Voltage readings in not-controlled phases

Thyro-P 2P

Although phase 2 is not controlled with Thyro-P 2P, it is possible to take measuring values during this phase. The voltage transformer suitable for standard rail assembly (order no. 2000000399) is to be used. Connection is made as in table 21 to X7.1.26 – X7.2.25. The maximum induced voltage of the transformer (incl. over-voltage) must be less than 50 volts.

Thyro-P 1P

As only phase 1 is controlled with Thyro-P 1P, the reading systems of phase 2 and 3 can be used freely. The voltage transformer suitable for rail assembly (order no. 2000000399) is to be used. Connection is made as in table 23 to terminals X7.1.26 – X7.2.25 for “phase 2” and X7.1.36 – X7.2.35 for “phase 3”.

The measuring values do not influence the controller and are available for Bus interfaces, display and analog outputs. Parameter values must not be changed.

4.12 OTHER CONNECTIONS AND TERMINAL STRIPS

 

ROOT*

BREAK CONTACT

CLOSER

Alarm relay K1

X2.7

X2.8

X2.9

Limiting K2

X2.10

X2.11

X2.12

Option K3

X2.13

X2.14

X2.15

* tie point

TAB. 18 TERMINAL STRIP X2 FOR K1, K2, K3

Image 42